Air Conditioner Condensate DRAIN TRAPS! Function, Problems, Cleaning, Air Loss! Do I Need it?

แชร์
ฝัง
  • เผยแพร่เมื่อ 22 ธ.ค. 2024

ความคิดเห็น •

  • @williamserver4332
    @williamserver4332 2 ปีที่แล้ว +123

    You young guys getting into the trade are very lucky to have access to this guys videos. I wish I had them 20 years ago.

    • @aaronjosselyn8827
      @aaronjosselyn8827 2 ปีที่แล้ว +6

      A lot of younger guys don’t utilize this information . I study every chance I get

    • @superdutyscaler6823
      @superdutyscaler6823 2 ปีที่แล้ว +4

      We had installation manuals, that's all you need even to this day

    • @williamserver4332
      @williamserver4332 2 ปีที่แล้ว +9

      @@superdutyscaler6823 install manuals don't show how to service a system.

    • @jonahlee1272
      @jonahlee1272 2 ปีที่แล้ว +2

      Right you are sir. I had no idea this guy was so legit!

    • @falkonklan1622
      @falkonklan1622 2 ปีที่แล้ว +1

      As a young guy in the trade, I agree! I am very grateful!

  • @joedixon8804
    @joedixon8804 2 ปีที่แล้ว +24

    Make sure to always add a tee on p trap. Clean out is needed especially in a attic

  • @philo7686
    @philo7686 ปีที่แล้ว +21

    The amount of things that I can learn from Craig in a day is ridiculous 👍🏿 thank you for all of this information and helping people become better techs

  • @jo997
    @jo997 2 ปีที่แล้ว +17

    Wanted to comment on your latest vid in the hopes you see it. I spent hours watching your videos in order to fix my HVAC system. I know you teach to help the pros but I hope you dont mind that you help a lot of DIYers like myself. I took the time to watch many videos on your highly accurate and detailed inspections and repairs of HVAC systems and in the end I was able to fix it myself. Thank you so much for all of the videos and just know youre helping so many. Cheers!

  • @WCNYC
    @WCNYC ปีที่แล้ว +3

    Thanks so much! I moved into a house with a furnace/ac combo and it over flowed. I had to figure it out at 1:30 am! I had to cut the pvc pipe- I was going to put another trap- but now know I don’t need one. I can just use the pump. So grateful!!! ❤

  • @joecooksey4331
    @joecooksey4331 2 ปีที่แล้ว +14

    For 13 years my Nordyne 4 ton unit drained out what I thought was a pretty good condensate "drip". It had NO p-trap. After watching a previous video you did, I installed the Rectoseal trap and turned the condensate drain into a small garden hose. Everything equal, I dropped the RH by 5%. To test how well this works I opened up the cap between the trap and air handler and added food coloring and let the unit run. The food coloring just sits there. Closed the cap and off she goes.

    • @publicmail2
      @publicmail2 2 ปีที่แล้ว +8

      There you go, all that water siting in pan and air until unit turned off to drain, plus sucking in outside air. You may have reduced runtimes by 10-15% by reducing latent load.

  • @JuanTodoli
    @JuanTodoli 2 ปีที่แล้ว +2

    Those visuals, as simple as they seems, are priceless to adress the mindset toolbox of any tech. Thanks forever Craig!

  • @mavirek
    @mavirek ปีที่แล้ว +5

    Wow 😮 Now I’m even more freaked out. I’m a first time homeowner. I watch these videos all the time trying to learn what I should be doing. My AC is on the second floor in a closet. It ducts out from there. Another video told me I should flush the pvc drain pipe with vinegar. But my drain pipe had no cap to open to pour in vinegar. Apparently that’s not unusual because there was a video for how to cut a T valve in. But now you added a p-pipe. I don’t have that either. Where does that go? Before or after the T-valve? The prior videos just warned that the drain pipe had to slope down from the AC. 😱

  • @thejaebeing
    @thejaebeing 29 วันที่ผ่านมา

    Thank God for TH-cam. This is pure gold.

  • @apeel2008
    @apeel2008 5 หลายเดือนก่อน +1

    Just found your channel. I have been having HVAC/Furnace issues with my drain line so have been looking at TH-cam to better understand what I don’t know. I have seen a lot of videos on drain lines, p-traps, air exchangers and exchange coils and this is THE BEST of all that I have seen. Your explain the different requirements for air handlers HVAC), exchange coils (Furnace) , and mini split systems. FANTASTIC. Thank you!

