How to size your string? How many panels in a string ?
ฝัง
- เผยแพร่เมื่อ 1 ต.ค. 2024
- Hello,
This video is about calculating your string size.
The number of panels that you need to connect in a string to get optimum power from the inverter.
Depending upon your location, module & inverter.
#solar #inverter #electrical #string #electricalengineering #calculation #battery
You can write to me at Sajid.sayyad3@gmail.com
For any doubt or details.
Simple and Well Explained. Just one small addition from my side. 21 Modules will make max V = 21 * 49.23V = 1033.83 V and to keep it in MPPT range the max number of the modules should be limited to 20 Nos. i.e. max. V = 20 * 49.23V = 984.6 V
Yes, correct.
Extreme heat will affect minimum string size, though, and you may want to check that your minimum string size still falls within the MPP range for optimal efficiency. To do that, you follow the same calculations as above, but you need to use different values:
Use the panel Vmp in place of Voc.
Use the panel Temperature Coefficient of Pmax in place of Temperature Coefficient of Voc.
When it comes to calculating the true voltage of the panel, subtract the voltage compensation from the panel Vmp (instead of adding it to the panel Voc).
@@electrical-sajid Thanks
Yes correct, I was pointing out the same.
One doubt actually that why we are taking temperature coefficient of Power instead of voltage ?
I don't know if anybody sees my comment. By following this discussion I did calculations again. The panels range is 8-20 to keep values in MPPT range. Did I get the correct answer?
Explained well but just had mistake in summer and winter voltage range calculation you swapped the voltages differently in two slides.
sir great Mashallah great explaination sir kindly how we can consider DC cables size ,AC cable size let suppose our project is 1MW , from inverter to laod distance is 500 ft what will be dc and ac cables are se
I have made separate videos for ac and dc cables
I'm sure he said something important
U mean string in series the panels
Sajid you have explained the string in a easy way, keep it up. kindly also
explain the 8 input vs 4 Mppt tracker in SUN2000-30KTL-M3
Hi Rajesh, above video was good. I need you to do a video on calculating the rating for DCDB( fuse, SPD, MCD) n ACDB(fuse, SPD, MCB) for On grid rooftop solar plant 2, 3, 4, 5, 6,8,9,10,12Kw using Solis inverter.
My calculation is correct
Invertor technical specification
Max. input voltage 1.100 V
Operating voltage range 140 V ~ 980 V
Start-up voltage 200 V
Rated input voltage 600 V
Max. input current per MPPT 13.5 A
Max. short-circuit current 19.5 A
Number of MPP trackers 2
Max. input number per MPP tracker 1
Solar Panael 570W (STC)
Maximum Power (Pmax) 570W
Maximum Power Voltage (Vmp) 42.70 V
Maximum Power Current (Imp) 13.35 A
Open-circuit Voltage (Voc) 51.80 V
Short-circuit Current (Isc) 13.81 A
Temperature coefficients of Voc -0.25%/C
9 solar panel / string (2 string total 18 panel)
max Voc / sting (in +25C STC) 9 x 51,80 V = 466 V
max Voc / string (in -20 C) 9 x 57.63 V = 518.67 V
51,8 V * 0.0025 = 0.1295 V dif -1C
-20C +25C => 45C dif
0.1295 V x 45 = 5,8275 V
51,8 V + 5.8275 V = 57.63 V
This is what I was looking for and stumbled upon your video, Excellent Bro, Keep it up.
Glad it helped
That's fine. But I will also suggest you to make a video on selecting the PV array size i.e how many cells should be connected per string per module and how many parallel strings need to be connected per cell?
Sir , Good Expalined.
I have some doubt ,Please clarify.
1.Why we calculate max. no of string at max. system voltage not in MPPT max. voltage?
2. Why we consider module data of STC not NOCT?
Sir how to calculate the maximum pv input power of grid tie inverter. I need the formula to calculate
Bhai your knowledge is perfect no doubt,but do it in Hindi as your English is not so fluent as English men. wish you best luck
That was really helpful, thank you for sharing. Please keep up the good work.
Thankyou
Nice👍, can you plz also explain Ooper & Aluminium AC wire selection for different inverters like 50ka , 80kw & bigger. How much cable size we can use for these bigger inverter.
Sir I am new in solar
I want to do solar
I watch a lot of video
And I have 10 panels and battery 48v and inverter but I can not figuring out how to make the strings to come close to max preform
Can you give me some advice when I provide the data
The video is nice but for me a little bit to fast to follow 😉
this is awesome!! thank you so much. very easy to understand, and great examples.
