Dear sir jaise ki plinth beem tk 9 by 9 ka colam hai .to ab usko 9 by 15 ja 9 by 18 mein convert krna hai .ho skta hai kiya kiuki dono colam ki bech ki door 21 feet hai.aur span 5 feet hai.bech mein se ek colam mis kr diya hai humne parking ke liye .so please reply ja videoo
@@surjitsingh1844 First of all 21 ft opening is not needed for parking gate.. Second of all if u want to convert 9x9 column into 9x15 then u can do it.. But the tie beam must be heavily reinforced and it should be 450 mm in height..
Sir Aapne ek column k liye load bataya hai kya aap Kisi planning par uska total load Kitna lag Raha hai aur wo kaise har ek column par Kitna distribute Hoga sir please is par video bana dijiye
Very good and easy to understand for beginners, guide to get confidence with trust to make decisions at site work.. Going good brother. My best wishes to you. Regards Er Safeeq Ahmed.
Sir kya aap IS code wali kisi video ka link apni agali video me dal sakte hai to aapki bhut mahrbani hogi Mai aapki lagbhag sabhi video dekhta hun Thankyou sir......
Sir if we calculate the total loads including every type of load and then divide it by the no. Of column and then we can easily get the load weighing by one pillar
@@civilsitevisit sir aap to yeh 1 direction column ka bata rahe ho. Mai puch raha hu ki 1 floor pr 5 Colum ho to 10nd floor pr bhi 5 Colum ho to kya unse bhi Multiply hoga?
Sir, 50*30 feet ka hall hai. Ismein beech mein ek hi coloumn daalna chahta hu. Upar jo chat banegi uspar machines rakhi jaayengi 1200 kg ki 15 machines. Kya size pillar ka aur beem ka rakha jaaye jo load seh le
Thanks sir Concrete grade kya rakhna h column ka wo bhi bataiyega according to load And next floor pe load km ho jayega to usme column me change kaise hoga ya nhi hoga wo bataiyega next video me wo bhi batiyega
Sir colom or beam me jo density diye concrete k liye alag or Steel k liye alag woise hi beam me diye agar Direct rcc concrete ka density dene se hota ki ny...or brick ka density 1900 ki 2000...or baki samaj me agiya sir thank u ... wating for next video
Osm Knowledge sir, Sir Please Ek Video Bana dijiye jisme ye ho ki koi bhi construction means house, road, bridge ko banane me Sabse Pehle Kahan Se starting karenge
sir if i want to build my house, how can i figure out what type of soil it is. i have seen your video on depth of foundation. so there we need type of soil.
Sir muje y samaj nhi aya ki agar rk manjil banani h ..uska load Nika liya .phir second manjil par column Jo banega uska wait bhi to niche wale column par padega ..tab uska weight nhi buadega Kya ...please give me answer...
Sir ji ak pyara sa request tha..Can u make a design at least two storey building by manual calculation ?
ofcourse brother soon keep watching & Keep loving
Yes sir...it is needed
It is needed,not only 2 storey but also 3 storeyed
Dear sir jaise ki plinth beem tk 9 by 9 ka colam hai .to ab usko 9 by 15 ja 9 by 18 mein convert krna hai .ho skta hai kiya kiuki dono colam ki bech ki door 21 feet hai.aur span 5 feet hai.bech mein se ek colam mis kr diya hai humne parking ke liye .so please reply ja videoo
@@surjitsingh1844 First of all 21 ft opening is not needed for parking gate.. Second of all if u want to convert 9x9 column into 9x15 then u can do it.. But the tie beam must be heavily reinforced and it should be 450 mm in height..
Thanks for responding to our request by uploading this video bro ..
Keep uploading videos like this sir .. ..
yes ofcourse brother stay tunne
more is coming soon
Bahut shandar hai sir ji
Dear good job keep it up 👍
Thanks brother keep watching
Nice Sir your videos very helpful to freshers civil Engineer
Good vedio after the next vedio should be do
Nice video
Sir Aapne ek column k liye load bataya hai kya aap Kisi planning par uska total load Kitna lag Raha hai aur wo kaise har ek column par Kitna distribute Hoga sir please is par video bana dijiye
zarur brother bnata hun jld
@@civilsitevisit sir please make a video
Thanks you for given very important knowledge.
