ความคิดเห็น • 130

  • @justme5384
    @justme5384 หลายเดือนก่อน +19

    We have an electric supply house that is open with staff mo-fri 7-16 and outside that it's a self service. You of course have to register in advance and get an access card to use that service. And there are CCTV all over that place

  • @geerjonk2314
    @geerjonk2314 หลายเดือนก่อน +32

    I noticed a lot of frozen waterdrops on the ceiling in the walk-in freezer. It usely indicates that the defrost-end temperature setpoint is to high. The heating elements will stay on way to long resulting in boiling/steaming the water in the evaporating coil. The steam wil condensate again on the ceiling. A bad functioning drain is also an extra cause of to much water remaining in the drainpan.
    Greeting from the Netherlands 🇳🇱

    • @johnbell6956
      @johnbell6956 หลายเดือนก่อน +4

      I have also found that too many defrost cycles will cause the fan shrouds to ice and droplets on the ceiling around the evaporator.

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน +2

      That is something I've run across as well in the past.

    • @Rollerguitar96
      @Rollerguitar96 หลายเดือนก่อน +3

      i agree with everything the fellow dutch said :). Drops Usually means a too high Defrost-endtemperature. it could also be that the dripping time (time after defrost before the metering device starts opening up) is a bit too long. or if its not regulated on End-temperature it could be that the End-time is too long. other thing could be too many defrost cycles per day.
      Defrost is individual for every location and takes time. sometimes its really tedious to fine-tune.
      Greetings from Switzerland😊

  • @user-bz8dq5ld6w
    @user-bz8dq5ld6w หลายเดือนก่อน +9

    I always replace those with EC5408E motors and then use a 5140C fan blade set. Still the same equivalent "wattage" range, but a lot lower cost motor. Just have to cut the plug as someone else said.
    Thank you for the always great videos!

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน +2

      Great tip!

  • @kens.3729
    @kens.3729 หลายเดือนก่อน +13

    You are getting the Customer back up and Running because GOD knows Food and/or Booze is Expensive and especially with the Inventory they carry. Nice Repair. 👍🙏

  • @garylankford9306
    @garylankford9306 หลายเดือนก่อน +2

    I am watching this video right now and I work sales at a refrigeration parts house - I am sitting here on Saturday waiting for the tech that called me in to get here. 😁
    I've been the tech - I like this side of the counter just fine.

  • @christianairikainen9820
    @christianairikainen9820 หลายเดือนก่อน +4

    in Sweden we also have 24/7. There you enter with, for example, a mobile phone with personal identification as security. So no one needs to come to the location to open. Some companies have through their app and personal identification we have in the phones.

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน +1

      That's a neat idea

  • @kg4muc
    @kg4muc หลายเดือนก่อน +7

    Customer should appreciate you catching the dirty condenser and failing contactor Could save them in overtime repairs later😊

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน +1

      I like to think they appreciate it greatly

  • @jshelby78
    @jshelby78 หลายเดือนก่อน +17

    Great video, Chris! That customer should be doing PM for sure

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน +3

      Thanks bud

    • @craigmills6275
      @craigmills6275 หลายเดือนก่อน +3

      You are absolutely right. but as we all know, a lot of companies that will do “preventative maintenance” schedules don’t do a single thing out side of spraying the coil and changing the filters. The customer would be lucky if they even tightened the belts up. On exhaust fans, RTUs, walk in, reach ins, etc. I know guys that wouldn’t check a single thing if a unit was making temp. I do understand why some restaurants pass on setting up a PM schedule. They can afford it and there is more work for the real refrigeration techs. But so frustrating getting a call at 4 on a Saturday with a walk in freezer.

    • @suezq74
      @suezq74 หลายเดือนก่อน

      @@HVACRVIDEOS Hello HVACR videos it’s me Riley once again! Remember me for my knowledge in HVAC? And my thoughts on your video is: it freezes itself up and it gets its own supply house! - Riley (use my name, Riley as i’d like it)

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน +1

      When the budget is already tight it is difficult to allocate funds to a PM contract when the contractor in question didn't provide any actual value to that customer.

