Assalamulaikum bhai sahab Aap khairiyat se Hai. Aap samjhane ka larika bahut hi acha hai. Bhai mere ek sawal hai ki. Same carrier ka package a/c hai us ka blower ka contector jaal ja raha hai. Blower 12.4 Amp. Le raha hai
waalaikumassalam brother 🤝 . ji Alhamdulillah..🤲 contactor ke point ya coil kya jal raha hai ? .. agar point jal rahe hain to over size ka contactor laga dijiye aur agar coil kharab ho raha hai to kai sare reason ho sakte hain jaise 24 volt poore na banna . 22 volt , 20 volt agar aise banenge to bhi coil kharab ho sakta hai . to uske liye aapko load par incoming volt check karne honge ki 220 volt ban rahe hain ki nahi agar incoming volt kam aa rahe hain to sabse pahle us ko fix kar len ab uske baad transformer ke output ( 24. volt ) ko check karen agar voltage sahi hai to koi aur problem ho sakta hai aur agar 24 volt poore nahi ban rahe hain to transformer weak ho sakta hai to us condition main tranformer ko change kar den .. phir kabhi kabhi aisa bhi hota hai ki kisi ne transformer ko change kiya lekin under capacity ka laga diya hai to ek reson ye bhi ho sakta hai to uske liye 75VA se 100VA ki capacity tak ka use karen .. aur bhi kai sare reason ho sakte hain jaise remote ka wire jyada lamba hona ya wire bahut hi patli hona ( 1.sqmm ya 18.AWG ki wire use karna chahiye) , ya relay ( lockout relay , black relay ) problem karna , ... agar phir bhi kuchh samajh main nahi aa raha hai to uske liye aap ye kar len ki 24 volt coil ki jagah 220 volt coil wala contactor laga den . baki wiring same rahe gi bas jo contactor ke coil par 220 volt aayenge wo ek nutral direct de dena hai aur doosri supply ko relay ke throw....
waalaikumassalam brother 💚 khair mubarak jis type moter ki aap baat kar rahe hain wo direct drive ( without belt ) shayad aati hai ? us type moter ko aap direct nahi chala sakte kyonki us ko control karne ke liye moter ke ander aur bahar do pcb board hote hain jo dono aapas main mil karke kaam karte hain agar koi ek pcb kharab hogi to moter nahi chalega
brother compressor ki capacity ke according sab ka alag alag rahta hai . lekin bahut hi aasan hai compressor main jis size ka pipe connection diya huwa hota hai bas usi size ka hota hai . han bada ho sakta hai lekin chhota kabhi bhi use nahi karte !
whatsApp no. yahan se mil jayega koi bhi agar doubt rahta hai to aap maloom kar sakte hain 24 hours ke andar andar main time nikal karke jaroor reply karoonga .. visit my facebook page and please LIKE 👍 PAGE . check description 👇 ( MENTION IN BIO )
jaisa aap bata rahe hain ABC teen wire hain to usme ek wire common hogi aur ek wire NO aur ek wire NC hogi . lekin aap ko agar simpal way main batayen to aap teeno wire ko aapas main connect kar do direct ho jayega .
@@thetechhvac thanks for your reply ... Isko lockout relay q bolte h? Ye to DPDT relay h maine isk box pe dekha tha double pole double throw, lkin lockout q bolte b ise...
ye simple ek relay hai 24 vac ki lekin lockout relay is wajah se bolte hain kyonki ye jyadatar compressor ke contactor ko lockout karne ke liye wiring main use karte hain is wajah se .
Thank you bhai is video se jankari achchi mili hai
shukriya ❤️
Bro you are a Real Teacher 🥰❤️👍👨💼💖
Aapke video se itna kuchh sikhane Ko milta hai ki dil khush ho jata hai
shukriya brother 💚
Very informative video thank you so much brother have a good time may Allah Pak bless upon you and bundles of thanks for your help.
Nice bhijaan
Very nice
Very useful video
Glad you think so!
Bhai AP bohat neki ka kaam kr rhe ho
Super se uper video. Thanks buddy. Eid mubarak.🎉
khair mubarak 🤗 ❤️
Ok thanks Bhai 🎉
thanks u so much
Bai is reley heater hogi tu lagana hi kya? .. Cool mode me lagana nahi hi kya
❤
Assalamulaikum bhai sahab
Aap khairiyat se Hai.
Aap samjhane ka larika bahut hi acha hai.
Bhai mere ek sawal hai ki.
Same carrier ka package a/c hai us ka blower ka contector jaal ja raha hai.
