Assalamualaikum sir I checked micro motion mass flow meter, if isolate then TX output is showing 4mA but take in line it's output of range . Plz tell me what is problem
What other parameters you are monitoring on SCADA? If, only Totalizer is being monitored; check for cable, cable size, use shielded cable, ground the shield. Check temp of core processor, health of core processor, any noises in the power line or interference. You can re-route the cable for for no or less interference provided core processor is good in all respect.
If totalizer has high value, you may reset the totalizer or configuration may be reloaded with much care. All settings should be saved prior this event.
Check Voltage applied to the core is within range, wiring and wiring connections and sometime internal connections of core dry soldered. Make resistance check between core terminals specially 3 and 4 (A & B)
Difficult and Critical Job. You must understand circuitry first. Depends on type of fault.. First of all check electrolytic capacitors, Bridge Rectifier, Mosfet, dry soldering etc
Very good explanation thanks you sir
Assalam O Aliykum Sir! The way you explain everything is so perfect , To be honest, I learn more from this video my all doubts are clear now. I appreciate your work and way of explaining.
Please keep sharing such kind of video.
Very good explanation..thanks
good work
very good explanation
good job sir
excellent
Nice
Masha Allah
nice.
great
good
Masha Allah.
Thank you sir.
👍
💓
When we can see the communication video? Waiting for it....thank you.
Very Soon Insha Allah
my micro motion can't be used, can't connect the HMI to the RS485, what do you think is the problem?
Try with Protocol: MODBUS RTU, Baud Rate: 9600, Parity: Odd, Stop Bit: 1, Address: 1 (common address)
8 Bit
Please guide the any wiring diagram
How to read wiring diagram
Instrument and electrical
Thank you sir
I have need 2700 transmitter Modbus address and modbus mapping.
Assalamualaikum sir
I checked micro motion mass flow meter, if isolate then TX output is showing 4mA but take in line it's output of range . Plz tell me what is problem
Sir glass Fuse ketne Ampere ka hi
Glass Fuse located in the base/housing is 1.25A, 250V.
Glass Fuse located on the PCB of Power Supply is 250mA (F250H), 250V
Isme Hart connect nhi ho rha... please btaein Hart kaise connect krna h
Sir totaliser value update taking time in scada other aise all ok flowmeter any solution
What other parameters you are monitoring on SCADA? If, only Totalizer is being monitored; check for cable, cable size, use shielded cable, ground the shield. Check temp of core processor, health of core processor, any noises in the power line or interference. You can re-route the cable for for no or less interference provided core processor is good in all respect.
If totalizer has high value, you may reset the totalizer or configuration may be reloaded with much care. All settings should be saved prior this event.
Thanks
Asalam-u-ahlikum. Sir. Some time core connected. And some time not working.. Any solution???.
Check Voltage applied to the core is within range, wiring and wiring connections and sometime internal connections of core dry soldered. Make resistance check between core terminals specially 3 and 4 (A & B)
salam bro
in english also please
230V AC IS provided ,but DISPLAY IS ON BUT NOT SHOWING ANYTHING ON DISPLAY . WHAT TO DO ??
Probably Processor Card is bad.....
how to repair power supply card
Difficult and Critical Job. You must understand circuitry first. Depends on type of fault.. First of all check electrolytic capacitors, Bridge Rectifier, Mosfet, dry soldering etc