How to Rebuild HONEYWELL ZONE VALVE
How to repair Honeywell Zone Valve - Part number: V8043E1012 + V8043E1061
Honeywell Zone Valve Rebuild Kit: amzn.to/2LlDYVA
Honeywell Zone Valve: amzn.to/2Lk1ylP
NEST Thermostat - amzn.to/2Szw28y
NEST Carbon Monoxide + Smoke Alarm - amzn.to/37vdgmX
Fuel Pump Strainer: amzn.to/2QwkxiI
Wool Filter: 1A-30 : amzn.to/2EwFzYg
4 Pack Fuel FILTERS: amzn.to/2UNWfPR
Burner Coupling: amzn.to/2CgoIXl
Burner Suntec Fuel Pump: amzn.to/2Lj6ozx
Beckett Cleancut Fuel Pump: amzn.to/2BjieFo
Pipe Dope to seal fuel oil lines: amzn.to/2Gk28RG
Threaded Fuel line check valve: amzn.to/2Exy9Uy
Flared fuel line check valve: amzn.to/2EvMyk5
option #2 : Fuel oil Check Valve: amzn.to/2GtpwvU
Boiler Safety
3/4" NPT Male x Female: amzn.to/2UOJPaz
Boiler Safety
3/4" NPT Female: amzn.to/2QUF2oF
Loctite Anti Seize: amzn.to/2Bm1f5i
Pipe Dope to seal fuel oil lines: amzn.to/2QxZEDL
High Temp RTV: amzn.to/2CeZfNM
KO Wool Blanket: amzn.to/2S4N37M
1/2" Boiler Rope Gasket: amzn.to/2UOLPQ7
3/8" Boiler Rope Gasket: amzn.to/2BjisMK
Blower Motor: amzn.to/2UKvvQp
Burner Coupling: amzn.to/2UN4agh
Beckett AFG Electrodes + Transformer Kit: amzn.to/2S4ybGD
Burner Suntec Fuel Pump: amzn.to/2QXBli5
Beckett Cleancut Fuel Pump: amzn.to/2Bq0J6a
Fuel Pump Strainer: amzn.to/2Gg7T2z
Wool Filter: 1A-30 : amzn.to/2Ey0vhl
4 Pack Fuel FILTERS: amzn.to/2S2SAfi
Tools:
11 in 1 Screwdriver: amzn.to/2BnAvl3
Pump Rotation Tester: amzn.to/2UNWA55
Milwaukee Head Lamp: amzn.to/2LjmiKs
5 Gal Shop Vac: amzn.to/2Lj6JlN
5 Gal Soot Vacuum Bags: amzn.to/2ExyBlI
Small Wire Brush: amzn.to/2BlS6K6
Milwaukee 2462-20 M12 1/4 Hex Impact Driver: amzn.to/2S4Pg3p
Greenlee PVC Cutter: amzn.to/2LqSfkd
Boiler Brush: amzn.to/2UOBdAr
Basic - Caulking Gun: amzn.to/2QS0Hhv
Soot Saw: amzn.to/2Bxhi0r
((( Post your questions in the comments and remember to subscribe! )))
"WARNING" - Do not attempt to work on or disassemble any part of your HVAC System if you're not a Skilled Technician. You assume any and all responsibility. Working on HVAC Systems can be VERY DANGEROUS and should only be performed by Highly Trained Technicians.
Thank you for your watching our videos.
มุมมอง: 12 288

