when detection detects .. sprinkler not burst . Water want to enter into pipeline but it was filled with air so due to air water cannot enter into the pipeline.. in this stage how stage how air get release
Water will still enter the piping when the detection activates (this releases the solenoid to vent priming water). There will still be air but the system will start filling with water. Supervisory approval is normally around 10 PSI. The water will compress the air until the pressures equalize but the alarms will have activated by this point.
How the air release from pipeline once detection detect and sprinkler not burst
Air will release whenever sprinkler breaks
when detection detects .. sprinkler not burst . Water want to enter into pipeline but it was filled with air so due to air water cannot enter into the pipeline.. in this stage how stage how air get release
Water will still enter the piping when the detection activates (this releases the solenoid to vent priming water). There will still be air but the system will start filling with water. Supervisory approval is normally around 10 PSI. The water will compress the air until the pressures equalize but the alarms will have activated by this point.
thank you mr.Irfan
Thanks
Thanks
So what is the difference between a single and a double interlock system
Pls check this link Class 5 | Pre action sprinkler system
th-cam.com/video/r0BDk4UJXJg/w-d-xo.html