  • @Kevin-mm6xm
    @Kevin-mm6xm 8 หลายเดือนก่อน +8

    Here in Florida the majority of houses are built on slab foundations with the line set and condensate line running under the slab in 3 or 4 inch pvc. The exit point for the condensate line is outside the house and rises up 8 to 10 inches above ground level. This creates a natural "P" trap as the under slab vs the exit point in total is about 15 inches, trapping the water in the line. Therefore no "P" trap is necessary. Depending on your construction it may or may not be necessary to add a "P" trap.

    • @Mr.Martini549
      @Mr.Martini549 5 หลายเดือนก่อน +1

      Good to know.

    • @BobSmith-rg4rh
      @BobSmith-rg4rh 3 หลายเดือนก่อน +2

      True. But absolutely ridiculous to run those lines 20 plus feet from air handler. Better I think to put in a p trap and exit house right by handler.

    • @Kevin-mm6xm
      @Kevin-mm6xm 3 หลายเดือนก่อน +1

      @@BobSmith-rg4rh It's not always possible to exit close to the air handler. In my case it's in the garage with no clear exit point to an outside wall. Even then, why punch a hole in the wall when you don't have to? It really doesn't matter how long the condensate line is as long as it empties and doesn't back up into the coil case.

  • @calex9398
    @calex9398 2 ปีที่แล้ว +14

    This man, legend

  • @Mitch2294
    @Mitch2294 2 ปีที่แล้ว +4

    Best video on traps i have seen. Thanks

  • @germanarellano5119
    @germanarellano5119 2 ปีที่แล้ว +6

    Best video ever 10 stars and 10 thumbs up. Specially now that I am about to install a heat pump and I had been searching for this answer since I didn't know the requirements for it and also because I new ducted and ductless work differently and also because I was debating whether to drain it outside or inside into a drain or even a pipe that drains my kitchen sink but was concerned about sewer gases backing into the drain pipe.

  • @adambarrett3296
    @adambarrett3296 4 หลายเดือนก่อน +1

    You are a wealth of knowledge. The best hvac videos out there.

  • @brianmcdermott1718
    @brianmcdermott1718 ปีที่แล้ว +2

    Great info. Helps to understand why we use the traps. Thanks Craig.

  • @perciusadlawan5853
    @perciusadlawan5853 2 หลายเดือนก่อน +1

    Thank you for this informative video. Hopefully you can make more videos. HVAC is still quite new to me and sharing infos like this makes it easier for me to catch up :)

  • @shanefrank3281
    @shanefrank3281 2 ปีที่แล้ว +1

    Thank you for this excellent explanation. I was confused when my horizontal high efficiency furnace had a trap on the furnace condensate drain, but not on the AC coils condensate drain.

  • @erichorton1440
    @erichorton1440 ปีที่แล้ว +1

    Jesus I love this Channel. I just bought his mini split book. Very excited to read it!

  • @drdickqueso
    @drdickqueso 2 หลายเดือนก่อน +1

    Craig is a god send. Love you man ❤

  • @victorgallardo9409
    @victorgallardo9409 2 ปีที่แล้ว +3

    Just what I was looking for, I was having issues with negative pressure. Great video!

  • @charliewingard6244
    @charliewingard6244 2 ปีที่แล้ว

    Thanks!

  • @betaonemusic
    @betaonemusic 2 ปีที่แล้ว +3

    Great video. I'd love to see how a clogged/dirty filter can affect air ingress pressure on the drain line, too. My guess is more air clog = more water column. Can a clogged filter cause enough vacuum to suck a trap dry?

  • @cck1496
    @cck1496 2 ปีที่แล้ว +3

    Good video. At 6:03, what is that small white colour tin with red colour cap?
    Thanks.

  • @Phil-D83
    @Phil-D83 ปีที่แล้ว +1

    I put a trap on my gas hvac with an ac onto. I clean it when I check the water softener salt level.