วีดีโอ

Service Call - Troubleshooting TOO COLD in HOUSE
มุมมอง 5863 ปีที่แล้ว
All Zone valve calling for heat and No power to circulation pump AquaSmart Control: amzn.to/3aXcJPI Alpha Circ Pump: amzn.to/3stXQKB ((( Post your questions in the comments and remember to subscribe! ))) "WARNING" - Do not attempt to work on or disassemble any part of your HVAC System if you're not a Skilled Technician. You assume any and all responsibility. Working on HVAC Systems can be VERY ...
How to replace Boiler Circ Pump
มุมมอง 2.8K3 ปีที่แล้ว
Step by step video to change out a BAD BOILER Circ PUMP. Alpha Pump: amzn.to/3stXQKB Turn off boiler power Drain boiler Unhook power to pump Remove bad pump Clean flanges Install new pump Hook up power to pump Refill system Remove Air from system Turn on boiler power and continue bleeding air and testing for good fluid flow ((( Post your questions in the comments and remember to subscribe! ))) ...
How to FIX Baseboard Leak
มุมมอง 12K3 ปีที่แล้ว
Fire Extinguisher leak in baseboard heater including Tools and supplies used in the repair process. TOOLS Milwaukee Copper Cutter: amzn.to/3ung16J Milwaukee Drill: amzn.to/37JeKNl Milwaukee Pen Light: amzn.to/3qVUD6s Bernzomatic Torch:amzn.to/2NASTRl Wire brush for drill: amzn.to/3qJWomZ Tape Measure: amzn.to/3kf7UEw Sheet metal cutter: amzn.to/2Nq3uid Reamer: amzn.to/2OYtHEM Needle nose pliers...
Installing T4 Pro Honeywell Thermostat
มุมมอง 70K3 ปีที่แล้ว
New Tstat install on 4x4 box. THERMOSTATS CO DETECTORS T4 Pro Thermostat: amzn.to/3k0RgIC NEST Thermostat - amzn.to/2Szw28y NEST Carbon Monoxide Smoke Alarm - amzn.to/37vdgmX BURNER PARTS Blower Motor: amzn.to/2UKvvQp Burner Coupling: amzn.to/2UN4agh Burner FUEL PUMP Suntec Fuel Pump: amzn.to/2Lj6ozx Burner FUEL PUMP Beckett Cleancut Fuel Pump: amzn.to/2BjieFo Beckett AFG Electrodes Transformer...
BAD BURNER FUEL PUMP
มุมมอง 22K3 ปีที่แล้ว
Step by step video showing how to replace a burner fuel pump. INTRO: 0:01 REPLACING BURNER COUPLING: 2:08 REPLACING FUEL PUMP: 3:13 INSTALLING BYPASS PLUG: 4:57 CHECKING FUEL PRESSURE: 7:55 HOW TO RESET BURNER: 8:45 RECAP: 9:17 BURNER FUEL PUMP: amzn.to/2Lj6ozx BURNER COUPLING: amzn.to/2UN4agh PIPE DOPE: amzn.to/2QxZEDL BURNER PARTS Blower Motor: amzn.to/2UKvvQp Burner FUEL PUMP Beckett Cleancu...
ABOVE GROUND FUEL TANK - HOOK UP
มุมมอง 2.7K3 ปีที่แล้ว
Setting up ABOVE GROUND Fuel Tank SPACE HEATER: amzn.to/37buUPm Pipe Dope to seal fuel oil lines: amzn.to/2QxZEDL Complete GOLDENROD FILTER: amzn.to/3d8BLNn GOLDENROD Spin on filter with water blocker: amzn.to/2ZgkBFy TOOLS RIDGID PIPE WRENCH: amzn.to/3jNJEsM Quick Reamer: amzn.to/3ajjHy7 Honeywell Zone Valve Repair Kit: amzn.to/2LlDYVA Honeywell Zone Valve: amzn.to/2Lk1ylP NEST Thermostat - am...
Zone Valve Troubleshooting - Honeywell V8043E1012 + V8043E1061
มุมมอง 24K3 ปีที่แล้ว
Found bad Honeywell Zone Valve Part number: V8043E1012 V8043E1061 Honeywell Zone Valve Repair Kit: amzn.to/2LlDYVA Honeywell Zone Valve: amzn.to/2Lk1ylP NEST Thermostat - amzn.to/2Szw28y NEST Carbon Monoxide Smoke Alarm - amzn.to/37vdgmX Fuel Pump Strainer: amzn.to/2QwkxiI Wool Filter: 1A-30 : amzn.to/2EwFzYg 4 Pack Fuel FILTERS: amzn.to/2UNWfPR Burner Coupling: amzn.to/2CgoIXl Burner Suntec Fu...
Boiler not firing - Burner Tripping OFF
มุมมอง 2.8K3 ปีที่แล้ว
Troubleshooting blower motor. Burner control tripping. BURNER PARTS Blower Motor: amzn.to/2UKvvQp Burner Coupling: amzn.to/2UN4agh Burner FUEL PUMP Suntec Fuel Pump: amzn.to/2Lj6ozx Burner FUEL PUMP Beckett Cleancut Fuel Pump: amzn.to/2BjieFo Beckett AFG Electrodes Transformer Kit: amzn.to/2S4ybGD Burner Coupling: amzn.to/2CgoIXl Beckett AFG Electrodes: amzn.to/3oZBqyM Z gauge: amzn.to/36YxGaD ...
Water in Fuel Filter
มุมมอง 1723 ปีที่แล้ว
Close up look at water in the fuel system FUEL FILTERS: Wool Filter: 1A-30 : amzn.to/2EwFzYg 4 Pack Fuel FILTERS: amzn.to/2UNWfPR Fuel Pump Strainer: amzn.to/2QwkxiI BOILER TUNEUP SUPPLIES High Temp RTV: amzn.to/3oVLTeH 1/2" Rope Gasket: amzn.to/3aErSnJ 3/8" Rope Gasket: amzn.to/2YNgccM KO WOOL High TEMP Strips Blanket, 2200F 1" x 1/2" x 300": amzn.to/3jq6J4s Loctite Anti Seize: amzn.to/2Bm1f5i...
