How Screw Chillers control Load

แชร์
ฝัง
  • เผยแพร่เมื่อ 10 ก.พ. 2025

ความคิดเห็น • 20

  • @HVACTIME
    @HVACTIME  9 หลายเดือนก่อน +1

    Finish your chiller course understanding chiller systems and terminology at your pace to advance your career! chilleracademy.com

  • @ziaarnie3694
    @ziaarnie3694 9 หลายเดือนก่อน +3

    Amazing video buddy as always , please make a complete video of screw compressor over hauling. Thanks once again

  • @juanskatebr
    @juanskatebr 3 วันที่ผ่านมา

    Bitzer compressors use both tecnologies with yaskawa drivers for maritime applications

  • @yzhang8629
    @yzhang8629 9 หลายเดือนก่อน +1

    Carrier 06T series compressors on XWV/XAV series VFD chillers combine both slide valve and VFD together, about the first half is controlled by the slide valve, and the last half is controlled by VFD

  • @younesizraren1641
    @younesizraren1641 7 หลายเดือนก่อน +1

    What about trane compressor? Do they combien the speed and the valve discharge

  • @dgapp76
    @dgapp76 9 หลายเดือนก่อน +3

    You might wanna wear hearing protection while working in the same room as the chiller. Those rotary screws are crazy loud.

  • @kasimshaikh3750
    @kasimshaikh3750 9 หลายเดือนก่อน +1

    I had a question you said loading depends on supply water temperature.
    What if the delta T increases shouldn't that also increase the loading percentage. As we are getting warmer water back from the building.

    • @HVACTIME
      @HVACTIME  9 หลายเดือนก่อน +1

      For standard equipment the chiller really only cares about leaving water temperature. While we monitor entering water temp it is not an active part of the control sequence. There may be unique exceptions out there but that is not the standard.

    • @kasimshaikh3750
      @kasimshaikh3750 9 หลายเดือนก่อน

      @@HVACTIME Thanks 👍

  • @Amuahmad249
    @Amuahmad249 8 หลายเดือนก่อน

    Is there possible to control screw chillers load by 1 percent instead of 25 percent?

  • @3harath
    @3harath 9 หลายเดือนก่อน

    Slide valve is to control compression ratio, means only change the discharge pressure the capacity remains same, correct me if I am wrong

    • @HVACTIME
      @HVACTIME  9 หลายเดือนก่อน +1

      The capacity is being adjusted by the slide valve. This is how we can make a 50 ton compressor operate at 30 tons to match load.

  • @hanifkadar8114
    @hanifkadar8114 9 หลายเดือนก่อน

    Hello Boss i have one question my screw compressor not taken full load sov active what reason?please reply

    • @HVACTIME
      @HVACTIME  9 หลายเดือนก่อน

      Could be a valve or oil pressure issue

  • @wh2410
    @wh2410 9 หลายเดือนก่อน

    Hi
    I wanted to tell you about whats happening with a York screw chiller. I can send you a pdf of the name plate but it's YCRS0140SC460YAADB. Whats happening is the demand stays level for the morning, but suddenly starts rising and falling. So its level at about 28 to 30 KW then rises pretty fast to 41+ KW. Then falls (at about the same speed) back to 28 KW. I'd like to send you some graphs from the metering so you can see. I asked the mechanic and he said its normal. I asked an old York guy and he said it's not normal at all. Thanks Bill Hendrix

  • @PraxZimmerman
    @PraxZimmerman 9 หลายเดือนก่อน

    Only experience with these is watching an HVAC tech bang his head against 4 of 'em because the electricians swapped the building feed breaker but didn't mesure rotation first and no one knew which direction the compressor took. Had to tear into it and remove the motor coupling and bumbstart to test. Added an hour and a half to a 30min restart 😑

  • @LeeBuilt
    @LeeBuilt 9 หลายเดือนก่อน

    Trane ACRA

  • @HEFTYLEFTY303
    @HEFTYLEFTY303 9 หลายเดือนก่อน

    Some screws have port loading my man

    • @HVACTIME
      @HVACTIME  9 หลายเดือนก่อน

      What is an example?

  • @blacksmith8642
    @blacksmith8642 9 หลายเดือนก่อน

    Good afternoon sir, I have a question. Do you have an institute of training? If is there. l want to attend regular classes in your country. Do you send me invitation letter or admission letter. I will pay your institute fee. I want training about YK york centrifugal chiller overhauling teardown training. Kindly send me details about admission details.