How & When To Charge LPH AND HP HEATER ll Thermal Power Plant Light Up Procedure Part 12

แชร์
ฝัง
  • เผยแพร่เมื่อ 7 ก.ย. 2024
  • Regeneration in Rankine Cycle
    With help of steam extracted from turbine , Increasing the temperature of condensate water (LPH) and Feed Water (HPH) is called regeneration system of Rankine cycle on which the thermal power plant is works`
    How to charge LPH
    After load of generator gets more than 25% of rated then we can charge the LP heaters
    step1 open steam vent of LPH vessel
    step 2 open drain to 100% and close the drip
    step 3 open extraction valve and when pressure gets more than lower heater pressure open the drip and close the drain watching water level of vessel
    step 4 close the vent of vessel
    HOW TO CHARGE HPH
    After load gets more than 40% of rated we can start charging HPH one by one
    step1 open steam vent of HPH vessel
    step 2 open drain to 100% and close the drip
    step 3 open extraction valve partially by inching and when pressure gets more than lower heater pressure open the drip and close the drain watching water level of vessel
    step 4 close the vent of vessel

ความคิดเห็น • 16

  • @samarmajumdar1008
    @samarmajumdar1008 ปีที่แล้ว +1

    Thank you, sir.

  • @worldinstrumentationengineer
    @worldinstrumentationengineer ปีที่แล้ว +1

    BAHUT ASSA GURU JI 🙏🙏 PRANAM

  • @amitmotorshow
    @amitmotorshow 2 หลายเดือนก่อน +1

    Sir drain kholne se pressure drop n hoga heater ka plz batiye

    • @BhagwanSRathore
      @BhagwanSRathore  2 หลายเดือนก่อน

      Water level maintain rahega to pressure drop nhi hoga

  • @amitmotorshow
    @amitmotorshow หลายเดือนก่อน

    Sir drip line... Niche wale heater m jakr heat exchange karta hai.... But niche heater ke liye to already extraction se steam jaraha hai.. To drip aur extraction dono se heat gain karta hai kya lower heater....... Plz guide🙏

    • @BhagwanSRathore
      @BhagwanSRathore  หลายเดือนก่อน

      Ha bcz upr heater ka drip high temp ka hota hai lagbhag us heater ke feedwater inlet ke temp ke barabar ye drip lower heater me heat release karta hai

  • @manohardhaker423
    @manohardhaker423 12 วันที่ผ่านมา

    Why LPH-1 given inside condenser

    • @BhagwanSRathore
      @BhagwanSRathore  12 วันที่ผ่านมา

      Turbine ex hood steam temp is higher so lph consumes this temp and lower to the temp near to condensate temp watch video for deep detail
      th-cam.com/video/7LsdLYPK-wk/w-d-xo.htmlsi=jvMdneos0u9QDdNg

  • @samlastseen
    @samlastseen ปีที่แล้ว

    Lp heater should be charged from extraction steam from higher pressure to lower pressure?

    • @BhagwanSRathore
      @BhagwanSRathore  ปีที่แล้ว

      No, lph always charged From lower pressure to higher pressure

    • @samlastseen
      @samlastseen ปีที่แล้ว

      Sir if it will be charged from low pressure to high pressure what may happen

  • @SuReShSaHu-lb9ik
    @SuReShSaHu-lb9ik 2 ปีที่แล้ว

    sir, why not charge the steam line in HPH first, why do we do water side first?

    • @BhagwanSRathore
      @BhagwanSRathore  2 ปีที่แล้ว +1

      If we charge from steam first then there will be no heat transfer happen in the heat exchanger and due to this the vessel get pressurized and the heat exchanger tubes gets stressed/strained so first we need to charge from water side first
      In every heat exchanger the cooling fluid should be charged first for avoid abnormal heating

    • @worldinstrumentationengineer
      @worldinstrumentationengineer ปีที่แล้ว

      Bahut assa guru ji🙏🙏