Vector Groups in Three Phase Transformers

แชร์
ฝัง
  • เผยแพร่เมื่อ 19 ต.ค. 2024

ความคิดเห็น • 28

  • @enriquitocortez2601
    @enriquitocortez2601 23 วันที่ผ่านมา

    Great! Thanks for the knowledge Sir.

  • @SureshBabu-iu8mm
    @SureshBabu-iu8mm ปีที่แล้ว +2

    Very good presentation. Need more lectures on Switchgear and testing relays

  • @eepower
    @eepower 2 ปีที่แล้ว +2

    Amazing work! Thank you for sharing this great knowledge

  • @sky1army423
    @sky1army423 2 วันที่ผ่านมา +1

    6:13 how did you got the diagram with Vbn, Vcn and Van pls explain!!!!

  • @arkytoon
    @arkytoon 2 ปีที่แล้ว

    Thanks a lot.
    The explanation with slides are amazing.
    👍👍👍

  • @cadribopraiseoyo5636
    @cadribopraiseoyo5636 3 หลายเดือนก่อน

    Excellent lecture

  • @rjshtk
    @rjshtk 2 ปีที่แล้ว

    Excellent session sir!

  • @mayurtalekar3597
    @mayurtalekar3597 2 ปีที่แล้ว

    Excellent explained

  • @surendrakverma555
    @surendrakverma555 2 ปีที่แล้ว

    Very good. Thanks 🙏🙏🙏🙏🙏🙏

  • @artyb7696
    @artyb7696 ปีที่แล้ว

    Thank you!

  • @RituGouda-og5de
    @RituGouda-og5de หลายเดือนก่อน

    Sir it's 30 degrees leading or 330 degrees legging? You told in this video it's 30 leading. I m very confused sir plz explain

    • @PowerNotes
      @PowerNotes  หลายเดือนก่อน

      30 degree leading and 330 degree lagging are the same.

  • @HowTo-ob6yu
    @HowTo-ob6yu 2 ปีที่แล้ว

    Please tell me about Dy9 configuration please

  • @AmitSharma-ik4tq
    @AmitSharma-ik4tq ปีที่แล้ว

    How test Vector group Yd5 or Dy5 transformer vector group test

  • @haldharchouhan007
    @haldharchouhan007 2 ปีที่แล้ว

    Superb

  • @NattawatNil
    @NattawatNil 2 ปีที่แล้ว

    very goodddd

  • @MINHAJUDDINKhan
    @MINHAJUDDINKhan ปีที่แล้ว +1

    what is the difference between Dyn11 and Dy11

    • @sakthidhasan3764
      @sakthidhasan3764 11 หลายเดือนก่อน

      Dyn11 means neutral is grounded at Y side, Dy11 means neutral is open grounded at Y side. Here 11, indicates LV side voltage and current are 30 lagging to HV.

    • @rjshtk
      @rjshtk 9 หลายเดือนก่อน

      @@sakthidhasan3764 About the grounding part your explanation is fine. But 11 means, the LV side voltages and currents are leading HV by 30 degrees.

    • @ssengonzidenis5254
      @ssengonzidenis5254 6 หลายเดือนก่อน

      I think Dyn11 and Dy11 are the same but on Dyn11 the neutral is brought out unlike Dy11 where neutral is not considered at any point

  • @krishnannambiathiri5661
    @krishnannambiathiri5661 3 ปีที่แล้ว +1

    Distribution transformer is generally of Dyn11. But generator transformer is Ynd1. Why it is so

    • @rjshtk
      @rjshtk 2 ปีที่แล้ว +6

      The distribution transformer is usually of Dyn11 vector group, since the single phase distributed loads will be far from ideal condition, in the sense there will always be unbalance between the loading of each phases, resulting in an unbalance of LV side neutral due to all the unbalanced loads at a moment. It means that the LV neutral will have a resultant zero sequence current flowing into its neutral point at the transformer. This will cause a shifting of the neutral point voltage too. The zero sequence current will be trapped inside the delta winding on the HV side of the distribution transformer and thus the propagation of zero sequence current towards the source is prevented. The delta winding is hence said to have a have a circulating zero sequence current that is trapped in the delta, i.e, It will not be reflected in the primary side of the transformer(the CTs at the HV side of the distribution transformer will not see it as they are not installed in the transformer usually). If the HV winding was of star type, instead of delta, the an HV equivalent of the LV zero sequence current will flow though the HV side neutral of the distribution transformer towards the source (i.e towards the substation transformer that feeds the distribution transformer). This would cause the protective relay to pick up and possibly trip the CB, in case if there is enough unbalance in the loads in the star connected secondary side. In order to prevent these unwanted trippings, the distribution transformer is selected as of Dy11 vector group. Similarly in a generator transformer, the outputs from the generator transformer (GT) is Star connected. It means whenever there is a fault or unbalance in the load side (ie. on the HV side of the GT, which will be the load side), it will cause a zero sequence current to be generated in the star point of the GT's HV side, for the protective relays of the GT's HV side to pickup and even trip. In normal case this would not happen. So in case there is an unbalance or fault in the the GT's LV side, which is connected in delta will have a circulating zero sequence current, which will NOT be permitted to go further upstream into the generator stator. The generator stator would have had to accept the zero sequence currents, had the GT's LV side been Star connected. This would cause zero sequence component of current and some negative sequence current in the stator. Negative sequence component would cause rotor heating. Zero sequence current will be flowing into the generator neutral also, causing the Earth fault relay of the Generator to pick and even trip in case of enough unbalances due to the faults on the HV side. (This could be possible in case of a single phase auto reclosing event at the GT's secondary side, after a fault occurance). So , the GT's LV in delta configuration prevents the load unbalances in the secondary sides from propagating to stator. Also, it suppresses the various harmonics from load side from propagating upstream. I hope this explanation gives an idea now!

    • @SureshBabu-iu8mm
      @SureshBabu-iu8mm ปีที่แล้ว

      ​@@rjshtk Amazing

    • @rekhyl
      @rekhyl 14 วันที่ผ่านมา

      @@rjshtk thank you

  • @bikramareddy4162
    @bikramareddy4162 8 หลายเดือนก่อน

    I think Dy1 is wrong phasor digram

  • @shashivendrashukla6985
    @shashivendrashukla6985 8 หลายเดือนก่อน

    Your connection is not matching with IS 2026 Part 1

  • @muhammadathar2358
    @muhammadathar2358 ปีที่แล้ว

    it is standard practise to bring Terminals with subscript 2 are brought out or connection terminals, you have shown reverse to it

    • @rjshtk
      @rjshtk 9 หลายเดือนก่อน

      Usually the subscript 1 is found on terminals.. like 1U1,1V1 & 1W1 (primary side)and 2U1, 2V1 & 2W1 (secondary).. I guess it varies from country to country.