  • @ge0brick
    @ge0brick ปีที่แล้ว +6

    Great Video. In some positive pressure situations, a trap may still be needed. There's a youtube video out there where they use a clear evaporator chamber where the positive pressure is high enough to cause the air flow escaping from the drain to actually push the water away from the drain hole preventing it from draining until the system shuts off. It's similar to what happens with negative pressure but there's positive air flow pushing through the drainpipe. A trap in that case will prevent that. It will also prevent the loss of conditioned air escaping. However, in the case of the overflow, when it is drained outside the house, air will always be able to escape the system. A trap on that line won't help because it won't fill with water until the main drain clogs. Not a problem if you use an overflow switch. Forum threads on these p-trap topics go on and on and never seem to resolve to a solution for all cases.

  • @RayRay-nb7tn
    @RayRay-nb7tn 4 หลายเดือนก่อน +1

    Awesome explanation of traps. Great job Craig

  • @dontarguewithfools
    @dontarguewithfools 4 หลายเดือนก่อน +1

    How much of a difference would it be with air filter at the return grill? Also a slightly restrcited air filter?
    You the man Craig

  • @alexsunder9122
    @alexsunder9122 3 หลายเดือนก่อน +1

    U are doing God's work my man 💪 thanks ❤

  • @mwelsh64
    @mwelsh64 2 ปีที่แล้ว +2

    My Furnace & A coil didn't have a trap on it for 10 years when I moved in this old house. I seen a video online and it showed the water trapped in the pan because of no trap. I looked at my unit. It had no trap. I looked while the unit was running and the condensate was pooled because of negative air flow. It looked just like this video at 3:08 min. I put a U-trap on it a few yeas ago. The u stays full of water now. When I pull the cap, I noticed positive air flow. Why would it have negative one time and positive later on? I went to HVAC school, but I don't use that knowledge except for my personal house.

  • @keeloe
    @keeloe 2 ปีที่แล้ว +1

    Best channel on youtube

  • @JoeSmith-um2sg
    @JoeSmith-um2sg 2 ปีที่แล้ว +2

    Any videos on where to take line temperature readings for superheat and subcooling on packaged rooftop units??

  • @wilwiljames1
    @wilwiljames1 2 ปีที่แล้ว +2

    The first 95% furnace that I installed constantly quick cycled and I found out the the condensate plug had to be opened so the water could drain off (Yeah I finally read the manufactures instructions) I added a p-trap with a clean-out tee and it worked fine at after that.

  • @scottteague2190
    @scottteague2190 4 หลายเดือนก่อน +1

    So for a furnace / AC unit with a frame coil, you do not need a p-trap or even a vent to safely drain water for the condensation drain?

  • @Berglund-Chiropractic
    @Berglund-Chiropractic ปีที่แล้ว +1

    Can you please clarify when to use a P trap vs. when to use a U trap on a residential air handler. Thank you.

  • @kauaireed9006
    @kauaireed9006 2 ปีที่แล้ว +2

    Great video, should I add bleach water every so often to p-trap to help stop blockage issues. Thanks in advance

  • @fiji16g8
    @fiji16g8 6 หลายเดือนก่อน +1

    I just had a new Goodman installed and when I asked them why they didn't use a P-trap they said it didn't need it because the condensate line comes out of the bottom. I knew that wasn't right but I did read in the manual that if you have a shut off installed then you don't need a P-trap necessarily but I'm not sure if that's a good idea. Meanwhile these guys who installed it seem like they don't know what they're doing because they didn't mention that all they said is because the PVC pipe comes off the bottom of the air handler you don't need a P-trap meanwhile even though the pan is draining there is a small leak where are the threads attached to the pan. To show you what kind of workers they are in order to try and fix the leak they hit the PVC pipe with a hammer to break it off then they replaced it but didn't use any plumbers tape so it's still leaking a tiny bit. Maybe it wouldn't be leaking if they had a P-trap even though it's not really backing up in the pan much at all. I can't trust these guys that's for sure. I also have a little bit of water dripping off the coil and not going into the pan. I mentioned that and of course they're playing dumb. Not sure what I'm going to do about that

  • @markinfantado3255
    @markinfantado3255 4 หลายเดือนก่อน +1

    If a condensate safety shut off switch is added to the evaporator coils overflow port, will the negative pressure not allow the condensation to enter said shut off switch?