BOILER CLEANING - FAST MOTION
มุมมอง 5703 ปีที่แล้ว
I tried to waste no time showing you how to clean an oil fired boiler system. Hope it helps! BOILER TUNEUP SUPPLIES High Temp RTV: amzn.to/3oVLTeH 1/2" Rope Gasket: amzn.to/3aErSnJ 3/8" Rope Gasket: amzn.to/2YNgccM KO WOOL High TEMP Strips Blanket, 2200F 1" x 1/2" x 300": amzn.to/3jq6J4s Loctite Anti Seize: amzn.to/2Bm1f5i Pipe Dope to seal fuel oil lines: amzn.to/2QxZEDL KO WOOL HIGH TEMP Blan...
How to change BURNER Fuel Filter
มุมมอง 8703 ปีที่แล้ว
Replacing burner fuel filter FUEL FILTERS: Wool Filter: 1A-30 : amzn.to/2EwFzYg 4 Pack Fuel FILTERS: amzn.to/2UNWfPR Fuel Pump Strainer: amzn.to/2QwkxiI BOILER TUNEUP SUPPLIES High Temp RTV: amzn.to/3oVLTeH 1/2" Rope Gasket: amzn.to/3aErSnJ 3/8" Rope Gasket: amzn.to/2YNgccM KO WOOL High TEMP Strips Blanket, 2200F 1" x 1/2" x 300": amzn.to/3jq6J4s Loctite Anti Seize: amzn.to/2Bm1f5i Pipe Dope to...
How to replace burner electrodes
มุมมอง 14K3 ปีที่แล้ว
Installing new burner electrodes in AFG Beckett Burner Beckett AFG Electrodes: amzn.to/3oZBqyM Z gauge: amzn.to/36YxGaD Electrode setting tool : AFG Burners with - F Heads: amzn.to/36Ko5UK Universal Electrode Setting Tool: amzn.to/2YTpVy5 High Temp RTV: amzn.to/3oVLTeH 1/2" Rope Gasket: amzn.to/3aErSnJ 3/8" Rope Gasket: amzn.to/2YNgccM KO WOOL High TEMP Strips Blanket, 2200F 1" x 1/2" x 300": a...
How to replace a pellet stove control board
มุมมอง 2.8K3 ปีที่แล้ว
Replacing bad control board on a pellet and Start Up. PELLET STOVE Parts: amzn.to/3p14bLj Rope Gasket Kits: amzn.to/3rsOTAF HVAC TOOLS Magnetic Flashlights: amzn.to/2YUQyml 11 in 1 Screwdriver: amzn.to/2BnAvl3 Milwaukee Headlamp: amzn.to/2LjmiKs 5 Gal Shop Vac: amzn.to/2Lj6JlN 5 Gal Soot Vacuum Bags: amzn.to/2ExyBlI Small Wire Brush: amzn.to/2BlS6K6 Milwaukee 2462-20 M12 1/4 Hex Impact Driver: ...
How to CLEAN a BURNHAM BOILER
มุมมอง 21K3 ปีที่แล้ว
High speed boiler cleaning BOILER TUNEUP SUPPLIES High Temp RTV: amzn.to/3oVLTeH 1/2" Rope Gasket: amzn.to/3aErSnJ 3/8" Rope Gasket: amzn.to/2YNgccM KO WOOL High TEMP Strips Blanket, 2200F 1" x 1/2" x 300": amzn.to/3jq6J4s Loctite Anti Seize: amzn.to/2Bm1f5i Pipe Dope to seal fuel oil lines: amzn.to/2QxZEDL KO WOOL HIGH TEMP Blanket: amzn.to/2S4N37M BOILER PARTS Blower Motor: amzn.to/2UKvvQp Bu...
HOW TO Replace BURNER NOZZLE - Beckett AFG Burner
มุมมอง 4.1K3 ปีที่แล้ว
HOW TO Replace BURNER NOZZLE - Beckett AFG Burner
-15 degrees (below zero) Troubleshooting Furnace
มุมมอง 1.1K3 ปีที่แล้ว
-15 degrees (below zero) Troubleshooting Furnace
20,000 VOLT BURNER IGNITION VS 10,000 VOLT BURNER IGNITION
มุมมอง 13K4 ปีที่แล้ว
20,000 VOLT BURNER IGNITION VS 10,000 VOLT BURNER IGNITION
How to fix a Honeywell Zone Valve. Part number: V8043E1012 + V8043E1061
มุมมอง 148K4 ปีที่แล้ว
How to fix a Honeywell Zone Valve. Part number: V8043E1012 V8043E1061
How to CHANGE FUEL FILTER on your BOILER or FURNACE
มุมมอง 4.7K4 ปีที่แล้ว
How to CHANGE FUEL FILTER on your BOILER or FURNACE
AFG Beckett Burner
มุมมอง 28K4 ปีที่แล้ว
AFG Beckett Burner
DANGER - SLOW MOTION Boiler Ignition
มุมมอง 7034 ปีที่แล้ว
DANGER - SLOW MOTION Boiler Ignition
Boiler Safety Valve
มุมมอง 5384 ปีที่แล้ว
Boiler Safety Valve
What's Inside a Fuel Oil Line Check Valve
มุมมอง 6K5 ปีที่แล้ว
What's Inside a Fuel Oil Line Check Valve
What's inside a burner nozzle!!
มุมมอง 7025 ปีที่แล้ว
What's inside a burner nozzle!!
GOT SOOT? Check out this Dirty Boiler!
มุมมอง 7956 ปีที่แล้ว
GOT SOOT? Check out this Dirty Boiler!
Tigerloop in Action - Video #15
มุมมอง 7K6 ปีที่แล้ว
Tigerloop in Action - Video #15
Suntec B2VA-8216 - BURNER FUEL PUMP
มุมมอง 96K6 ปีที่แล้ว
Suntec B2VA-8216 - BURNER FUEL PUMP
How to Clean a Boiler Heat Exchanger - Video #9
มุมมอง 51K6 ปีที่แล้ว
How to Clean a Boiler Heat Exchanger - Video #9
What's Inside a circulator Pump - Video #6
มุมมอง 2.7K6 ปีที่แล้ว
What's Inside a circulator Pump - Video #6

