Solenoid valve (different types)
มุมมอง 2.3K2 ปีที่แล้ว
Different types of solenoid Valves and it's applications
Fisher DVC 6000 Positioner Internal Parts
มุมมอง 2.8K2 ปีที่แล้ว
Fisher DVC 6000 Positioner Internal Parts
Fisher DVC-6200 manual calibration
มุมมอง 10K2 ปีที่แล้ว
Manual calibration, Analog calibration, Digital Calibration
Operating Control valve with SOV
มุมมอง 7302 ปีที่แล้ว
Operating Control valve with external PID controller, 5/2 SOV, and LVDT.....
Temperature controller (Omron -E5CC)
มุมมอง 20K3 ปีที่แล้ว
basic parameters configuration, controller checking .
Metso ND-9000 Positioner basic settings
มุมมอง 11K3 ปีที่แล้ว
Metso ND-9000 positioner basic settings
Troubleshooting of Metso Positioner, ND-9000 series
มุมมอง 7K3 ปีที่แล้ว
Spool Jammed error, Removing spool block, checking and cleaning.
Concept of Digital Inputs Contacts (NO-NC)
มุมมอง 5404 ปีที่แล้ว
Concept of Digital Inputs Contacts (NO-NC)
Temperature Transmitter Compensation CJC, Cold junction compensation of thermocouple
มุมมอง 6K6 ปีที่แล้ว
Temperature Transmitter Compensation CJC, Cold junction compensation of thermocouple
Metso's Neles ND9000 Smart Positioner Calibration
มุมมอง 27K7 ปีที่แล้ว
Metso's Neles ND9000 Smart Positioner Calibration
Siemens PS2 Smart Positioner used as Remote Positioner
มุมมอง 6K7 ปีที่แล้ว
Siemens PS2 Smart Positioner used as Remote Positioner
Can you share your contact number
Smart Positioner Calibration video Please
full video of calibration please
Thanks 👍
Dear sir , How to reset password. Because we forget password.
Hello.,how to fix Error-03??
Sir please send me calibration video
Block ko kaise repering kare
Thank No 1, teach us ...
Sir magnetic assembly positioner me uski direction kaise rakhe
Feedback module?
Sir. 4 ma pe automatic fully open and close ho rha he contiue ! Problem solve kese kare ?
Auto calibrate Karo...you will get the error if any problem with the positioner...
what size resistor you used?
250 ohms
How to reverse the feedback of dvc 6200 positionet
Sorry, I never done ... and right now, I didn't have that positioner to check ..
How reverse the feedback of 6200 positionet
Acha hei…
Electro pneumatic volve video pl upload sir
Useful video
Useful video
Thanks bro, your videos helped us
Good
Dear how i can adjust fork lever bcz when i calibrated it error came 0002
Best practices are to give external air supply to actuator and open 50% and at that time, the positioner feedback link should be (horizontal -----------------)
Spool block se continue air passing ho raha hai wo kaise thik karege please btaye
If double acting actuator then check actuator passing and remove spool clean it and refix it....check the gasket once
Auto calibration option is not showing after going CAL option what is problem
If there is any error, you need to rectify that 1st ...
Facing an issue not powering up even after connecting power
Check the polarity once and remove one wire and check voltage in series, then you will know any problem with PCB ....
Looks like a very informative video. Too bad I don’t understand the language. Do you want to make the same video in English?
I will try ...thq u
Adjustment kaise karte hai.Agar scale me error aata hai to. Q k pneumatic me error aata hai to zero or span se adjust kar lete hain. Smart me kaise karte hain. Please reply.
Only you can adjust realy in 6200, other smart positioner having different options for little adjustments...ABB I/P can be adjusted... need to go through those instruments..
SOV & Volume booster ke work me kya difference hai.
Both are totally different 1. Volume booster used for large actuator for quick response or speed operation. (can be used in the control valve as well as in on/off valves ) 2. SOV are used for operating on/off valves and in some applications used to block the path (safety interlock)
BAHUT ASSA GURU JI
Thq you
Positioner is not taking Setpoint/ demand from remote DCS... Able to operate locally... What can be the issue
Keep positioner operating mode to 1.1 .. Check the feedback cable and current mA cable once ... Sometimes cable can be interchanged ...
@@instrumentationandsolution5013 checked in 1.1 it's working fine and also able to operate in local mode. Only in remote mode it's not operating. ps. it's a profibus PA device
Check the address in the positioner ..
What is sigma 1 & sigma 2? Is it like different totalizer readings? Is it same like trip A & trip B in cars?
I never used and zero sigma values are used for uneven/bad installation, vibration, air/gas bubbles in flow tube...
क्या कोई बता सकता है, दिल्ली की हवा में कितने प्रतिशत आक्सिजन है ?
Multi gas analyzer lagana hai Bhai ... Wo bohut costly hai... Pollution is going to increase everywhere 😔😔😔😔....
Output bias means???
Positioner output is not accurate as per a given signal ... So the controller checks given signal vs output or outcome of the signal ...
Trex communicator se lowercase letter kaise type karna hota hai specially unit change karne ke liye please btaye
The unit can be changed in basic setup or detailed setup,
sir i ues auto adjust and run 20 outlet no have any air come out how to do ?? can repair or no??
May I/P having issues... Check and Calibrate I/P... U can check my I/P checking and calibration Video once ...
@@instrumentationandsolution5013 I try use reset, still can not use . Always run 20 outlet no have any air come out
sir i ues auto adjust and run 20 outlet no have any air come out how to do ?? can repair or no??
U can adjust I/P... Plz check my I/P adjustment video...
Sir, The meter keeps running when the pump is in off position can you please solve this
If the flow tube is empty then sometimes the flow transmitter shows values.. earthing.. and external induction... Or flow converter/ transmitter having issue
Thank you sir for your valuable information 👍👍👍👍👍❤️❤️❤️
S N kaise change hoga?
What do you mean by S N..?
Serial Number kaise Change hoga pls sir
Very Good Video.
Sir your video is jabardast hai
Hello dear friend there is one resion in abb positinor that when we give comand 0 to 100 then going 0 to 50 direct
Not going 25 percentage going 0 to 50 ,75,100. And 100 to 75,50 ,and when giving 25 not going 50 to direct come 0
Check Parameter -3.0 minimum range should be zero% and maximum should be 100%, and what is the parameter selection of 2.0 and 2.2 ... If possible update me 2.0, 2.2 and 3.0 parameter...
Can I simulate 0 to 100% traveling by using TREX. Because before I already try. The % value we can send,but valve haven't move. Similar another positioner value we can send by using TREX, or another option in that positioner. So Pls clarify this.
U can do a manual stroke check with the local buttons ... It's very easy... Through hart also u can simulation.. if the positioner has any issue then it will not operate ...
Isko zero kaise kare
Check the zero trimming option, before doing zero ensure the outlet valve should close properly and the flow tube should be filled with process fluid...
Sir Mera abb ka positioner me output feedback nhi aa raha hai
AO feedback?
What we can do if position is already out of range
Out of range means ? .. positioner pot having issues or positioner mounting issue... Need to find out the exact issue..
Can you help me ?
What is the problem..
Working manual but not working with 4-20ma.
plz show the connection of the wire. we need urgent . can we replace this by the simple directional valve
U can't replace it with normal DCV ...I left that company, unable to show you wiring connection,
Nice video sir ji....isi tarah aur bhi video banaye...
Suppose valve is closed and positioner displays 100% then what we can do to display 0%
While installing a new positioner or maintenance problem or you want to change it
Thanks u sir
Sir aap density transmitter par video banaye na please