  • @adambergmann7716
    @adambergmann7716 6 หลายเดือนก่อน +1

    Is it required for both upflow downflow and fan coil? Post and prefan

  • @khashcpt
    @khashcpt ปีที่แล้ว +2

    Does the condensation still drains while using a dry trap ?
    Also, should a overflow shutoff switch be installed as well ?

  • @ufcpubg1964
    @ufcpubg1964 2 หลายเดือนก่อน +1

    On an air handler that is in a negative wouldn't you cap the first T and the second T would be open for a vacuum break?
    And on a positive air handler would it be the same as listed on the negative pressure air handler?
    If both are capped why should both be capped

  • @حسين-ج9ط7ي
    @حسين-ج9ط7ي 2 ปีที่แล้ว +3

    Great job, thank you brother. You are so talented

  • @GeneG-wk2mz
    @GeneG-wk2mz ปีที่แล้ว +1

    Nice knowledge I’m having problem with apartment the water just sit in the drain pipe but want drain . But the drain lines running in from the same drain pipe ???? Help please

  • @simonmclaughlin9120
    @simonmclaughlin9120 2 ปีที่แล้ว +3

    Great video as always. For any newbies, don’t put trap there air you won’t get your filter out 😉

    • @rudyjanke5942
      @rudyjanke5942 2 ปีที่แล้ว +1

      You can do it so long as you don't glue the first drop 90

    • @Bbgfffdfffjj
      @Bbgfffdfffjj 2 ปีที่แล้ว

      Add unions if you have to.

    • @simonmclaughlin9120
      @simonmclaughlin9120 2 ปีที่แล้ว

      Yeah some clients want to change their own filter. Just as easy to run horizontal till I reach the side and put the trap there.. makes it easier on them for changing the filter

  • @AESmith-pr9xm
    @AESmith-pr9xm 4 หลายเดือนก่อน +1

    Ok my son purchased his first home and now is working out of town. So I have trying to help out at his house so his wife does not have to do everything. Noticed the other day water coming out a pipe in the eve of the house. So I knew it was the emergency over flow for the HVAC. When I get in the attic I notice that the water seems to be coming out I guess the emergency on the HVAC and air flow. On the main drain line that goes to the house plumbing seems the be clear flowing. Almost seems like the safety switch on the main line slows the flow or change air pressure to make it some out the emergency hole. Do know they had some warranty work done on the a/c and am wondering if they left out the drain. Will try to attach a picture so you can see what I’m talking about. Any ideas would be great!

  • @GFlCh
    @GFlCh ปีที่แล้ว +1

    So let me know if I have this right... The reason the unit on the left (Furnace/AC) has positive pressure at the A-Coil, and the unit on the right (AC) has negative pressure at the A-Coil, is because in the Furnace/AC (left unit), the blower is below/before the A-Coil (often between the A-Coil and the filter/return duct) blowing toward the C-Coil, and on the AC (right unit), the blower is after/above the A-Coil, blowing AWAY from the A-Coil.

  • @LeoSal
    @LeoSal 2 ปีที่แล้ว +1

    I was so confused, not anymore! Gracias!

  • @cadamham
    @cadamham 9 หลายเดือนก่อน +2

    Any issues placing the trap outside if the drain line is properly pitched ?

  • @jaimemendoza5739
    @jaimemendoza5739 2 ปีที่แล้ว +3

    Great and positive training, very informative, thank you so much

  • @deepcreek2269
    @deepcreek2269 2 ปีที่แล้ว +4

    The air escaping in your math scenario is 15.8 cfm, not 4 cfm. You forgot radius squared. Not sure why it’s acceptable to allow a loss of 15 cfm from any positive system. This would be the same as having a one inch hole in your ductwork. This makes a compelling reason to have a trap on a positive pressure system, to prevent air escaping. Nice job demonstrating the physics.