ความคิดเห็น

  • @foxtrottango8745
    @foxtrottango8745 4 วันที่ผ่านมา

    I never had a boiler before and am watching videos about them and baseboard heating before moving to Alaska. 👍👍 FJT.

  • @garymillerlcs
    @garymillerlcs 6 วันที่ผ่านมา

    Great explanation. Many thanks.

  • @nickotterstetter8343
    @nickotterstetter8343 หลายเดือนก่อน

    Should the fan blade spin freely while the pump is still connected?

    • @furnacetech2581
      @furnacetech2581 24 วันที่ผ่านมา

      Yes, there should be little resistance or binding. Most burners can be checked by Turning off power and lifting the ignition transformer cover. Spin the fan blade and see if it spins freely. If not, you may have a bad blower or fuel pump. If you replaced the coupling between the fan and fuel pump, be sure to check if it’s the correct length. If it’s too long, it will bind and not spin free!

    • @nickotterstetter8343
      @nickotterstetter8343 24 วันที่ผ่านมา

      Thanks for the reply. Had a child in June and while at the hospital our basement flooded. Had a furnace guy come out. He said the blower motor was still good but he couldn’t check the burner motor because my board fried and he didn’t have that style with him. I did buy a new board and a motor as the old one had froze up. Going to hook it back up tomorrow and give it a try

    • @nickotterstetter8343
      @nickotterstetter8343 24 วันที่ผ่านมา

      I also cleaned the tip that sprays the oil and the two electrodes as they were dirty

  • @aliafazeli2798
    @aliafazeli2798 หลายเดือนก่อน

    Thanks for your great video 👌

    • @furnacetech2581
      @furnacetech2581 24 วันที่ผ่านมา

      Thank you for watching

  • @OxenHandler
    @OxenHandler หลายเดือนก่อน

    Do the F turbinator heads always come off the nozzle assembly so easily? Loosen one screw and give it a wiggle and a pull? Are they all held on by friction alone?

    • @furnacetech2581
      @furnacetech2581 หลายเดือนก่อน

      Not all, I have had some tough ones.

  • @joshsmithward8848
    @joshsmithward8848 หลายเดือนก่อน

    Your helper is awesome. Thank you. Great content. Appreciate you sharing your expertise.

    • @furnacetech2581
      @furnacetech2581 หลายเดือนก่อน

      Thank you for watching

  • @MrRixsy
    @MrRixsy 3 หลายเดือนก่อน

    If I change the motherboard does it need programming ?

