Horner XL4 PLC HMI Modbus RTU Instructions

แชร์
ฝัง
  • เผยแพร่เมื่อ 19 ต.ค. 2024

ความคิดเห็น • 5

  • @motawemoha8225
    @motawemoha8225 4 ปีที่แล้ว +1

    Hi Garry, appreciate if you provide sketch for rj45 serial based rs232 pinout connection diagram. I tried following the manal, but no connection establishement between cscape and plc

    • @ACCautomation
      @ACCautomation  4 ปีที่แล้ว +1

      Hi Motawe,
      When dealing with RS232 I would only use three of the pins.
      Pin 8 - TXD
      Pin 7 - RXD
      Pin 6 - Ground 0V
      Jumper pin 4 and 3. (RTS - CTS)
      You did not mention the connector on the computer side. However, make sure that you jumper DTR to DSR and RTS to CTS. This will just leave the TXD, RXD and ground pins to connect.
      Note: If you are using a USB to Serial adapter, not all of these devices are the same. I have had success with the UGreen unit.
      www.ugreen.com/product/UGREEN_USB_2_to_RS232_DB9_Serial_Cable_Male_A_Converter_Adapter_with_PL2303_Chipset-en.html
      I hope this helps you out.
      Regards,
      Garry

    • @motawemoha8225
      @motawemoha8225 4 ปีที่แล้ว +1

      @@ACCautomation yes garry, im using rs232 to usb converter from pc side, i think i have same product ugreen which shared already.
      Still i should deal with TXD , RXD AND GND , CTS and RTS MUST BE JUMPER.
      IF I DID ABOVE , IT SHOULD ESTABLISH LINK?

    • @ACCautomation
      @ACCautomation  4 ปีที่แล้ว +1

      @@motawemoha8225
      Yes, this should then work. Since you are using a USB to RS232 adapter, also check your device manager in windows to ensure that the device is installed correctly and it has reserved a serial port.
      An alternative would be to purchase a cable from Horner.
      hornerautomation.com/product/optoisolator-13/
      Regards,
      Garry

    • @motawemoha8225
      @motawemoha8225 4 ปีที่แล้ว +1

      @@ACCautomation thank you so much