    • @wayneschneyer8699
      @wayneschneyer8699 2 ปีที่แล้ว +1

      And also, many local plumbing codes require a trap in any installation.
      Why? They tell me it’s because they didn’t want all that air escaping! To your point sir.
      Thanks

  • @nono-fn3zc
    @nono-fn3zc 2 ปีที่แล้ว +1

    I have a whole house dehumidifier and I piped the drain to a condensate pump; pipe just off the bottom. My hvac buddy added a trap when we were troubleshooting an unrelated problem. From your video, it sounds like I should remove the trap. Yes/no? Thanks

  • @rosemountbomber
    @rosemountbomber 5 หลายเดือนก่อน +1

    I moved from Florida to Oregon. Combo unit furnace central A/C. Notice no water coming out the condensate line outside the house. Air is quite dry though. Notice that on my unit the pipe just above the U trap has a plug (between the coil and the U trap) that is not covered - so open to air. Is that wrong and should that cap not just be a open pipe but closed top?

  • @timthetoolman5522
    @timthetoolman5522 5 หลายเดือนก่อน +1

    Getting ready to install new Trane 4-5 ton coil. In the installation instructions, it states: "The condensate trap is not mandatory but is recommended for efficiency". But after watching this video it would seem that a trap would be mandatory because otherwise the condensate water would not drain until the unit shut off. Any further explanation?

  • @cgeorge6786
    @cgeorge6786 ปีที่แล้ว +1

    With a positive pressure system many homes have line going into drain -vent stack so you need trap to keep out sewer gas right?

  • @centralmassanglers
    @centralmassanglers 4 หลายเดือนก่อน +1

    I was taught to put a tee with a riser to break the vacuum is that not needed either?

  • @andreicravtov494
    @andreicravtov494 2 ปีที่แล้ว +3

    The CFM result should be double. You forgot to multiply by 2 when calculating Area.
    Also considering ~8CFM coming out of the PVC pipe i would recommend adding a trap even on positive pressure system. The air will cause restriction for condensate...
    Thank you for the video. Great info as always.

    • @HVACRTECH-83
      @HVACRTECH-83 2 ปีที่แล้ว +2

      What? The air does not restrict the flow of condensate at all when trap is on supply side of the fan. If anything it helps to push it out. Only time the air will restrict the flow of condensate is on a draw through system. Either way I install traps on both types

  • @brianbezotte4595
    @brianbezotte4595 ปีที่แล้ว +1

    How do you configure the trap to allow access to/replacement of the air airhandler filter?

  • @archiefernandes1292
    @archiefernandes1292 2 ปีที่แล้ว +2

    As Always thanks for your great expertise !

  • @pcexpress911
    @pcexpress911 7 หลายเดือนก่อน

    At 3:49 there is a device... Couldnt quite make out what you called it.. my condensate line has no p trap. Its a verrical force air system. Its. A system installed in 2009. There really is no clearance to have a p trap.hvac Housing cover blocks the depth needed for a standard p trap.

  • @kennethbest5302
    @kennethbest5302 4 หลายเดือนก่อน +1

    The condensate drain on my 90%+ furnace is completely dry. I was going to pour bleach in there as instructed by my installer to clean it. I saw it was dry, which I had never seen before. Is it normal for this to become dry during the months that the furnace isn't being used to heat the house, only the A/C is being used.
    Also, did you say that if my drains are not going outside but just draining into a floor drain that I didn't need a trap?
    The furnace (heating) condensation drain has a sort of trap but not a conventional P trap. Two tubes come out the side of the furnace into the very bottom of a retention reservoir. The reservoir will fill up then overflow into a drain connected to the PVC drain that goes to my floor drain. That reservoir is what is dry right now.
    My A/C condensation drain comes comes out of the top part of the furnace/AC where that A coil is. The drain then makes a couple 90% turns and is connected to the same PVC that the heating condensation drain is connected to and drains into the floor drain. The A/C doesn't appear to have any sort of P trap. Is that okay or should there be a P trap.
    If pictures would help, I have some I could send you.

  • @mansourramzey7711
    @mansourramzey7711 2 ปีที่แล้ว +1

    great video
    learning more about how ac works.

  • @PROJECT.LUKE.ONE.75
    @PROJECT.LUKE.ONE.75 2 ปีที่แล้ว +1

    It is okay to have a upflow furnace with the coil on bottom, or a downflow furnace with a coil on top?

  • @FlakySky6080
    @FlakySky6080 2 ปีที่แล้ว +1

    are supposed to pipe it that way on a handler ? feel like they wouldn’t be able to change the filter themselves ?

