🌟 Access 100+ courses, 1,600+ videos, and 300+ hours of professional lessons! Master electrical engineering, renewable energy, and much more with Khadija Academy Student Membership. Learn real-world skills through expertly designed courses on topics like: ✅ Solar Energy, Electrical Design, MATLAB Simulink, Power Electronics, Wind Energy, Wave Energy, and more! 🔗 Explore it all here: www.khadijaacademy.com/p/khadija-academy-student-membership 💡 Your future starts here-click to join now!
hello brother, first of all thanks a lot and please I have a question about arc flash performance it says FCT NOT DETERMINED when I drag that SC symbol over a bus bar what is the problem?
This happens when you don't add the protective device that is used to denergize the equipment during a fault. Also, if the FCT is set to zero, you will see the same message.
@@EngrAhmedMahdy Thank you brother for your response the problem is that I added a HVCB That energizes the bus and Ive chosed it from etap library and the error still appears?
Good initiative Mr. Ahmed, could you please include information on correct Short circuit clearing time required to manage or reduce arc flash energy and also coordination of fault clearing circuit breaker with upstream circuit breaker, if possible explain it on TCC graph. Thank You
🌟 Access 100+ courses, 1,600+ videos, and 300+ hours of professional lessons!
Master electrical engineering, renewable energy, and much more with Khadija Academy Student Membership. Learn real-world skills through expertly designed courses on topics like:
✅ Solar Energy, Electrical Design, MATLAB Simulink, Power Electronics, Wind Energy, Wave Energy, and more!
🔗 Explore it all here: www.khadijaacademy.com/p/khadija-academy-student-membership
💡 Your future starts here-click to join now!
This List help me out with my grad project much appreciation for u, and thank u very much
Thank you brother :)
Appreciate highly your job on etap, Great job done Sir.
You are welcome 🙏❤
your videos are really helpful. Thank you so much for sharing these complete information.
Glad you like them! 😍
9:00
IE is the “Incident Energy”
Not Instant Energy
Nice work
bro, ur da best
Good help Mr. Ahmed. Please can you share how to use or implement Arc flash relay with ETAP. Thank you.
JazakAllah brother
You too brother
hello brother, first of all thanks a lot
and please I have a question about arc flash performance it says FCT NOT DETERMINED when I drag that SC symbol over a bus bar
what is the problem?
This happens when you don't add the protective device that is used to denergize the equipment during a fault. Also, if the FCT is set to zero, you will see the same message.
@@EngrAhmedMahdy Thank you brother for your response the problem is that I added a HVCB That energizes the bus and Ive chosed it from etap library and the error still appears?
Fault clearing time?
Hello Khadija, can you give a link to download a free ETAP 12.6? I look around and not found. Thank you very much for your help
Hey David,
You can find a link here:
www.ieees.com/f-9/11836/
please mention the cable details for the project which we are using
Watch the playlist from beginning, we added ratings of components in the first videos.