Hello! Thank you for such a thorough explanation. One question: do you know if it is possible to simulate Modbus communication with this drive, if I do not have a physical unit to do tests?
@@averageengineer4266 yes, actually I would like to control the drive with a microcontroller. But I don't have a drive to do communication tests, is there a simulator available?
Hey, thank you for the video. This is interesting. I have a query about the ACS880 and AC500 CPU modbus communication. Q. Apart from writing the controlling parameters like start command, speed reference etc.. Can we write other VFD parameters through Modbus TCP using FMBT adapter with ACS880 VFD. This is required if we need to use the same setup to run for different scenarios
I have SIEMENS TIA PORTAL PLC (1500) and ABB ACS580 and ProfiBUS between them. Can't find "running" status in control words. Can find only Ready for running RDY_RUN - but it's not it. I need get bool for monitoring "is it still rotate motor or not?" RO2 - give it but... I need it by ProfiNET
Cyclical communication between drive and fieldbus adapter module A or between PLC and fieldbus adapter module A is lost. 1. Check status of fieldbus communication. See user documentation of fieldbus interface.2. Check settings of parameter groups 50 Fieldbus adapter (FBA), 51 FBA A settings, 52 FBA A data in and 53 FBA A data out. 3. Check cable connections. 4. Check if communication master is able to communicate.
two drive acs 580(1&2) communicate each other with help of profibus cable but one drive operate then communication error found in line like a ON, OFF automatic but drive 1 bypass Karke dusra drive se line chalata hu to koe error nahi ata hai communication ka.
Thanks brother.....i was eagerly waiting for this video...thanks once again....
Excellent Contents. Thanks a bunch!
Mind blowing sir
Great 👍
Thank you.
Hello! Thank you for such a thorough explanation. One question: do you know if it is possible to simulate Modbus communication with this drive, if I do not have a physical unit to do tests?
Hi, so you mean to control drive without plc, not sure,i have never tried using modbus. But i know it will work with OPC without PLC.
@@averageengineer4266 yes, actually I would like to control the drive with a microcontroller. But I don't have a drive to do communication tests, is there a simulator available?
I think ACS880 has virtual drive that comes with Drive composer software but you may need the license.
Excellent bro, r u providing online class??
Hey, thank you for the video. This is interesting. I have a query about the ACS880 and AC500 CPU modbus communication.
Q. Apart from writing the controlling parameters like start command, speed reference etc.. Can we write other VFD parameters through Modbus TCP using FMBT adapter with ACS880 VFD.
This is required if we need to use the same setup to run for different scenarios
Yes, you can write to other parameters. You have to link those parameters in Data out in drive parameter configuration.
I have SIEMENS TIA PORTAL PLC (1500) and ABB ACS580 and ProfiBUS between them. Can't find "running" status in control words. Can find only Ready for running RDY_RUN - but it's not it. I need get bool for monitoring "is it still rotate motor or not?" RO2 - give it but... I need it by ProfiNET
drive time and plc can be synchronized?
you mean date and time?
@@averageengineer4266 yes i mean parameter 96.20, 96.29.
@@АдхамжонМамаджонов i have not worked on this parameter, if i get an answer i will reply.thx
Hey
I have a vfd acs800-04-0016-3,giving a fault communication module 7510.Any help on how I can remove this error
Cyclical communication between drive and fieldbus adapter module A or between PLC and fieldbus adapter module A is lost.
1. Check status of fieldbus communication. See user documentation of fieldbus interface.2. Check settings of parameter groups 50 Fieldbus adapter (FBA), 51 FBA A settings, 52 FBA A data in and 53 FBA A data out.
3. Check cable connections.
4. Check if communication master is able to communicate.
two drive acs 580(1&2) communicate each other with help of profibus cable but one drive operate then communication error found in line like a ON, OFF automatic but drive 1 bypass Karke dusra drive se line chalata hu to koe error nahi ata hai communication ka.
How i can create custom parameters 9. ?
Sir please make a vedio on Mitsubishi fx5U PLC to ABB acs880 modbus communication
Plz i need drive composer pro register key
Great lessons,
Can I connect with you in LinkedIn?