    • @suezq74
      @suezq74 หลายเดือนก่อน

      @@HVACRVIDEOS do you remember me Riley? I’m the one who understands HVAC like short cycling

  • @jonleiend1381
    @jonleiend1381 หลายเดือนก่อน +5

    Do you ever give an I am already on the roof with my tools quote and a Saturday night at 9:pm quote? LOL

  • @dkd1228
    @dkd1228 หลายเดือนก่อน +8

    You are the supply house's bread and butter. Good that they were responsive to your needs.

    • @jin8684
      @jin8684 หลายเดือนก่อน +5

      Sorry to say, but the parts houses have way bigger clients than Mr. HVACR Videos. They open because they charge him around $150 extra to open up.

    • @bensreferigeration
      @bensreferigeration หลายเดือนก่อน

      @@jin8684 It used to be the on call guy got to keep that opening fee. Not sure if still like that, but counter guys always happy to open weekends to make that extra money.

  • @zidane2k1
    @zidane2k1 หลายเดือนก่อน +2

    Think it's been a while since we've seen a filthy condenser being cleaned. Didn't look like it had the super chunkers that you show us sometimes, but it was still very satisfying seeing all the dirt wash away!

  • @WswRefrigeration
    @WswRefrigeration หลายเดือนก่อน +7

    That’s why I installed HEATCRAFT equipment when I have the choice of . Those Russel motors are dumb. Those 3 motors you replaced plus service call etc is the price of a new coil or close to it

  • @kat2641
    @kat2641 หลายเดือนก่อน +3

    I am that way it hast to be a life or death situation before I call the SH for parts.. I’ll even try to rig up anything to get by for 24 hours but sometimes we don’t have a choice!!!! ❤

  • @sherwinalvarez7365
    @sherwinalvarez7365 หลายเดือนก่อน +4

    So.... the D1126 doesn't fit in there. I was keeping an extra blade in case this happened. Oh, 35W motor. The one i have is way too big.
    Great video thanx for sharing.

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน

      Thanks for the info

  • @freefunky830
    @freefunky830 หลายเดือนก่อน +2

    That allied location is pretty good

  • @helmsajr
    @helmsajr หลายเดือนก่อน +2

    The big picture always works great job Chris.

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน +1

      Yes it does!

  • @gregmercil3968
    @gregmercil3968 หลายเดือนก่อน +2

    I worked out in our OC location for over a year up until recently, and had no idea that there was an Allied in Tustin. None of my coworkers there even mentioned it. I looked it up, it’s not far from the Trane Supply on Redhill, which I’ve been to a bunch of times.

  • @hmrody
    @hmrody หลายเดือนก่อน +5

    You missed your calling 😂. "Oh, yeah, look at that... It's coming through like chocolate milk... Nice and dirty... Yeah... I'm gonna get two hands in here... Nice and through". If you dropped your voice a few octaves, get a little Barry White action going... I am thinkin' that would work for ya 😜. Great video and just messin'

  • @zekenzy6486
    @zekenzy6486 หลายเดือนก่อน +1

    Great video. Thank you for sharing

  • @LilyRoseElectric
    @LilyRoseElectric หลายเดือนก่อน +2

    Handled it... I use Allied as we'll in Tustin 🎉

  • @brianmcdermott2430
    @brianmcdermott2430 หลายเดือนก่อน +1

    Good work, Chris. Thank you.

  • @chap3845
    @chap3845 หลายเดือนก่อน +2

    Better man than me... They would have gotten 2 pieces of cardboard over those dead motors and I'd see them monday. If it was a good customer I would of moved the working motor to the middle and de iced it 😂

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน +1

      In some situations that would be fine as well

  • @TheChipmunk2008
    @TheChipmunk2008 หลายเดือนก่อน +2

    i was going to ask what opening a supply house was, but you answered it.. also, the phrase is nip it in the bud, not in the butt lol

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน +5

      I know but it drives you all nuts and makes me laugh when I say it wrong…..

  • @johnwalker890
    @johnwalker890 หลายเดือนก่อน +1

    Good job Chris......

  • @oscalerup1129
    @oscalerup1129 หลายเดือนก่อน +2

    I’ve had to replace two of those motors. Opened up the old ones both had obvious moisture damage. If it’s a real problem I wonder if a film of silicone around that seam would help them last longer, one looked like the water came in through the wire hole but it had been so long since I replaced it couldn’t tell you witch way it was mounted.

