Sir, same configuration main bhi kiya hu to program plc me download ho gaya hai but hmi me click karne pr download to device ka option highlight nahi hota hai.
Check the version and IP address of the HMI first, then create project for the HMI using the same version of TIA Portal software and then select this HMI project and download to HMI.
Check the version and IP address of the HMI first, then upload an existing project from the HMI using the same version of TIA Portal software and save to your computer. Now modify the uploaded project and re-download on HMI.
Follow the steps given below. 1 - Use the highest version of TIA Portal you need to initially connect online S7-1200 PLC to check your internal Tia Portal version. 2- Try to upload project " for example PLC program Version is v15 and your TIA Portal Version is V17 " then the below massages shall be display "the program on the cpu is incompatible with step7 project version of program on the cpu : v15 ..> version of step7 project v17" It means the version of plc program is v15, so you need v15 TIA to upload project of PLC So in this way you can find the version of Siemens S7-1200 PLC. Hope you understand, how to check CPU Project version. .. Thanks
Follow the steps given below. 1 - Use the highest version of TIA Portal you need to initially connect online S7-1200 PLC to check your internal Tia Portal version. 2- Try to upload project " for example PLC program Version is v15 and your TIA Portal Version is V17 " then the below massages shall be display "the program on the cpu is incompatible with step7 project version of program on the cpu : v15 ..> version of step7 project v17" It means the version of plc program is v15, so you need v15 TIA to upload project of PLC So in this way you can find the version of Siemens S7-1200 PLC. Hope you understand, how to check CPU Project version. .. Thanks
First option: You can upgrade the firmware image of HMI form 15.1 to 17. Second option: Downgrade the PLC project from TIA17 to TIA15.1. After that you can communicate PLC with the HMI.
indian best automatoin explain youtuber
thank you so much.
You explained it in a very easy way
thank you
BAHUT ASSA GURU JI 🙏🙏
Thank you,
keep watching our videos share with others.
Subscribe our channel for latest updates.
superb video..
Thanks a lot
Sir, same configuration main bhi kiya hu to program plc me download ho gaya hai but hmi me click karne pr download to device ka option highlight nahi hota hai.
Check the version and IP address of the HMI first,
then create project for the HMI using the same version of TIA Portal software
and then select this HMI project and download to HMI.
@@plctraining Thanks a lot sir.
How can I rewrite the program in hmi?
I already have a program in hmi and now I can not get a connection with hmi.
Check the version and IP address of the HMI first, then upload an existing project from the HMI using the same version of TIA Portal software and save to your computer.
Now modify the uploaded project and re-download on HMI.
thanks sir
All the best
How u loaded program in HMI by just giving 24VDC. HMI not connected to any software or no pendrive
Thank you for your concern,
Please watch full video you will get answer of your question.
thank you sir....
Most welcome
Sir how to do connection between plc HMI and laptop
We will soon upload the video on the asked topic.
@@plctraining please sir most of the students have this doubt
How to know version of plc
Follow the steps given below.
1 - Use the highest version of TIA Portal you need to initially connect online
S7-1200 PLC to check your internal Tia Portal version.
2- Try to upload project
" for example
PLC program Version is v15 and your TIA Portal Version is V17 "
then the below massages shall be display
"the program on the cpu is incompatible with step7 project
version of program on the cpu : v15 ..> version of step7 project v17"
It means the version of plc program is v15,
so you need v15 TIA to upload project of PLC
So in this way you can find the version of Siemens S7-1200 PLC.
Hope you understand, how to check CPU Project version.
..
Thanks
How to check plc version
Follow the steps given below.
1 - Use the highest version of TIA Portal you need to initially connect online
S7-1200 PLC to check your internal Tia Portal version.
2- Try to upload project
" for example
PLC program Version is v15 and your TIA Portal Version is V17 "
then the below massages shall be display
"the program on the cpu is incompatible with step7 project
version of program on the cpu : v15 ..> version of step7 project v17"
It means the version of plc program is v15,
so you need v15 TIA to upload project of PLC
So in this way you can find the version of Siemens S7-1200 PLC.
Hope you understand, how to check CPU Project version.
..
Thanks
@@plctraining i have followed the steps above using Tia v17 and there was no issue while uploading i think the plc supports v17.
@@plctraining the plc supports Tia v17 but my HMI KTP409 basic version is 15.1 what to do now.?
First option: You can upgrade the firmware image of HMI form 15.1 to 17.
Second option: Downgrade the PLC project from TIA17 to TIA15.1.
After that you can communicate PLC with the HMI.
@@plctraining I have Tia 17 i have configured both plc and HMI. thank you for your valuable information 🙂