Nicely explained.Also pls tell us about current matching of panel and inverter.I am finding suitable inverter for 595W 18.42 Amps Canadian Solar Panel.l for 8KW 3 Phase On Grid System.Can you pls suggest suitable inverter model?
Yes I will share by today evening
For the maximum number of modules calculation, I saw a research paper where one factor was used that at the time of morning, the temperature is lower but the radiation is Also lower (keeping wind velocity and other factors constant) , so the string will not active it's maximum open circuit voltage and thus the maximum number of modules they had increased. I'm not sure about the credibility of that paper but I have calculations where they've calculated Voc at different radiation levels.
Let me know if you have anything related to it, Also let me know your mail ID so that I can share the calculations so that we can discuss further.
You addressed how to calculate the number of panels for a series. Can you show how to calculate that for strings that are parallel ? ... I used this video to calculate how many panels for the Sol-Ark 12K-P inverter using SILFAB - SIL-490-HN panels. I get minimum 3 and maximum 8 panels per string. I need a total of 20 panels so have to use parallel strings. How can I calculate that using your formulas ??? Thanks enjoyed your video. Kurt
Explained in simple words 👏👏
Thanks for your sharing. but my opinion we also have to considering the max. power per MPPT to sizing the string of PV Module. During clarification with Huawei, they inform if MPPT have limitation of power.
Ofcourse
Nice your video
Hello sir
Ji
Why you have not considered value of Vmp for the minimum voltage at maximum temperature. For maximum voltage at minimum temperature it;s ok but at higher side calculation of voltage did not take value of Vmp & power coefficient factor. Plz correct it.
It's correct kindly re watch
bht bhtreeéeeeeeeeeen hogya Sir
jazakallah
an we give 26A on each string of MPPT ?
Don't you mean into your solar controller??
Great Presentation. Thank you
Very informative and very helpful 👍 👏
For minimum no. Of modules we take Vmpp in consideration, so (at 7.42 time) minimum voltage in summer should be calculated using Vmpp with temperature coefficient formula.
What about current ??????
Great Presentation. Well spoken 👍👍👍👏👏👏👌👌👌
❤❤❤🎉🎉🎉 Nice Nice 👍👍👍👍
You explained Entire TH-cam 🎉
And about current Sir?
Super information bhai
Thanks a lot dear.....
where did you get STCtemp value which you said was 25 because on the module data sheet is not there.
Well explained.
Well explained
Saral language mai batao sir
This is great.
Are you planning to do a sample project from scratch which covers client requirements, what questions to ask as a designer and how to do sizing of everything, including, panels and wires and voltage drops etc, and codes to follow for the USA, if not the USA then also it's fine? Sorry if I asked too much :).
Excellent...
nice
Thank you
great effort
waiting for your 1Mw SLD design Video sir
Very soon
Very informative video. Greeting from Angola, Lobito.
Why the subtraction sign of temp. Coff. Of Voc is not taken in consideration ?
Hi I have seen in a case for the maximum temperature didn't use Voc but vmp of the panel what's the difference?
This explains everything EXCEPT calculating the number of panels -__- Bro, we don't want "ranges" we want an example of an actual sizing procedure.
There are no fix number of panels brother. It depends upon your input dc voltage of your inverter. Ex. If your max. Input voltage is 1000V for inverter, and MPPT range is between 400V to 850V then you must try to keep your voltage within this range.
Ex. One panel voltage Voc is 54V, you can plan around 16 -18nos of panels per string.
Thanks this helped me with the uneven panels and strings going to the mpp trackers in the inverter
I looking at getting a Growatt MIN 4200 TL-XE Single Phase Solar PV Inverter 2 MPPT for a 3.69 kW solar array (9 panels at 410W each). If I had 2 strings with one string having 4 panels (150.4Vmp) and the other having 5 (188 Vmp), would I lose the wattage from that additional 5th panel of that string or do the 2 mppt scale it so that I still utilise the whole solar array wattage. Great vid btw.
You will not loose the power as it is in different MPPT
Good Video. Greeting from Angola, Lobito.
Very informative. Thanks
Sajid, I need one query if I make 1Mw solar substation... First I decide the invertor size then only I plan to arrange the string... How I will go through.. Could u suggest me the way of designing Sajid
First you decide the plant capacity (DC) then you choose the inverter depending upon the required size and number of MPPT. Then as per input voltage of the inverter you select the size of the string.