  • @PleaseExplainMe
    @PleaseExplainMe หลายเดือนก่อน

    There in Europe we use motor starters on compressors, so in the case of single phasing, the compressor shuts off, instead of waiting for a thermal overload in the compressor, and risking of burning up the compressor.

  • @Alexelectricalengineering
    @Alexelectricalengineering หลายเดือนก่อน +4

    Great video 👍👍

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน +1

      Glad you enjoyed it

  • @ivoryjohnson4662
    @ivoryjohnson4662 หลายเดือนก่อน +2

    If you have a down site you gotta do what you gotta do. The customer needs to be running and is willing to pay the costs .

  • @fshn76
    @fshn76 หลายเดือนก่อน

    I really like your videos when you’re cleaning a coil. It’s my zen spot. Nothing better looking then a clean coil rather it is a condensor or evaporator. Hopefully you’re doing well. Thanks for another good video.

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน +1

      Thanks for watching

  • @Kardall
    @Kardall หลายเดือนก่อน +3

    What is a 'regular maintenance schedule' on average for companies like this or ones with say one or two walk-in freezers, maybe stove/cook top air vents and what not? When you negotiate as a maintenance schedule with a company, would you say you do a job for X amount of dollars which would be inspection and any cleaning/belt maintenance every 4 months or something? Or is it more of a (every refrigeration unit is once every 2 months, every oven vent would be once every 5 months)? Just curious as to why people don't have maintenance schedules with some contractor. You seem to come across a lot of companies that don't do it, and when it fails they get massive bills that may exceed what they may have spend on the maintenance itself.

  • @DANGERTIM112
    @DANGERTIM112 หลายเดือนก่อน +5

    Why isnt it common to use motor-starter contacters with thermal block on them for compressors? so it can lock itself out incase it single-phases and prevent the compressor from burning out.

    • @richodude2679
      @richodude2679 หลายเดือนก่อน +1

      @@DANGERTIM112 there are also phase protection relays which will cut power if all the phases are not there.

    • @WilliamHaggerty
      @WilliamHaggerty หลายเดือนก่อน

      A lot of these compressors seem to have thermal overload built in, that usually negates a proper motor starter.

  • @ItsallabouttheRack
    @ItsallabouttheRack หลายเดือนก่อน +1

    I work for United Refrigeration. We do have a replacement that is less expensive, that we buy from the mfg, but nothing "generic" to replace it as of this time.

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน +1

      Yeah a few people have reached out and gave me the part number, it’s literally the same motor but 400 dollars cheaper… it’s still gonna fail in a year or so but at least it’s cheaper

    • @reynanmegx23
      @reynanmegx23 หลายเดือนก่อน +1

      ​@@HVACRVIDEOSNo it's not, I've used it, last longer time and EC Motors on WI Freezers dont last long because moisture gets in there and freezes the motor.

  • @chrisgamecave
    @chrisgamecave หลายเดือนก่อน +4

    I may or may not have "protected" my face when he said it shouldn't blow up lol

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน

      You have great instincts my friend

  • @kdoggie90
    @kdoggie90 หลายเดือนก่อน

    I'm debating on plumbing or hvac...it seems more electrical and diagnostic stuff goes into hvac in comparison to plumbing.

  • @joshua.sookoor20
    @joshua.sookoor20 หลายเดือนก่อน +1

    Hi Chris love ur videos! They should really do proper maintainence that condenser was dirty! I learn so much from ur videos great job man.!

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน

      I appreciate that

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC หลายเดือนก่อน

    Wish more places would take maintenance more seriously...the fan motors were legit...and so was opening up the supply house. Kinda sucks to have to do maintenance related things on weekends. As an owner I'm sure it's easy money....as a tech...its irritating to have to leave home to wash coils. Chris is someone who understands it from both angles. We have started replacing contactors with SSR's. Not in everything, but much more frequently.

  • @thesilentonevictor
    @thesilentonevictor หลายเดือนก่อน

    Great tech work chris customer should be happy

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน

      Thanks 👍

  • @albertoramirez4203
    @albertoramirez4203 หลายเดือนก่อน +1

    I put a 16 or 25 watt ccw Unit bearing watt motor

  • @DFxDesignz
    @DFxDesignz หลายเดือนก่อน +1

    I have been using the rescue ecm motors from RSD. I cut off the 2 prong plug and wire it in without the relay. Been working for me on emergency calls, those oem ecm motors are just insanely expensive

    • @WswRefrigeration
      @WswRefrigeration หลายเดือนก่อน

      Part number?