Blower 12.4 Amp. Le raha hai
Unit chalne me koi problem nahi.
Bas contector udh ja rahe hai.
Sare L/P & H/P switch bhi naye laga diya hai
waalaikumassalam brother 🤝 . ji Alhamdulillah..🤲
contactor ke point ya coil kya jal raha hai ? ..
agar point jal rahe hain to over size ka contactor laga dijiye aur agar coil kharab ho raha hai to kai sare reason ho sakte hain jaise 24 volt poore na banna . 22 volt , 20 volt agar aise banenge to bhi coil kharab ho sakta hai . to uske liye aapko load par incoming volt check karne honge ki 220 volt ban rahe hain ki nahi agar incoming volt kam aa rahe hain to sabse pahle us ko fix kar len ab uske baad transformer ke output ( 24. volt ) ko check karen agar voltage sahi hai to koi aur problem ho sakta hai aur agar 24 volt poore nahi ban rahe hain to transformer weak ho sakta hai to us condition main tranformer ko change kar den ..
phir kabhi kabhi aisa bhi hota hai ki kisi ne transformer ko change kiya lekin under capacity ka laga diya hai to ek reson ye bhi ho sakta hai to uske liye 75VA se 100VA ki capacity tak ka use karen ..
aur bhi kai sare reason ho sakte hain jaise remote ka wire jyada lamba hona ya wire bahut hi patli hona ( 1.sqmm ya 18.AWG ki wire use karna chahiye) , ya relay ( lockout relay , black relay ) problem karna , ...
agar phir bhi kuchh samajh main nahi aa raha hai to uske liye aap ye kar len ki 24 volt coil ki jagah 220 volt coil wala contactor laga den . baki wiring same rahe gi bas jo contactor ke coil par 220 volt aayenge wo ek nutral direct de dena hai aur doosri supply ko relay ke throw....
Bhai sare carrier ki same wiring Hogi?
Bhai jo apke pss meter ha usy ksy single phase compressor chck kr skty short ha k nhi thora smjna bhai bht muskil hoti smj nhi ari
Assalamualaikum Faiz Bhai Eid Mubarak
Train packedg AC me blower side me pcb kit kharab honjaye to dairect kaise chlaye without kit
waalaikumassalam brother 💚 khair mubarak
jis type moter ki aap baat kar rahe hain wo direct drive ( without belt ) shayad aati hai ? us type moter ko aap direct nahi chala sakte kyonki us ko control karne ke liye moter ke ander aur bahar do pcb board hote hain jo dono aapas main mil karke kaam karte hain agar koi ek pcb kharab hogi to moter nahi chalega
@@thetechhvac ha Yes
Bhaiya package ac me copper pipe size kaun kaun sa suction discharge me lga rhata hai
brother compressor ki capacity ke according sab ka alag alag rahta hai .
lekin bahut hi aasan hai compressor main jis size ka pipe connection diya huwa hota hai bas usi size ka hota hai . han bada ho sakta hai lekin chhota kabhi bhi use nahi karte !
@@thetechhvac 10TR ka bata dijiye
Hello bro york ka package ac new compressr lgaya h likin us me temperature nhi aara h kuchch batahiye
back pressure aur head pressure kitna hai ❓.
whatsApp no. yahan se mil jayega koi bhi agar doubt rahta hai to aap maloom kar sakte hain 24 hours ke andar andar main time nikal karke jaroor reply karoonga ..
visit my facebook page and please LIKE 👍 PAGE . check description 👇 ( MENTION IN BIO )
Bhai denfos lp hp switch agar kam nahi karta hai to use kaise direct karte hai 3 wire hai ABC
jaisa aap bata rahe hain ABC teen wire hain to usme ek wire common hogi aur ek wire NO aur ek wire NC hogi . lekin aap ko agar simpal way main batayen to aap teeno wire ko aapas main connect kar do direct ho jayega .
Aap ka bahut bahut shukriya Bhai aap comments ka reply karte hai koi bhi youtuber reply nahi karta hai walking cooler hai ABC conection hai
Bhai 24V ac or dc 😢😢
Ac
Bhai reply me
Is relay ko kaun sa relay bolte h....
relay ya lockout relay
@@thetechhvac thanks for your reply
... Isko lockout relay q bolte h? Ye to DPDT relay h maine isk box pe dekha tha double pole double throw, lkin lockout q bolte b ise...
ye simple ek relay hai 24 vac ki lekin lockout relay is wajah se bolte hain kyonki ye jyadatar compressor ke contactor ko lockout karne ke liye wiring main use karte hain is wajah se .