LG - Troubleshooting Common Multi V Error Codes

แชร์
ฝัง
  • เผยแพร่เมื่อ 5 ก.ย. 2024
  • Some common Multi V error codes.

ความคิดเห็น • 61

  • @jg3775
    @jg3775 3 ปีที่แล้ว +1

    I only get CH53 or CH05 when I connect more than one indoor unit, the auto addressing says "1" and there's 2 units connected. the outdoor unit is MULTI Vs and can connect up to 16 units.

    • @GlacierSupplyGroup
      @GlacierSupplyGroup  3 ปีที่แล้ว +1

      A CH53 is an outdoor unit communication fault and a CH05 is an indoor unit communication fault. Also, LG requires a minimum of 2 connected units and minimum 40% capacity. The error code you mentioned has to do with your daisy chain communication wiring. You also need to run an auto addressing and then run a hot pipe.

    • @jg3775
      @jg3775 3 ปีที่แล้ว

      @@GlacierSupplyGroup thanks for replying, I get no errors but it says "pre heating is running" and it doesn't change until I disconnect all the units and only wire one and then it says "ODU is running". I've double, triple and quadruple checked the daisy chain and even replaced the entire line ands I ran the power away from the communication so there isn't any interference but to no avail. im kinda lost

    • @anwarhussain7887
      @anwarhussain7887 2 ปีที่แล้ว

      Dear sir
      Multi v 4 ch 53 error occurred.
      What's possible error.
      Thanks

  • @miguelroman4479
    @miguelroman4479 2 ปีที่แล้ว

    I am experiencing a CH 62 indicates a sink error how do I trouble shoot ?

  • @thewannabemartialartist4613
    @thewannabemartialartist4613 3 ปีที่แล้ว +1

    I keep getting CH 26, and after replacing about 10+ compressors over the past 2 years is there something that im missing here?

  • @jorgeuribe4512
    @jorgeuribe4512 2 ปีที่แล้ว +1

    Ch21?

    • @dlanyc168
      @dlanyc168 2 ปีที่แล้ว

      Ch21 C 1 1 is what I have. Need answers!! Lol

  • @vusalmmmdov4204
    @vusalmmmdov4204 3 ปีที่แล้ว

    What is Ch-150? How can this problem be solved?

  • @imonevBG
    @imonevBG 3 ปีที่แล้ว

    Do you know what might be the cause of Error 73 and what is the eventual fix.

  • @AK-yu3cu
    @AK-yu3cu ปีที่แล้ว

    Please share link for testing &commissioning

  • @Samima823
    @Samima823 4 ปีที่แล้ว

    Discharge line work but not cooling

  • @Doels_Channel
    @Doels_Channel 2 ปีที่แล้ว +1

    How to solve eror 211, C11 please..

    • @dlanyc168
      @dlanyc168 2 ปีที่แล้ว

      Did you ever find this out?

  • @smartboy1489
    @smartboy1489 4 ปีที่แล้ว

    Please help me.i bought lg dual inverter 5star ac . After 3 days. In night the temp is set for 27celcius and enegy control in 60% when we wake up on the morning the room is not cooled but blower is running and the compressor is off. Then after restarting it shows a error code of CH21 and then again restarted the error code became vanished. But the compressor is not turning on after some hours again restarted the compressor runs and cools .Is there any problem?

    • @upsidezium1
      @upsidezium1 3 ปีที่แล้ว

      Inverter compressor run current high. Check compressor windings all equal 1 to 4 OhmsCheck to earth 50 MOhm minimum, check run current

    • @user-dx4bp8rf1l
      @user-dx4bp8rf1l 6 หลายเดือนก่อน

      Ch21 problemas con la tarjeta pcb La que le lleva tensión al compresor haga el cambio de pasta térmica al disipador de calor revise que él ventilador forzador esté trabajando bien y por supuesto revise el compresor

  • @Samima823
    @Samima823 4 ปีที่แล้ว

    Sir.. Pless help... LG smart inverter model ABUQ60LM3T0... Ch 35 error code in outdoor panel... Compressor run but not cooling.. Please answer me

    • @Samima823
      @Samima823 4 ปีที่แล้ว

      24000 BTU

    • @upsidezium1
      @upsidezium1 3 ปีที่แล้ว

      Excessive low pressure drop under 1 Bar at LP sensor. Check pressures, and check service valves open

  • @FirojAlam-ec3su
    @FirojAlam-ec3su 2 ปีที่แล้ว

    Sir guidance plz 211error plz help me

  • @edercardoso9259
    @edercardoso9259 3 ปีที่แล้ว

    olá!
    pode me informar o cód 237?

  • @acmohamed9935
    @acmohamed9935 2 ปีที่แล้ว

    CH44 what problm

  • @coolcoolaircondition9005
    @coolcoolaircondition9005 5 ปีที่แล้ว

    Vrf Lg 30 min coling but stop after not runing

  • @fiona9912
    @fiona9912 4 ปีที่แล้ว

    What if it just says ch

  • @jitendrasah2668
    @jitendrasah2668 3 ปีที่แล้ว

    How to solve CH51

  • @tipuzheaven6317
    @tipuzheaven6317 4 ปีที่แล้ว

    CH 242.Please tell me solution

  • @tompastian3447
    @tompastian3447 4 ปีที่แล้ว

    This video is more for an LG technician, not the average home owner. When the narrator talks about checking the fan motor, what fan motor is he referring to ? The fan motor in the air handler or the fan motor in the compressor unit? What would be much more helpful is an LG trouble shooting video that addresses specific problems. I have one of the larger mini split AC units with the heat pump. The inside unit started hissing, and then the smell of something electrical overheating. Unfortunately it looks like the mini split systems are too complicated for anyone but an experienced LG technician. Very disappointed with mine failing, considering what it costs to have the Freon lines hooked up (rip off). Before I had the LG system, I had a Fredrick mini split system (no longer available) and the technicians from Brandsmart could not figure out what was wrong with it. I got a refund since I bought a 5 year extended warranty, and had to return the entire unit. Friedrich ac units were once top of the line, but not so with the newer ones I've seen.