    • @DFxDesignz
      @DFxDesignz หลายเดือนก่อน

      @WswRefrigeration along the lines of EC5414E depending on wattage

    • @WswRefrigeration
      @WswRefrigeration หลายเดือนก่อน

      @@DFxDesignz that’s what I thought. I have the 5412e on the van. I’m pretty sure that one will work as it’s cw se

    • @DFxDesignz
      @DFxDesignz หลายเดือนก่อน

      @@WswRefrigeration they have been working great for me

  • @ionnuone8883
    @ionnuone8883 หลายเดือนก่อน +1

    So this video was made on my birthday 🥳👍

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน +1

      Happy Birthday

    • @ionnuone8883
      @ionnuone8883 หลายเดือนก่อน

      @@HVACRVIDEOS Thanks a lot! 🥳👍

  • @ThePowerofElectricity
    @ThePowerofElectricity หลายเดือนก่อน

    With how the left condenser fan motor stopped, it's probably on it's way out too. That plus the lubricant that seeped out of the bearing...

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน

      I would have to agree

  • @karnvir3542
    @karnvir3542 หลายเดือนก่อน +1

    Ec 5414e dual voltage and reversible rotation for these units if you are only running one speed sir

  • @carloshilarionvazquezaranda
    @carloshilarionvazquezaranda หลายเดือนก่อน +2

    Otro excelente trabajo mi estimado Chris, es muy importante todo lo que haces así te anticipas a fallas futuras, una estupenda manera de enseñar a cómo se debe tratar a los clientes seguiré firmemente tú forma de trabajar y te lo agradezco.
    Tengo unas dudas:
    Russell es la marca de los motores?
    Que significa OEM?
    Cuál es la bobina AA?
    También que significa PSC.
    Muchas gracias por todo tú tiempo, saludos desde Coacalco Edo de México.

    • @germanespinal7672
      @germanespinal7672 หลายเดือนก่อน +1

      OEM en ingles significa 'Original Equipment Manufacturer' en español seria 'Fabricante original de equipo'

    • @germanespinal7672
      @germanespinal7672 หลายเดือนก่อน +1

      Y si, Russell es el Fabricante de los motores que el uso

    • @carloshilarionvazquezaranda
      @carloshilarionvazquezaranda หลายเดือนก่อน +1

      Muchas gracias amigo Germán son dudas que me resuelves y aclaras.
      Saludos 🤗

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน +1

      Hola, Russell es la marca de la evaporada no de los motores. OEM, significa original equipment manufacturer y PSC significa Permanent Split Capacitor, ese es un motor que neccisitas un capacidor

    • @carloshilarionvazquezaranda
      @carloshilarionvazquezaranda หลายเดือนก่อน

      @@HVACRVIDEOS
      Muchas gracias por todo mi estimado Chris.
      Dudas concluidas gracias a todos.

  • @drewthornton4684
    @drewthornton4684 24 วันที่ผ่านมา

    Hey Chris have you thought of using Gloves to keep your hand warm in the Freezers

  • @rogerghiardi7723
    @rogerghiardi7723 หลายเดือนก่อน +1

    OMG, that coil wasn't working at all. People don't realize that heat dissipation doesn't work thru dirt. It's a metal to air process like a heat sink. But with fans.

  • @Pippy626
    @Pippy626 หลายเดือนก่อน +1

    If you can get me the size and what you need I can 3d print a plastic with carbon fiber spacer to take fan blade to aftermarket motor

  • @alejandrozometa1951
    @alejandrozometa1951 หลายเดือนก่อน +1

    Damn I didn’t know allied opened after hours I thought it was just United

  • @Extremely_crazy_toaster_light
    @Extremely_crazy_toaster_light หลายเดือนก่อน +1

    *the forbidden chocolate milk*

  • @Granth_Man
    @Granth_Man หลายเดือนก่อน +1

    I love ur vids even tho im a kid lol

  • @freefunky830
    @freefunky830 หลายเดือนก่อน +1

    Sheesh working in OC

  • @briansmith6135
    @briansmith6135 หลายเดือนก่อน +1

    Just curious as to what they charge you to open a/hrs?