  • @bradc7254
    @bradc7254 4 หลายเดือนก่อน

    I have the same attachment foe my ash vac i use on my pellet stove except the bristles are a wire brush instead of plastic. Should work mint for doing my furnace. Isn't there a few other things like adjusting the fuel ratio and checking the co2 being released or something? And also ik you gotta use Chimney Sealant stuff, kinda like mortar around where the exhaust flue meets the actual chimney, also how frequently do i need to clean my actual chimney for my furnace? Idk if ive ever seen my plumber do that, he has however cleaned the exhaust flue that goes from the furnace to the chimney. And last question, also how do you adjust the oxygen ratio and air intake vent? Is there anything you even have to do there and if so how frequently?

    • @furnacetech2581
      @furnacetech2581 24 วันที่ผ่านมา

      Yes, there are many items to check when doing service and repairs. Mortar is perfect for connecting to chimneys for sure, just depends on the application or connections needed. It’s good practice to clean the chimney annually and inspect it for wear. Sometimes you may need to hire a chimney sweep company. Every burner is different when it comes to making air adjustments. Never adjust the air or fuel pressure without a combustion analyzer. Most adjustment locations are on the left or right sides of the burner. You will see makings with numbers which represent the current settings. You can loosen the set screws and slide the air bands or shutters. Make sure to tighten them after you make adjustments to get a good reading on your analyzer and don’t forget to make sure burner covers are in place during testing.

  • @Dave-wz8nv
    @Dave-wz8nv 4 หลายเดือนก่อน

    3 years later. What an excellent informative video. Thanks from the UK.

  • @user-vw8nh4dw2o
    @user-vw8nh4dw2o 5 หลายเดือนก่อน

    This a great video for that 'headache' thing. Thank you.

  • @johnmitchell3719
    @johnmitchell3719 6 หลายเดือนก่อน

    Hi what type of screws holds the motorized valve to the frame i tried a philips but i cannot get really tight.

    • @furnacetech2581
      @furnacetech2581 6 หลายเดือนก่อน

      I normally use a flat head

    • @johnmitchell3719
      @johnmitchell3719 6 หลายเดือนก่อน

      Thanks it was difficult to see flat worked great.

  • @4Fox59
    @4Fox59 6 หลายเดือนก่อน

    What happened to the programming link?

  • @Rysdad1
    @Rysdad1 7 หลายเดือนก่อน

    What is the large piece that you are working on that it's connected to called? Just called an oil burner?

    • @furnacetech2581
      @furnacetech2581 7 หลายเดือนก่อน

      The burner housing is the metal body that the fuel pump mounts to. The whole thing is the burner!

  • @ncooty
    @ncooty 7 หลายเดือนก่อน

    2 questions: 1. Why not use the common wire? 2. Why not mount the metal box cover to the box first, then the thermostat?

    • @furnacetech2581
      @furnacetech2581 7 หลายเดือนก่อน

      Thank you for watching and leaving your feedback! Most of our systems use only two wire setups. You can definitely use the common wire! I am sure there are many ways to mount a thermostat. This is just the way I did it for this project!

  • @tomclose6643
    @tomclose6643 8 หลายเดือนก่อน

    can i just leave zone valve head off and open up with that little handle so its getting hot water all the time when the other two zones call for heat?

    • @furnacetech2581
      @furnacetech2581 8 หลายเดือนก่อน

      Yes! It will heat if you manually open the valve!

  • @anthonyrosario7841
    @anthonyrosario7841 8 หลายเดือนก่อน

    Hi I got a question for you I have smoke coming out of the oil burner and I have oil leaking under de oil burner as well is that has to be with the oil pump or I will have to replace the entire oil burner.

    • @furnacetech2581
      @furnacetech2581 8 หลายเดือนก่อน

      You may have a fuel leak on the nozzle assembly or fuel line! Be careful it does not start a fire.

  • @GreenEarth140
    @GreenEarth140 8 หลายเดือนก่อน

    TRULY , a fantastic explanation about a zone valve. Excellent.

  • @dgmenace73
    @dgmenace73 8 หลายเดือนก่อน

    Thanks for the detailed video.....I just purchased some Beckett electrodes and they along with the old set have what looks like a butt connector to attach the length electrodes ends to match the others. The instructions don't say to crimp them or anything

    • @furnacetech2581
      @furnacetech2581 8 หลายเดือนก่อน

      I am not sure exactly what you are referring too. I know the electrodes come in many different designs. Most of the ones I run into, I cut to length or screw them together and then cut off excess. Some I am able to get the exact lengths. I know there is one type that I have come across that pushes together. I am sorry my reply is not much help!