  • @acrepairnearme
    @acrepairnearme 2 ปีที่แล้ว +1

    Craig, Thank you. Also please make a video about piston sizes. Can the piston used for r22 be used for r410a? I always install the TXV when I do only condenser change out. But I always wondering what is gonna happening if I will leave the piston without touching anything on the air handler side.

  • @danyell4870
    @danyell4870 ปีที่แล้ว +1

    Question - we have a gas furnace & A//C system and the unit in your video is right on top of the American standard freedom 80vs (the air filter is at the bottom of that for reference) anyway it's all in a 2ft Wx 9.5ft H closet that's in our laundry room... yeah it's all weird idk. The pvc lines coming out of the unit your talking about in this video don't have those black rubber seals or anything sealing the open area around where they enter or exit the unit. Cold air just blows right out them into the closet. Is that ok? Should we have them patched around? Trying to figure out where any and all air leaks can be sealed. Thanks 😊

  • @anthonybarragan1687
    @anthonybarragan1687 ปีที่แล้ว +2

    I’m having a problem with air handling systems that are inside the ceiling at a gym, I’m getting water leaking from the bottom of the units, could this be due to the drain traps being full of air and not not trapped with water?

  • @jonathanraul4086
    @jonathanraul4086 2 ปีที่แล้ว +1

    Thank you! Great video again. Question, if I have a horizontal air handler draining into a pump, do I need a p-trap?

  • @Eddie2425
    @Eddie2425 ปีที่แล้ว +2

    I looked this up because I’ve been working in my attic, and since it’s transitioning into winter, it dawned on me that the water in my condensate P-trap will more than likely dry up since the AC is not being run. So I take it I should keep an eye on that in the winter and add water to it if I need to?

    • @billmellater
      @billmellater ปีที่แล้ว +1

      Been wondering the same thing. Can't find an answer anywhere. I have a Trane heat pump with positive condensate pressure.

  • @johnconnor7501
    @johnconnor7501 2 ปีที่แล้ว +11

    I think we should be calling the system either ‘Positive pressure’ or ‘Negative pressure’ system to avoid confusion.
    A good topic of discussion would be what to do with that secondary drain port for each style system.

    • @ishalljr
      @ishalljr 2 ปีที่แล้ว +2

      SS2 (or the like) safety switch or p-trap on negative pressure. SS2 or indicator tube/drain line on positive pressure.
      Alternative is to run an in-line safety switch (SS1) on the primary then the above option minus the SS2.

  • @alacran1986
    @alacran1986 2 ปีที่แล้ว +1

    Does the air flow meter work well on wall vents?

  • @ricardoluqueferrandez4543
    @ricardoluqueferrandez4543 หลายเดือนก่อน

    Hi, can you explain how to solve the very loud gurgling noise that you can have on a condensate pump line? In my case, the line goes up to the ceiling, cross my house and then goes down to the backyard. Is a very long line. Can a siphon breaker or an anti siphon device solve the air that is sucked through the pump? Thank you.

  • @blkmacster
    @blkmacster 9 หลายเดือนก่อน +1

    Thanks guy. I really appreciate this.

  • @janibashamolla
    @janibashamolla 2 ปีที่แล้ว +1

    Exlent explanation thanks for your kind information

  • @GFlCh
    @GFlCh ปีที่แล้ว

    What would be the effect of using a larger value capacitor on the air-handler blower? The value should be 5.0 uF (original capacitor, but someone replaced it with a 7.5 uF capacitor (both 370 VAC).

  • @omarii_jones
    @omarii_jones ปีที่แล้ว +1

    U trap is awesome

  • @Mridgwell
    @Mridgwell 2 ปีที่แล้ว +1

    What does it mean if you pull the cap on the inlet side of trap and water starts flowing into trap then put cover back on and water flow stops .

    • @mark8684
      @mark8684 ปีที่แล้ว

      Yes, I noticed the same thing on my gas furnace with A-coil above! The U-trap is full of water but I can’t tell if it’s flowing until I pull the inlet side cap off,

  • @birdnestfarms
    @birdnestfarms 6 หลายเดือนก่อน +1

    Excellent video. Thank you!

  • @mabbaticchio
    @mabbaticchio ปีที่แล้ว

    If the trap was empty and the unit was not draining while running, would it then fill up the trap when it shuts off? Assuming that it was not on long enough to overflow the pan.