  • @madcapmartin1
    @madcapmartin1 หลายเดือนก่อน +1

    Question, Do you have to pay a callout charge or a premium on the parts for the supply house when it's out of hours?

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน +1

      Yes, this particular supply house charges 150.00 dollars extra as an emergency open fee

  • @frankmashione139
    @frankmashione139 หลายเดือนก่อน

    is the reason for two speed evaporator fan part of energy code or just something manufacture decided to do

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน +1

      In most cases yes to reach a certain energy efficiency

  • @PuddinJr1993
    @PuddinJr1993 หลายเดือนก่อน +1

    Appliance tech not HVAC, what costs are associated with opening the supply house?

    • @natepeterson7145
      @natepeterson7145 หลายเดือนก่อน +4

      Appliance tech also. It depends on the supply house it can range from $100 and up. Customer pays the extra cost.

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน

      Exactly

  • @mainj54
    @mainj54 หลายเดือนก่อน +1

    What is the call out fee these days? Used to $100 when I was working.

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน +1

      150 at allied if I remember correctly

  • @maxsantana1
    @maxsantana1 หลายเดือนก่อน

    Hey Chris. So besides the obvious, voltage, watts does really matter when it comes to replacing a motor?
    I’m assuming you didn’t want to go down in watts using an after market motor.

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน +1

      This coming Monday during my live stream im going to discuss this a bit further, tune in if you can make it 5pm pacific

  • @steveblake8766
    @steveblake8766 หลายเดือนก่อน +1

    37 thumbs uP

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน +1

      Heck yeah

  • @michaelcoonts6253
    @michaelcoonts6253 23 วันที่ผ่านมา

    Have you ever had anything blow up? Lol😂

  • @pzpxc
    @pzpxc หลายเดือนก่อน

    In my area (AZ) good techs can be upwards of 100/hr + gas charge for there time. Is this normal for your area as well ?

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน

      It is similar

  • @AnonymaxUK
    @AnonymaxUK หลายเดือนก่อน

    What is the cost of asking the supply house to come open up after hours?

    • @EverythingisFire
      @EverythingisFire หลายเดือนก่อน +2

      I think in my area it's $100.

    • @sandy1653
      @sandy1653 หลายเดือนก่อน

      I'm in telco/ISP land, not HVAC, but one of ours charges $175 to open the supply house and the other charges a 30% fee, on top of only providing after-hours out of one warehouse that's at least a 2 hour drive away.

  • @CC-Rider
    @CC-Rider หลายเดือนก่อน

    Do you push for phase monitoring on three phase equipment?

    • @HVACRVIDEOS
      @HVACRVIDEOS  หลายเดือนก่อน +1

      Due to our nasty power grid it is something I recommend when possible

    • @CC-Rider
      @CC-Rider หลายเดือนก่อน

      @@HVACRVIDEOS we got to the point in South Florida where we require it for warranty purposes. Losing phases, etc because of the poor quality of utilities created the issue and after getting burned ourselves, we now require it on new /retro systems or if we pick up a new customer for PM contract. It was surprising at the amount of issues the monitoring caught.
      Excellent video... We don't feel so bad here seeing you battle your heat as well. We laughed at the "but it's s dry heat". It's frigging hot.

  • @youjiimoji6234
    @youjiimoji6234 หลายเดือนก่อน +1

    Man i hate thoose EC motors i understand they save energy but they really sucks 😑

  • @nhzxboi
    @nhzxboi หลายเดือนก่อน

    Their emergency, not yours...screw them until normal working hours.

  • @gmill1121
    @gmill1121 หลายเดือนก่อน

    I'm dealing with these motors at work, I'm curious as to the 2 speed function and which speed is which between the red and the black?

  • @raydoactive
    @raydoactive หลายเดือนก่อน +1

    “…And the sight glass is clear!” 🫡

  • @TonyKing-si2ns
    @TonyKing-si2ns หลายเดือนก่อน +1

    L

  • @rogerghiardi7723
    @rogerghiardi7723 หลายเดือนก่อน

    What !!! Big picture on the contactor. 🫡