    • @dgmenace73
      @dgmenace73 8 หลายเดือนก่อน

      @furnacetech2581 no apology necessary. I appreciate any advice. These electrodes have two lengths of rods that have a metal "coupler" that does push on but its very loose. I figure you're supposed to crimp them to make tighter? The old & new set both have the same "coupler". If this helps any, let me know your thoughts. Thanks

  • @akeyrecords5517
    @akeyrecords5517 8 หลายเดือนก่อน

    What spray were you using to clean it ?

    • @furnacetech2581
      @furnacetech2581 8 หลายเดือนก่อน

      Carburetor Cleaner works great to clean electrodes!

  • @christinemao9986
    @christinemao9986 8 หลายเดือนก่อน

    Thanks for this video! My problem is I cant not move that level freely and it seems like stuck in the middle while I can still feel the motor is hot. What do you think could cause the problem? Do I have to call the strata to replace the whole thing? Thanks

    • @furnacetech2581
      @furnacetech2581 8 หลายเดือนก่อน

      I would remove the powerhead off the valve body and check if the valve is stuck. If it’s stuck, then the internal valve parts need to be replaced. They sell rebuild kits. You can check this video’s description for a parts link if you have the ability to do it yourself!

    • @christinemao9986
      @christinemao9986 8 หลายเดือนก่อน

      Thanks!@@furnacetech2581

  • @TroyD-vo1bz
    @TroyD-vo1bz 8 หลายเดือนก่อน

    A question for you about bearing noise. I have a two-year-old furnace, and I'm hearing some pretty bad-bearing noise coming from around the fuel pump. At this point it's intermittent. I thought originally it was coming from the blower motor but upon closer examination, it's coming from around the Motor or the fuel pump. I'm assuming there are several bearings in and around the motor and fuel pump. Which do you think would be most likely to fail after just a couple of years? I've actually had furnaces 10 plus years old and never had bearing issues before, but this noise Is fairly loud and can be heard from 10 feet away.

    • @furnacetech2581
      @furnacetech2581 8 หลายเดือนก่อน

      I would remove the coupling between the blower and the fuel pump and test the blower motor. See if the noise goes away or not.

  • @watr77222
    @watr77222 9 หลายเดือนก่อน

    Hi, how would you suggest detecting location of heating pipe for baseboard water heater behind wall? Former owners severed the pipe in the boiler room for the basement. Thanks!

    • @furnacetech2581
      @furnacetech2581 8 หลายเดือนก่อน

      That’s a tough one! My best suggestion would be to start where the end of the baseboard run is located and work from there. You can cut small inspection holes to limit damages. I hope this helps

  • @michaelkatzenbach9478
    @michaelkatzenbach9478 9 หลายเดือนก่อน

    Are you adding a fill gauge

    • @furnacetech2581
      @furnacetech2581 8 หลายเดือนก่อน

      No, just fill cap, vent and supply line!

    • @michaelkatzenbach9478
      @michaelkatzenbach9478 8 หลายเดือนก่อน

      @@furnacetech2581I don’t understand the customer won’t know how much fuel is in the tank to order more fuel plus this tank is set on snow when the snow melts the tank will be off pitch. And don’t they have to dig that broken tank up and clean the spill. Are they filling that tank with kerosene or #1 fuel with temperature that low and lower. And with a bottom draw aren’t you going to draw moisture and sludge and possibly plugging the filter

  • @paulallen-01
    @paulallen-01 9 หลายเดือนก่อน

    I don’t miss these times of having to wear a mask in customer homes even though I always took mine off on e the customer left me alone in their boiler room. Anyway I stopped using pipe dope and know use Blue Monster anti-seize that’s rated for solvents and all fuels and I’ve had great success with it.

    • @furnacetech2581
      @furnacetech2581 8 หลายเดือนก่อน

      Thank you for the tip!

  • @bigpardner
    @bigpardner 9 หลายเดือนก่อน

    Does the higher voltage of the igniter improve combustion? Does it tax the ceramic insulation of the electrodes?

    • @furnacetech2581
      @furnacetech2581 9 หลายเดือนก่อน

      Stronger spark which help to ignite. The combustion is improved by adjust the fuel and air mixture using combustion tuning equipment. As for the electrodes, not 100% sure and every system is different because the controller may or may not turn off the spark after ignition had been established! I hope this helps!

  • @larchman4327
    @larchman4327 9 หลายเดือนก่อน

    My furnace quit today tried new filter. Ended up taking off b2va suntec pump and the pump shaft just came out of the pump thats not supposed to happen right. Any input appreciated.

    • @furnacetech2581
      @furnacetech2581 9 หลายเดือนก่อน

      Replace the pump and coupling together and you should be good to go!

    • @larchman4327
      @larchman4327 9 หลายเดือนก่อน

      @@furnacetech2581 OK will do. Gotta stay warm because fairbanks is a little cold in the winter.