  • @queensblvd86
    @queensblvd86 ปีที่แล้ว +1

    Any help is appreciated. Air blows out from my condensate line. It doesn't have a trap right now, do I need to install one to make it more efficient?

    • @stevenw815
      @stevenw815 3 หลายเดือนก่อน

      If it’s blowing inside your house my guess would be it’s fine but if it’s blowing outside that seems like a waste to me then I would probably put a trap

  • @jasonalley6524
    @jasonalley6524 7 หลายเดือนก่อน

    I have a commercial AHU drain question. The drain pan inside the motor housing, when the unit is cooling, is constantly full/overflowing and water is not draining through the trap, but when you open the door to the motor housing water begins draining out of the trap. There’s clearly a vacuum effect happening because the door is hard to open. What could be done to fix this issue? The condensate overflows the pan inside and the water level is about as high as the bottom of the door and leaks out of the unit wherever it can, just not through the condensate trap like it should. Any help would be greatly appreciated

  • @dr.lecter8874
    @dr.lecter8874 หลายเดือนก่อน

    When water fills up to the pvc line inside the condensate pump and there's a trap already existing it then becomes a double trap and when I see a double trap (regardless of condensate pump but in general) I'll usually see a vent on the PVC line. Can you please explain why that is?

  • @exclusive_148
    @exclusive_148 2 ปีที่แล้ว +1

    Is a trap as effective if its outside??

  • @padilla7019
    @padilla7019 ปีที่แล้ว +1

    A lot of great information

  • @MsFishingdog
    @MsFishingdog 2 ปีที่แล้ว +2

    Great video

  • @wayneguy6043
    @wayneguy6043 2 ปีที่แล้ว

    I have a machine similar to,the second one you show……it leaks condensate water under the two exit ports….they don’t have a crack, what is going on?

  • @effyootoob8321
    @effyootoob8321 2 ปีที่แล้ว

    What about a positive air flow drain without a vent? They seem to cavitate and splash the water from the pan, inside the blower..

  • @jameskennett8666
    @jameskennett8666 ปีที่แล้ว +1

    Awesome video!

  • @LeslieWood-qb8do
    @LeslieWood-qb8do 4 หลายเดือนก่อน +1

    Good job ❤️🙏🙏🙏

  • @DannerPlace
    @DannerPlace 2 ปีที่แล้ว +1

    Good video, thank you fro posting this.

  • @royalbleu3910
    @royalbleu3910 ปีที่แล้ว

    Does not having a trap cause water to drip off of the a coil?

  • @VaporheadATC
    @VaporheadATC 2 ปีที่แล้ว

    My drain line was plugged up and overflowed into the secondary pan, but I don't understand why the float switch which is attached next to coil drain didn't tell the system to stop? I pulled the float switch out and verified it does shut off the outside unit when moved, but don't know why it wouldn't shut off the unit before it started overflowing into the secondary pan. I have no P trap.

  • @OGCJ10
    @OGCJ10 2 ปีที่แล้ว

    With the second example shown (positive pressure system) I noticed the shut off valve is slightly higher than the drain vent. From the little bit of research I've done people stated that it's faulty and did not work as it should. That in order for the valve to be triggered it needs to sit slightly below the drain vent. Is this true?

  • @desmondwilliams4068
    @desmondwilliams4068 2 ปีที่แล้ว

    So should the U trap always have some water in it?...

  • @amio_roseto1
    @amio_roseto1 2 ปีที่แล้ว +1

    Great Video !!!

  • @thefreshride1510
    @thefreshride1510 2 ปีที่แล้ว +1

    Thank you for this video

  • @nc3bbq
    @nc3bbq 2 ปีที่แล้ว

    Do you have a link to the dry trap @3:48

  • @Jenomous
    @Jenomous ปีที่แล้ว

    I dont know anything about this stuff. Should the u shaped tube have water in it always?

  • @deanmartin1966
    @deanmartin1966 2 ปีที่แล้ว +1

    Great video. Thanks for sharing.

  • @Js-jh1qn
    @Js-jh1qn 2 ปีที่แล้ว +1

    Thanks

  • @JordieG8
    @JordieG8 2 ปีที่แล้ว +1

    Great demos. Thanks