    • @jahblessyourmom
      @jahblessyourmom 3 ปีที่แล้ว

      That's because only a trained technician should be working on these units. These are large commercial units. A homeowner shouldn't be working on any high voltage equipment and a manufacturer isn't going to tell you how due to liability for when some dummy fries themself because they didn't let the inverter board discharge its capacitors.

    • @tompastian3447
      @tompastian3447 3 ปีที่แล้ว

      @@jahblessyourmom Thanks for the reply Chris. I took a few days, but I did figure out what happened with the electrical burning smell and the hissing. Both were not related to the mini split system. The burning smell was from an Ace Hardware power strip on the back porch which is fairly close to the air handler inside the house. I had several items plugged into this power strip, and something caused the strip to short out. It could have been some water dripping from above, or a bad cord on the grinder. The cord melted on the grinder where it plugged into the power strip. The smell made it's way into the house, and my wife was thought it was coming from the air handler.
      I do think however, it would be helpful if companies would give an explanation of what the various codes are.

  • @richardibarra3641
    @richardibarra3641 4 ปีที่แล้ว

    Have you got a ch150 code

    • @upsidezium1
      @upsidezium1 3 ปีที่แล้ว

      Sub 2 check power supply voltage to the outdoor unit is correct (1ph 220 Vac ±10% or 3ph 380 Vac ±10%). check fuses, if fuses OK replace outdoor main PCB

  • @fazliey3783
    @fazliey3783 3 ปีที่แล้ว

    Ch 03 and ch 25

  • @salma23tariq
    @salma23tariq 5 ปีที่แล้ว

    Error CH 15 plz

  • @adilgamra6039
    @adilgamra6039 2 ปีที่แล้ว

    Ch 180 plzzz

  • @techyvlog5455
    @techyvlog5455 4 ปีที่แล้ว +1

    Ch 51

    • @upsidezium1
      @upsidezium1 3 ปีที่แล้ว

      Unit mismatch. Check model number of units do not exceed maximum. Multi V - also check Sub outdoor unit dipswitch settings

  • @prasannankollam8948
    @prasannankollam8948 3 ปีที่แล้ว

    CH 15

  • @coolcoolaircondition9005
    @coolcoolaircondition9005 5 ปีที่แล้ว

    COOLCOOL

  • @jorgecanoaburto1135
    @jorgecanoaburto1135 4 ปีที่แล้ว

    My is ch 27 help please!

    • @jayrae17
      @jayrae17 4 ปีที่แล้ว

      It’s the inverter

    • @HeavyHookSet14
      @HeavyHookSet14 4 ปีที่แล้ว

      Care to elaborate a little more on this? Have the same on a lmu36chv

    • @upsidezium1
      @upsidezium1 3 ปีที่แล้ว

      Inverter current irregularity. Check inverter PCB and reactor

  • @ahmedjawad9767
    @ahmedjawad9767 5 ปีที่แล้ว

    Ch52 😥

    • @GlacierSupplyGroup
      @GlacierSupplyGroup  5 ปีที่แล้ว +1

      That's a communication error between main Micom and Sub Micom.

    • @upsidezium1
      @upsidezium1 3 ปีที่แล้ว

      Communication error between inverter PCB and main outdoor unit PCB. Check wiring fuses and LEDs . If OK either inverter or main PCB defective

  • @jasonzabala7992
    @jasonzabala7992 4 ปีที่แล้ว

    Error code 54

    • @upsidezium1
      @upsidezium1 3 ปีที่แล้ว

      Reverse or open phase. Check all 3 phases are present and correct. If correct voltage appears at all three phases, swap any two to cure the fault

  • @ericyeboah6340
    @ericyeboah6340 4 ปีที่แล้ว

    Please my ch 621

  • @ValValiantThor216
    @ValValiantThor216 5 ปีที่แล้ว

    Mine is ch50

    • @GlacierSupplyGroup
      @GlacierSupplyGroup  5 ปีที่แล้ว

      It's probably a CH05. I don't see a CH50 in the error code list. If it IS a CH05, that's a communication error.

    • @mmademusic3836
      @mmademusic3836 4 ปีที่แล้ว

      @@GlacierSupplyGroup CH50 is in this video, what are you on about?

  • @luisvaquero3452
    @luisvaquero3452 4 ปีที่แล้ว

    CH237??

    • @beergo99les
      @beergo99les 3 ปีที่แล้ว

      Any update?

    • @jg3775
      @jg3775 3 ปีที่แล้ว

      @@beergo99les I get CH237 when the auto addressing isn't done correctly.

  • @josealfredovelazquezmartin8025
    @josealfredovelazquezmartin8025 4 ปีที่แล้ว

    Multi v plus ch 50

  • @chiragrana2733
    @chiragrana2733 5 ปีที่แล้ว

    How to solve 28 2 error

  • @josealfredovelazquezmartin8025
    @josealfredovelazquezmartin8025 4 ปีที่แล้ว

    CH50?