Hi Toyin, Thank you for your comment. Design delta T, K Relative Natural Forced humidity convection convection 95-91 7 to 8 5 to 6 90-86 8 to 9 6 to 7 85-81 9 to 10 7 to 8 80-76 10 to 11 8 to 9 75-70 11 to 12 9 to 10 For temperatures of -12 deg.-c / 10 deg.f and below an evaporator TD of 6K is generally used for forced convection. Hope this was helpful :-)
Thanks for the Reply John and Whole Danfoss team 👍👏
You're welcome. Have a nice day :-)
Thanks you for the update.
however, please publish the Temperature difference to it Relative Humidity.
Hi Toyin, Thank you for your comment.
Design delta T, K
Relative Natural Forced
humidity convection convection
95-91 7 to 8 5 to 6
90-86 8 to 9 6 to 7
85-81 9 to 10 7 to 8
80-76 10 to 11 8 to 9
75-70 11 to 12 9 to 10
For temperatures of -12 deg.-c / 10 deg.f and below an evaporator TD of 6K is generally used for forced convection.
Hope this was helpful :-)