Why did you round off upwards in some cases and round off downwards in other cases? i.e. the max and min number of panels as well as with the max and min voltage in summer and winter? should we consider this criteria a rule of thumb that should always be adhered to?
U r doing great buddy
Thank you kindly check other videos as well.
Very well explained, thanks!
Dear please reply if possible dear I want to install 30kw solar system using same huawe inverter of 36 kW than how will be my string arrangement using 455w mono perc half cut solar panels having same voltage and temperature as your please reply
I am currently busy. I will reply you tmw.
@@electrical-sajid OK dear , dear according to your panel the maximum number of panel we connect to this inverter are 160 panel because there are four mppt input and every mppt can support 22 A it means every mppt support 40 panel 20 ,20 panel in parallel for one mppt input ,dear I am right or wrong please reply
Dear waiting for your responce
Sir do not worry,
Send me your inverter and solar panel datasheet in mail I will tell you exactly.
For simplicity, if your inverter maximum dc input voltage is 1500V then you should go for 3 nos x 22 panel string.
If your inverter is 1100V
Then go for
2x16 panel string
2x18 panel string.
Can i ask u a question!😊
yes?
Please clarify is it the maximum size of 21 of array or string? I mean for the same inverter is it ok to have two strings each of 21 in parallel?
That you need to check on inverter datasheet. Either you can connect two strings or first connect 2 string in parallel and connect to 1 string input of inverter. Check the per MPPT or input current for the inverter on datasheet
Sir
Hindi pe bolte to or hi accha hota
i will surely cover this in hindi
Simple and well Explained
very good information sir you gave
Can you offer excel
Great job of explaining this concept.
Thank u, very well explanied
i have 8 panels, each panel rated (540w,13Amp,49voc), if I make 2 strings, (4+4) so each string will have 4 panels with 196voc+13Amp, after i connect both strings together before i connect them to inverter...what will be my total given voc and Amps to inverter....will it stay 196voc 13Amps or this value will get double????
Thank you sir
If you connect the panels by the connectors itself then it will
Double voltage and same current.
But you combine in DCDB Or by using cascade connector it will be same voltage and double current
@@electrical-sajid
let me be more clear, I got 2 strings, each string got, 149voc+13Amps.... before I wired them to my inverter I have to connect both strings together...Positive wire from string No, 1, to positve wire of string No,2 and negative wire of string No,1 to negative wire of string No,2....after I am done with this, now I am ready to connect my inverter....I am curious here...wether the voc will change or Amps will change...U said the voc will stay the same and Amps will get double am I right sir????
@@mybirds8671 It means you are connecting them in parallel, so in parallel voltage will be the same and current will add up.
V GOOD
Beautiful
So i have a question. If my inverter has 9 MPPT and 18 inputs. I have maintained the string voltage range according to the inverter data sheet range, How many strings can i insert into the Inverter based on my MPPT inputs. (My max input current per MPPT is 26A and Max Short circuit current per MPPT is 40A). Please explain.
You cannot go beyond 26A per MPPT. I have not seen any inverter with 18inputs and 9MPPT, if there is pls share the make and model number.
Just note you cannot more than 26A in MPPT
@@electrical-sajid Correction. I have just realized that i misconceited the inverter data. As it stands I have a choice of (12/14/16) MPPT Individual inputs with 2 input connectors for each MPPT input. With max PV input current of (40A/30A/30A) Respectively. So what i understood from your explanation is that i should not exceed the 40A input for each MPPT. (or) Should i not Exceed 40A input for the overall Inverter?
@@riyazahamad1316 Inverters nowadays have the ability to clip the current of solar panels if it exceeded the pv input and short circuit current.... though the panels will underperform
@@riyazahamad1316 Do not exceed the inverter pv input and short circuit current max values if you are designing a string per mppt
Excellent & informative
Good explanation.👌Keep it up.
You're a rock star
Nice ...what is the STC temp , from where we can get this as 25 in your example.
Stc is mentioned on the solar panel datasheet. It means standard test condition.
@@electrical-sajid Ok Sir Thank you
Zabardast A1
Bahut Badhiya sir ji
Sir wanted to discuss strings made with the help of your video, can you share your contact
Solis 3p15 4g-AU, 37 panels jinko cheetah + HC 78M-v 440w. For Karachi. Doesn’t say tested temp. What strings should I get?
@@muhammadmahmood3693 sajid.sayyad3@gmail.com send me a mail. With datasheet of panel and inverter and also let me know the site location.
Thank you, sent you the email. Site is in Karachi pakistan
I hope all your doubts are cleared.