Analog Output Measurement | Measure 4 to 20 mA DC current of DP Transmitter

แชร์
ฝัง
  • เผยแพร่เมื่อ 5 มิ.ย. 2024
  • In this video, I have shown two different methods to measure 4 to 20 mA analog output current of Pressure Transmitter, DP Transmitter, Level Transmitter & Temperature Transmitter
    _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
    Video content:
    1. Different methods to measure analog output current of transmitter.
    In First method, we need to connect multi meter in series with transmitter.
    As you can see from the diagram, put multimeter in current measuring mode.
    To put multi meter in current measuring mode, connect red probe to 400 mA port, and black probe to common port of multi meter.
    After this, rotate the knob of multi meter in clockwise direction, and select ma function.
    After this, press yellow button at once to select milli ampere dc function.
    Analog current output can be measured in dc form. So, it is important to select milli ampere dc function.
    Once you have put multi meter in current measuring mode, connect red probe to negative terminal of transmitter, and common probe to negative terminal of 24 volt dc power supply.
    Now, multi meter in series with transmitter. So it will show 4 mA in normal condition.
    And analog current value keep increasing, when measured value increases.
    In second method, we need to connect multimeter probe to negative terminal and test terminal of transmitter.
    As you can see from the diagram, this method is only applicable for transmitter, which has test port.
    In order to measure output current, we need to connect red probe to negative terminal of transmitter, and common or black probe to test terminal.
    After connecting probe to negative and test terminals, put the multi meter to current measuring mode.
    And select mA dc function of multi meter. Once you select mA dc from multi meter, multi meter will show mA output of transmitter.
    _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
    If you have missed our most recent videos, then watch them here:
    1. What is a PID Controller | Proportional Band | Integral Action | Derivative Action
    • What is a PID Controll...
    2. What is Direct Action and Reverse Action - Understanding Process Controller Action
    • What is Direct Action ...
    3. What is Closed Loop Control System and Open Loop Control System
    • What is Closed Loop Co...
    4. How to perform Kurz Thermal Mass Flowmeter Calibration
    • How to perform Kurz Th...
    _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
    Keep Supporting us.
    || LIKE || COMMENT || SUBSCRIBE
    _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
    #analog_output_devices
    #analog_output_cable
    #analog_output_module
    #analog_output_examples
    #analog_output
    #analog_output_current
    #output_mA
    #analog_output_wiring

ความคิดเห็น • 30

  • @premsis
    @premsis 7 หลายเดือนก่อน

    Thanks from India

  • @lucassegoviaolan5370
    @lucassegoviaolan5370 2 หลายเดือนก่อน

    Thank You!! How you apply it to 3 and 4 wire transmitter?

  • @khuwaylid1677
    @khuwaylid1677 2 ปีที่แล้ว +1

    Loved your content

  • @MrAbuhaidar
    @MrAbuhaidar ปีที่แล้ว +1

    Good content

  • @edisupono2335
    @edisupono2335 2 ปีที่แล้ว

    Good 👍

  • @user-iq4mu1is5d
    @user-iq4mu1is5d ปีที่แล้ว +1

    Nice video pro

  • @maricelalexe7193
    @maricelalexe7193 ปีที่แล้ว +1

    Very nice

  • @owendarroch6366
    @owendarroch6366 หลายเดือนก่อน

    I've got a question for you, today I was testing a pressure transmitter which had been configured to be a flow meter. It was installed as a two-wire instrument. So when testing I powered the DP metre with 24 volts and I measured the milliamp outputs on the test points. At my LRV with a Beamex MC6 I measured a credible reading of around 4 mA, however, moving the test leads to a fluke 707, I had a current reading of around 1.7mA at LRV, can you think of an explanation for this??

    • @pokyu2853
      @pokyu2853 หลายเดือนก่อน

      Try DA trim

  • @michaelcostello6991
    @michaelcostello6991 ปีที่แล้ว +1

    Does polarity of meter matter in series when measuring current.

    • @InstrumentCalibration
      @InstrumentCalibration  ปีที่แล้ว +1

      Yes...You must need to connect negative terminal of transmitter to 400 mA(red probe) terminal and common probe to negative terminal of power supply to measure mA value.
      Please let me know if you need any further help.

    • @michaelcostello6991
      @michaelcostello6991 ปีที่แล้ว +1

      @@InstrumentCalibration t
      Thank you for clarifying. What would happen if you got polarity wrong when measuring the current

  • @serdarkaraca1332
    @serdarkaraca1332 3 หลายเดือนก่อน

    Why do connect to negative terminal

  • @muhammadabid688
    @muhammadabid688 2 ปีที่แล้ว +1

    How to generate 4 to 20 milliampere signal inorder to check our transmitter

  • @Alfred2226
    @Alfred2226 7 หลายเดือนก่อน

    yes like the pdf of this video

  • @ydrissambarke3923
    @ydrissambarke3923 ปีที่แล้ว +1

    I want know if possible have version PDF please

    • @InstrumentCalibration
      @InstrumentCalibration  ปีที่แล้ว

      Hello
      I don't have it at present. But i will create one for you in future

  • @deepakgawali1774
    @deepakgawali1774 ปีที่แล้ว +1

    How to check 4 to 20 mimli ampeare analog input in panels

    • @InstrumentCalibration
      @InstrumentCalibration  ปีที่แล้ว

      Hello Deepak
      Thanks for your question. In order to check mA in panel, you need to connect DVM in series with negative cable. I hope you get your answer.

    • @muse069
      @muse069 ปีที่แล้ว

      @@InstrumentCalibration if connect DVM in positive terminal is possible or not?

  • @itsmesheriff7315
    @itsmesheriff7315 2 ปีที่แล้ว +1

    Why we check ma in series

    • @InstrumentCalibration
      @InstrumentCalibration  2 ปีที่แล้ว

      Thanks for asking this question. mA is analog current value, and it should always measure in series.