Good knowlege Sir Thank You
Welcome sir keep watching
All doubt clear. Thanks sir
Welcome brothee keep watching
Useful video
Good job
Welcome brother
Thanks sir
Welcome brother keep watching
Thanks sir aap bahut easy way m hr topic ko samjhate ho sir meri aapse ek request h ek video truss pe banaye plz sir
Thank you
Very good sir make load related video sir
soon brother keep watching & Keep loving
Very nice explanation, thank you so much my dear Sir
Very good and easy to understand for beginners, guide to get confidence with trust to make decisions at site work..
Going good brother.
My best wishes to you.
Regards Er Safeeq Ahmed.
Many many thanks to you sir ,it is best method sir
Welcome brother keep watching & Keep loving
staad pro par load calculate kaise karte hai dekhao
Superb
Sir super support
Thank you so mach sir
Nice sir video. And 2nd se 4th floor level ke liye apne batya wo sab kase apply kare
jitna houga utna multiply
Nahi samj aaraha. Plz explain briefly sir
थैंक्स सर
welcome brother
Mast video sir
nice sir
Thanks brother keep watching
Apne yeh thumbrule ke mutabik bataya hai ya yeh real me shi hai.q ki thumbrule not proper in future use engineer
Good
Thanks
Very nyc sir
Sir please make video on Plastering quantity of a room........
ofcourse brother soon keep watching & Keep loving
n but check playlist you will get video on it
Method is very understanding sir, pls also share the vedio of steel require,dia , nos of bar for column, and beams with footing
Sir 1 single stroy ka example.se btaye n .............stards se ......
zarur brother
Sir slab ke oupar gharka kouch saman ka bhi to loads including hoga
Sir is this steel values is standard
Sir kya aap IS code wali kisi video ka link apni agali video me dal sakte hai to aapki bhut mahrbani hogi
Mai aapki lagbhag sabhi video dekhta hun
Thankyou sir......
zarur brother ❤️
Thank you
Sir if we calculate the total loads including every type of load and then divide it by the no. Of column and then we can easily get the load weighing by one pillar
sir beam ke upar load nikalana sikheye plz with the help of yield theory...aur iske upar video upload zrur kre...!!!
zarur brother
Thank you sir.....I am waiting
1)How to calculate load on plinth beam and on footing??????
2) How to select dia of bar in plinth beam, colm etc.
3)can We assume the size of colm
i will upload video on it soon
Sir 9ench wall ko esi tarah nikala jayenga
Sir good video
I have a question does the brick quantity or load includes plastering and all
Sir ye bataye colum Ka size badhega to load v badhega n sir jii
sir make a vdo on depth of foundation, i know the types of foundation.. but i hv always question on.. i don't think its only depnd of firm strata..
check playlist you will get video on it sir
When your next video will be released , regarding the column design to bear the 39 KN load ?
Sir slab may steel Ka load percent may Nahi nekala wo bhi add hoga
bo tbhi mene 2500 le liya
Uske baad ki vedio kab aayegi sir
thanks
Welcome brother keep watching
Sir how grouping of column is done❓
i will upload video soon on it
OK sir
Or ek que or building ke center me column ka size zada rakhe ya Kam or corner pe ispe we video bnaye
bnata hun brother jld dnt worry
Sir drawings p vidioes bnado
Request???
jald lata hun uspe b video sir
@@civilsitevisit thanq you so much sir
Ek house plan ka beam ka design part by part krna hoga ya phir total span lekar design krna hoga ???
full beam load ke hisab se
Sir jese 5 Colum he to jo Colum ka self weight ayega usse 5 se multiply kardenge na?
haan but uske upper houga usse ka use upar ayega
@@civilsitevisit sir aap to yeh 1 direction column ka bata rahe ho. Mai puch raha hu ki 1 floor pr 5 Colum ho to 10nd floor pr bhi 5 Colum ho to kya unse bhi Multiply hoga?
1 residential building ka pura estimate &costing keya hoye uske upor 1 video banao
zarur brother bnata hun jald
Sir video ka last mein samajh nehin paya. Aur agar 4 storeyed building hai to column pe kitna load ayega
toh usko 4 se multiply karte hai
Sir
ISMB
K UPAR VIDEO BANAYE PLZ
Bro. Good vdo. But 2400kg is for pcc. So take 2500kg per m3. Its for rcc. Beam, slab. Column. For all. As we use rcc in these. Not pcc.
but we take steel and cincrete diff diff dats why
Sir internship certificate is available in other countries
yes
@@civilsitevisit and its a free or to pay and how to pay
Sir please make a vdo on brick calculation for a building
Yes ofcourse soon on it
I am CS Engineer, proud to feel learning Civil engineering.
How to know our column is so safe for having the load?
