Thanks for video! Can you cover all transmision line protection and automation functions in detail after you finish series with transformer protection lectures?
There is a mistake in drawing . You are showing Ynd11 from generator. Generator is star connected and it is connected to step up transformer with vector group Ynd11. Here Y is always high voltage side. But in drawing you are showing in reverse way. Please check
Hi thanks for the video ,but I didn’t get why we need phase displacement. If we transmit it with zero degrees and distribute it with zero degrees what will happen?
When Step up transformer (11/500kV) is YNd1, then Unit Aux Transformer (11/6.3kV) is Dyn11, the Distribution Transformer (6.3/0.4 kV) Should use Dy11 or Dyn5 or we can used both, what is the Reason? Above is for in SLD.
@@wongsabarchannel1335 The Dyn5 trafo can be used to supply the excitation system with incoming ac that gets converted and controlled by thyristors. The harmonics produced in the exxcitation circuit due to the semi con devices is prevented from reflecting on the upstream CTs by using the Dyn5 type transformer. The Dy11 is used for normal station auxiliary loads.
Sir thank u nice explanation. There's can be many transformer in between generator transformer and distribution system so how this phase matching helpless.
All those in between transformers will be YNyn0 type. So these will just carry forward whatever phase angle from the Generator Transformer side to the Distribution Transformer.
nice one brother. so much appreciate your effort to make us enlighten.👌🏿
thank you and most welcome
I really appreciate your teaching method and I am watching your videos everyday . Wish you best health.
thank you very much
Thanks for video! Can you cover all transmision line protection and automation functions in detail after you finish series with transformer protection lectures?
There is a mistake in drawing . You are showing Ynd11 from generator. Generator is star connected and it is connected to step up transformer with vector group Ynd11. Here Y is always high voltage side. But in drawing you are showing in reverse way. Please check
this is ref. schematic diagram from site
Hi thanks for the video ,but I didn’t get why we need phase displacement. If we transmit it with zero degrees and distribute it with zero degrees what will happen?
when we make DY transformer it will naturally make phase displacement.
Thank you for this video... Please upload more videos like this... Please make video on distance relay
Thank you sir your video very like fully that
your most welcome
When Step up transformer (11/500kV) is YNd1, then Unit Aux Transformer (11/6.3kV) is Dyn11, the Distribution Transformer (6.3/0.4 kV) Should use Dy11 or Dyn5 or we can used both, what is the Reason?
Above is for in SLD.
it will compensated the angle different
@@baranitech It still not answer my question.. Can you check my question?
Should use Dy11 or Dyn5 or we can used both, what is the Reason?
@@wongsabarchannel1335 you can use DYn11 or DYn5 . over there. both have same value only.
@@baranitech What different when use Dyn5 and Dyn11? The advantage maybe
@@wongsabarchannel1335 The Dyn5 trafo can be used to supply the excitation system with incoming ac that gets converted and controlled by thyristors. The harmonics produced in the exxcitation circuit due to the semi con devices is prevented from reflecting on the upstream CTs by using the Dyn5 type transformer. The Dy11 is used for normal station auxiliary loads.
Good video.
Thanks, and welcome.
at 5:30 of the video, you have shown the Generator stator side of GT as Star. That would be wrong. It has to be delta!
if you use GT as Delta then distribution should be low voltage. in this video i have show for HV
Very Well Xplained!!! can you Have the video over other
i will try to make for other also.
What will happen if the phase shifts to 60 deg in a combination?
Thkz for the information
Always welcome
This is the most wanted explanation 💪🙄🌎🌏🐸😲🤔
thank you
Hi does it really requires to bond Neutral and Earth in the Secondary for Dyn11 Transformer?
Its depends on which application your going to use.
Sir can I connect parallel of two transformer having vector group ynd11 or ynd1
sir which software used for making this video????
i use PPT
Sir thank u nice explanation.
There's can be many transformer in between generator transformer and distribution system so how this phase matching helpless.
All those in between transformers will be YNyn0 type. So these will just carry forward whatever phase angle from the Generator Transformer side to the Distribution Transformer.
Good
thank you
Pls upload TTR test.....
i will make soon
why it is needed?
yes taking lv side star and to avoid 3th harmonic on HV
Thanks