  • @Thermoelectric7
    @Thermoelectric7 8 วันที่ผ่านมา +2

    You ever seen a Temperzone plug up the screens before the orifices? Had one at one of our sites, plugged the liquid line solid with what was like tarry lint just after the outdoor coil orifice. Tripping on LP
    Replaced that bit of pipe, put it back together and it ran fine. Came back later for a maintenance and it had plugged the screen at the indoor coil orifice.
    Put a biflow filter dryer in it yesterday (in hindsight we should have done that the first time), should have it sorted now but I'd love to know where all that shit came from.

    • @JesseDoesHVAC
      @JesseDoesHVAC 8 วันที่ผ่านมา +4

      brazing without nitrogen most likely

    • @tonymontana897
      @tonymontana897 8 วันที่ผ่านมา +1

      You should just remove that section of line and sweat in a straight through pipe.
      Always braze with nitro..

    • @Thermoelectric7
      @Thermoelectric7 8 วันที่ผ่านมา +1

      @JesseDoesHVAC it was a package unit, didn't look like it had been worked on previously. Unless the factory brazed without nitro but doubt it. Was bizzare that it somehow managed to plug a 3/8 liquid line solid

    • @Thermoelectric7
      @Thermoelectric7 8 วันที่ผ่านมา +2

      @tonymontana897 Yeah we did, removed the plugged bit and replaced. Went digging in it after we pulled it out to try and figure out what had plugged it.
      Would have been a pretty solid pressure differential across it (R410a), amazed it managed to plug the line solid.

    • @hvacraustralia
      @hvacraustralia  4 วันที่ผ่านมา

      I have seen it a few times but only partially blocked. I put it down to overheating the oil causing it to break down and block the strainers. Crazy to be fully blocked.

  • @CapitalCoastHVAC
    @CapitalCoastHVAC 7 วันที่ผ่านมา +1

    Peak summer also here in Wellington NZ (23c) Ha ha. 38c 🥵

    • @hvacraustralia
      @hvacraustralia  4 วันที่ผ่านมา

      It’s was a rough few days 😂

  • @tomasnewson6744
    @tomasnewson6744 6 วันที่ผ่านมา

    Those hplp switches may have not reset just because the ambient was so high that the reset diff was never achieved,or just took forever to achieve. But I’d have likely changed em anyway , like you . Decent video mate, will subscribe 👍🏻🇬🇧

  • @thesilentonevictor
    @thesilentonevictor 8 วันที่ผ่านมา

    Good troubleshooting

  • @Paul-IE-Repairs
    @Paul-IE-Repairs 8 วันที่ผ่านมา +2

    LEV1 linear expansion valve