Thankyou
It has separate calculation.
Sir kya 12 mm...ka ...colam main six. Pices main 3 story bana sakta hain
Sir please provide vedio,identify house drawing start point
sir aap staad pro ki koi video banaiye jisme sab koch cover ho jae .
okeah brother bnata hun jld
Sir!! How to calculate load transfer of slab to beam??
divison brother
Sir plzz!!! Make video on this topic..
Sir, 50*30 feet ka hall hai. Ismein beech mein ek hi coloumn daalna chahta hu. Upar jo chat banegi uspar machines rakhi jaayengi 1200 kg ki 15 machines. Kya size pillar ka aur beem ka rakha jaaye jo load seh le
espe video hai ...ap dekh ke khud nekal sakte ho
Sir if can we use density of rcc-2500 for beam & column as you use for slab?
nope in beam n column i took concrete n steel diff datz why
Sir aap jo column aur beam aur slab ka length and width le rahe ho wo kese lete ho please explain
For slap dalai.....is it necessery to hav colom in stright line in both direction
2000 density of brick fix hoti h kya brick ke liye
no sir
plz give footing design also sir.
Iske bad vali vedio ka link send krna sir
Sir 20*20 feet span ka room hai kitana load ayega Kya usame sariya provide kare
Thanks sir
Concrete grade kya rakhna h column ka wo bhi bataiyega according to load
And next floor pe load km ho jayega to usme column me change kaise hoga ya nhi hoga wo bataiyega
next video me wo bhi batiyega
zarur brother
Sir reinforcement kaise calculate krenge ispe ?
Sir colom or beam me jo density diye concrete k liye alag or Steel k liye alag woise hi beam me diye agar Direct rcc concrete ka density dene se hota ki ny...or brick ka density 1900 ki 2000...or baki samaj me agiya sir thank u ... wating for next video
zarur brother btata hun sb ....
Hi sir is slab mein aapne steel ka weight nhin btaya
Column ko ground k bad patala kaise kare plz bataye
Can we put Strong column and weeker beam system in it ..???
Osm Knowledge sir, Sir Please Ek Video Bana dijiye jisme ye ho ki koi bhi construction means house, road, bridge ko banane me Sabse Pehle Kahan Se starting karenge
Bnata hun tarun jald
@@civilsitevisit Thanks Alot Sir
Sir mera rcc foundation 2stories ka he maine 2stories karliya kya mai avi 3story kar sakta hu ab plz rply
risky hai kya size hai foundation aur column ka
Sir column depth 4ft hai or column size 12 inch by 12 inch or steal hai 4*16mm or 2*12mm
+sir offline training krna chahta hu chhattisgarh me kahi centre h kya jha field knowledge mil ske
yes Hai ....but abhi lockdown bhad
7006672812
@@civilsitevisit pls provide address after lockdown krna chahta hu
Sir steel ka weight percentage me kitna le rahe hain ..y kese pata chalega??
bo dekhaya hai na mene
Sir,
FOS may less than 1.5?????
Sir ji in before video u said abt size of the column Nd load acting on column bt in this video u assume the size of column
sir if i want to build my house, how can i figure out what type of soil it is. i have seen your video on depth of foundation. so there we need type of soil.
check playlist you will get videos on it
Aapne jo load calculation kiya hai wo ek col pr hi aa rha hai kya
For central column all four beams half load is acting on it ?
Also slab load half of dim ?
Beam ke upar slab rehta h sir?? Please confirm
Good evening sir
Road site ki height 7' karna hai aur usi ke upper mein 7' ka room banana hai to column
Pichhe ka 10' height pe chhat banana hai
smja ni draw krke bta sakte ho ap
12mm 4rod sa 2 manjil bana payanga sir
Sir. still weight I am not standardstud sir please tell me
Sir size nikalne k liye to load nikal rhe to phir size leke load calculate kr rhe
Bro whn u will upload the video of calculating the total load on foundation??
Check playlist
video is uploaded
Bro wt abt%of steel in slab
How to provide steel bar in beam column plz tell
Sir beam ,slab or brick work ka weight agar column corner m h to 2 side ka half length ka lenge na
yes two side a ayega
column ka design batado sir
Sir self weight of slab and dead load is same ??
How to design footing and column steel
Sir I want one more video
Sir muje y samaj nhi aya ki agar rk manjil banani h ..uska load Nika liya .phir second manjil par column Jo banega uska wait bhi to niche wale column par padega ..tab uska weight nhi buadega Kya ...please give me answer...
yes use pe ayega sir