  • @joecardenas8723
    @joecardenas8723 10 หลายเดือนก่อน

    Hi Mister Great video. I like to know what cause bleeding every 3 days? I replaced my single stage. Thank you

    • @furnacetech2581
      @furnacetech2581 9 หลายเดือนก่อน

      If you have a leak in the fuel line, it can cause the system to need bleeding after extended periods off time.

    • @joecardenas8723
      @joecardenas8723 9 หลายเดือนก่อน

      @furnacetech2581 I'll be check. Thank you so much

  • @minimule1
    @minimule1 10 หลายเดือนก่อน

    Hi there great video . I have a question because it getting cold and my furnace is not working. I have air comming out of the inlet filter on the side of the blow motor . Does this mean the motor is running backwards? The air is comming out of the filter where you adjust the air flow going into the burner head it that makes sense . My burner is a Beckett . I furnace runs but not well . I have changed everything from the control unit , nozzle,new igniter box. I thought the air was supposed to go into the burner head from the side where the adjuster ring goes. Should I change the direction of the blower motor ?

    • @furnacetech2581
      @furnacetech2581 10 หลายเดือนก่อน

      I have never seen one spin backwards. I wish I was there to see what you were talking about.

  • @kyledc6402
    @kyledc6402 10 หลายเดือนก่อน

    I'm curious if have 5 zones everything in 4 work fine the 5th is my garage it is always calling for heat even when the tstat is off. If the zone valve is set to auto but I'm curious if it is somehow stuck to open would that be why the zone is always calling for heat?

    • @furnacetech2581
      @furnacetech2581 10 หลายเดือนก่อน

      Yes, it could be stuck open for sure! If there is no power going to the zone valve, you can remove the powerhead and check it. The valve body stem could be stuck too so try rotating the stem too!

  • @willrise3980
    @willrise3980 10 หลายเดือนก่อน

    hi, is this installation is for heater only

    • @furnacetech2581
      @furnacetech2581 10 หลายเดือนก่อน

      yes, if you would like to hook up cooling or a fan, you would need to connect the (Y) & (G) wires to the tstat as well. I was only needing heating when i created this video.

    • @willrise3980
      @willrise3980 10 หลายเดือนก่อน

      @@furnacetech2581 can u make a video on how to connect heater and air conditionin

  • @TheDrewflav
    @TheDrewflav 10 หลายเดือนก่อน

    Did you have to drain whole boiler system line prior to cutting copper radiator??

    • @furnacetech2581
      @furnacetech2581 10 หลายเดือนก่อน

      No, I have isolation valves in each heating loop.

  • @jamesg5700
    @jamesg5700 10 หลายเดือนก่อน

    Very helpful video, thank you! Like another viewer, I now think I can fix my defective valve myself. ✅☺️

  • @joshfinkler6516
    @joshfinkler6516 11 หลายเดือนก่อน

    this video was PERFECT for helping me troubleshoot my honeywell zone valve problem, also gave me the confidence to do it myself. just got everything put together and tested and back to normal operations in plenty of time for winter. thanks for making this video!

  • @bigpardner
    @bigpardner 11 หลายเดือนก่อน

    It's been a couple years since I did this, but it would have been nice if they had put a note/warning with the pump that it was full of oil. Made a bit of a mess. I also had to put the pump in a vise and use a breaker bar to get the plug out for the fuel line. Made in France I recall. Has run like silk since putting the CleanCut pump with solenoid to replace the previous.

  • @Stacks2031
    @Stacks2031 ปีที่แล้ว

    Great job if you don’t mind me asking how long did it take you to disassemble , clean and reassemble?

    • @furnacetech2581
      @furnacetech2581 11 หลายเดือนก่อน

      It varies based on how dirty the boiler is! Plus if you have all the supplies/parts organized while doing the service. Normally takes between 2hrs and 3.5hrs for me.

  • @andersonandrew112
    @andersonandrew112 ปีที่แล้ว

    Are you in Anchorage? I have six of these at my apartment building, and I've had to have 14 motors replaced in 2 years. Either failure to open or failure to close. The plumber only hooks up the two yellow wires, leaves the red ones disconnected. Could that cause problems?

    • @furnacetech2581
      @furnacetech2581 8 หลายเดือนก่อน

      The red wires are used if the controls need to know when the valve is calling. I would check the valve body if it’s moving freely because if not, the motor may be working too hard and failing. I hope this helps! I am located in Fairbanks and North Pole!

  • @asiakevin
    @asiakevin ปีที่แล้ว

    Thank you

  • @jeffreyjohn2037
    @jeffreyjohn2037 ปีที่แล้ว

    How many years of training does it take to be certified?

  • @elizabethabar2011
    @elizabethabar2011 ปีที่แล้ว

    I need help with mine that looks like this! I’m so sick of hearing I need a whole new boiler system because no one can find this pump

    • @furnacetech2581
      @furnacetech2581 ปีที่แล้ว

      Pumps are not too hard to find! Even a new system will need the correct sized pump. Do you have the pump model?

  • @HonestDiner-cz4op
    @HonestDiner-cz4op ปีที่แล้ว

    Could you have done that repair with a ProPress?

    • @furnacetech2581
      @furnacetech2581 ปีที่แล้ว

      I don't see why not. I just don't use ProPress personally.

  • @JS-go1gu
    @JS-go1gu ปีที่แล้ว

    Satisfying!

  • @AlexisGuay-i4s
    @AlexisGuay-i4s ปีที่แล้ว

    Why is it just for hot water could we not put this on a cold water system??

  • @zoots15
    @zoots15 ปีที่แล้ว

    Does isolating the valve by turning off supply and return eliminate the system pressure when you pull off the old plate? Thanks for the video

    • @furnacetech2581
      @furnacetech2581 ปีที่แล้ว

      Yes, if you isolate the supply and return lines, you can slowly loosen the old plate. Place a bag or something to catch the fluid. Take your time because it can have a bit of fluid trapped in the lines.

    • @zoots15
      @zoots15 ปีที่แล้ว

      @@furnacetech2581 Much appreciated 👍

  • @iwktwom
    @iwktwom ปีที่แล้ว

    As soon as I turn on the boiler there is a call for heat, even though the heating is off at the program box. The hot water works normally just the heating is messed up. Do u think just replacing the metal box would work to fix the heat so it could be called when needed?

    • @furnacetech2581
      @furnacetech2581 ปีที่แล้ว

      The first thing I would check is the end switch. If the end switch is closed, then the boiler will get a signal to run the pump. Some boilers will turn on just to maintain minimum temp.

  • @gerardcianci582
    @gerardcianci582 ปีที่แล้ว

    Is there a way I can get a stuck open valve manually closed until I get a new one?

    • @furnacetech2581
      @furnacetech2581 ปีที่แล้ว

      Yes, there are a couple ways. Turn the thermostat off in that space, then remove the zone valve cover and take a screwdriver to see if you can move the linkage to free it. The spring should drive it closed. The other way is to turn off the thermostat in that zone and then close off one of the valves on that zone. I hope this helps!

  • @pulseharborwellness
    @pulseharborwellness ปีที่แล้ว

    Great! very helpful

  • @johnc6157
    @johnc6157 ปีที่แล้ว

    Very informative. Thank you.

  • @rene5313
    @rene5313 ปีที่แล้ว

    Ive been having trouble with my bekett burner. Ive trouble shooted everything i could think of and cant figure out the issue. My blower fan is not kicking on when i turn on the heat switch. It will kinda of turn on but get stuck then it trips my breaker. Do you think it could possibly be the fuel pump? Or something electrical? When i trouble shoot the motor blower alone without being assembled it works normal but when i place it into the shaft it looks like it gets stuck. Id appreciate the help. Thanks!

    • @furnacetech2581
      @furnacetech2581 ปีที่แล้ว

      You should be able to spin the fuel pump by hand. If you can, the blower motor may be going bad! That’s where I would start. I hope this helps!

    • @rene5313
      @rene5313 ปีที่แล้ว

      @@furnacetech2581 figured out the problem the next day. It was the fuel pump. The shaft inside the fuel pump was stuck causing my motor blower to get stuck. I changed out the fuel pump and it started working like a champ! I appreciate your videos I've learned so much. Thanks

    • @furnacetech2581
      @furnacetech2581 ปีที่แล้ว

      @@rene5313 That's Great news!

    • @anthonyrosario7841
      @anthonyrosario7841 8 หลายเดือนก่อน

      Hi I’m having issues with my oil burner. I keep getting smoke coming from the oil burner and the oil burner is leaking under. If you can give me an advise I will be so appreciate.

  • @rwpeter12
    @rwpeter12 ปีที่แล้ว

    I have just replaced my Honeywell motor head. I must have an older style as there are no screws holding it to the valve body. It is only held on with a wire clip. The issue I’m having is that when the thermostat calls for heat the motor head comes disengaged and does not open the valve. If i put pressure on the motor head towards the valve body it will engage properly.

    • @furnacetech2581
      @furnacetech2581 ปีที่แล้ว

      I am sorry for the late response. I would probably replace the zone valve unless you find another solution

  • @cahjavra
    @cahjavra ปีที่แล้ว

    thank you !