1st of all look battery voltage at display stop condition engine after at running condition voltage gone up to how much then tell me i will give you solution.
Have you check your fuel at tank 1st Then inter change fuel sensor connected wire 2nd After also showing low fuel level then take out sensor and check up and down it showing fuel or not 3rd At finally change fuel sensor
Then you take one KG 934 V2 display then change old display to new then look it will not show E S-Lockout after it will not show means your old display software crake so change one.
First off all look at Amper in which phase Amper goes high after then disconnected green wire which connected with city ratio coil on R phase then run dg set it will be normal.
Apne muje bohot madat kya . Thank you
Bhai ji 30 kva mai best silent dg single phase jakson Cummins/ Koel mai se kaunsa best hai
KOEL lunch Kirloskar 30kva but outerbody manufacture by Jackson&Co so Kirloskar is best then other.
@@kumardipshan7507 thanks
Bahoot Bahoot dhanyabad Sir 🙏
Sir gee Mera panel me low oil pressure indicate kar raha Hai please bataya na
First check Mobil gage there is Mobil in chamber at H or L point.
Sir ge mara be same problem ha
Well done sir keep it up
Sir KG934v2 new controller ki program kaise kare
Sir plz one doubt all Genraitar pin how to know sir
Sir I have 15 kva dg starting after 25 minut dg show high oil temp alarm and stop plz help me
What is the exact pin for parameters settings... Someone is truly 7788 somebody 5555 which is the correct pin ?
Both pin are correct but at India we use 7788 in Nepal we use 5555.
@@kumardipshan7507 ok thank u
Temp/ckt opn ?
Koel green 125kva Dg maintenance due bata raha h kya kare service karne ke bad 70 hr chala h
Setting mea jaka Maintenance Due off karna paryaga.
But one that which year genset have you.
Bahi 15 kva gen set show in oil t fault
Bhai jo e s look out aa rha hai kya kre
Crank rest kya karna
Sir 62 kva Kirloskar engine me fuel litre me display kaise kara
Sr oilp lock out a rha hi sr gen start nhi ho rha hai plz sr help me
First check lop sensor connection
Display me low charge voltage aaraha hai eska salution ka ek video banao
It's informative....thanks
I have a problem,sir.
Display showing a message "CHARGE VOLTAGE EXISTS " and then engine stops.
What does it mean ?
1st of all look battery voltage at display stop condition engine after at running condition voltage gone up to how much then tell me i will give you solution.
Sir 400 kva mein coolant sensor faulty bata raha hai
Coolant sensor bhi new replace kar diya
System ko decode kaise kare
Contact me on what's app +977-9802542128
Sir Plz make full wiring connections video
What is low charge volt
Bro 30 kva gen set - have showing E-S loc out
Display fault. You have to change Display or cut one wire of emergency stop at Display back side J2-12 port number 13 you have to cut.
Sir What to do if Generator showing stop failure?
Genset display model first?
Same gen but AGF HIGH VOLTE VY SHOWING THE DISPLY HOW WAS SOLVE THE PROBLEM PLS EMERGENCY
AVR replace
Sir 125kv
AGF LOW HZ THIS MENNING
Rely card indication lamp problem dhikare, please let me know how to solve
125kvadg kirloskar
Sir halp me
Sir sarvice alarm kaise hatayenge bataiye sir
Press ack button for 1 minute it will remove.
Thankyou sir
Wlcm and still alarm show or not
Sir my generator is showing E S Lockout, can u tell the solution
E S-Lockout means emergency switch on so first off emergency switch
You see Emergency bottom
Sir
AGF VB LOSS
ISKA KYA SOLUTION H
15 KVA GEN SET UNIT KG 934
SIR PLEASE REPLY
Have you find solution?
Bhai mahindra ka alarm kese reset karen batao plz
SPD alm kaya hota ha
+9779802542128 what's app me.
Nice sir
Agf low volt VB
What is parole
Help me sir
Look all fuse
@@kumardipshan7507 AGF over load alarm pls tell me what doing
@@soumenbiswas9813 in how much time later it's shows in which condition load or with out load it shows.
@@kumardipshan7507 without load show 10 sec
Then open alternator look at AVR there was 5Amper fuse burn change it and start.
Sar my garnetar is 82,5 kva alarm to agf vb loss
Mera mobile number hai 9754 763 888
Sir,what is A-S lock out and how to solve that problem
Auto sensing problem ( mains phase reverse)
Low voltage problem video banao
Kindly check first L1 L2 line voltage on Display .
How to rectified this type of problem
Sir please make video Kg541 settings
Sir please wiring video and troubleshooting
high engine temperature signal derihe iska matlab key he
Good
Good job
Thank u sir
Koel 40 kva genset Alarm AGF over load amp pls help solution this prlm
Please sir help this problem my nmbr 9932723150
Help me
Tell me your problem
Air coold engine me high oil presar ka Alarm de kr engine band ho rha h
What to do when it shows low hz and suddenly stops working?
1st tell me kva of your genset
Overload problem how to solve
How to solve e-s lock out
E-S Lockout means Emergency Switch kindly look first emergency outer switch then tell me.
@@kumardipshan7507 hlo
@@amarsandhu8318 hi
Hlo
My generator 82.5 kva hai
Alarm a raha hai
High oil press detected switch
सर इसी मॉडल का जनरेटर हमारे पास है उसका इंजन चालू है परंतु वह करंट सप्लाई नहीं कर रहा है और उसके अंदर का पंखा भी चालू नहीं हो पा रहा है। प्लीज हेल्प
AGF LOW VOLTAGE VR likha aa raha hai sir kya kare
प्रॉब्लम को हम बताएं
A gf VB alarm problem Sar bataiye na please
In my generator showing tacho lock out don't know why generator is 15kv
First off all your genset manually start or not from display.
@@kumardipshan7507 how to start manually Genset sir
Howw ccan ii ssolve loow agff volt
15kva low fuel level problem?
Have you check your fuel at tank 1st
Then inter change fuel sensor connected wire 2nd
After also showing low fuel level then take out sensor and check up and down it showing fuel or not 3rd
At finally change fuel sensor
@@kumardipshan7507 finally change fuel sensor bro thanks
@@kumardipshan7507 no speed signal problem bro?
@@kumardipshan7507 pls reply bro
@@kumardipshan7507 bro pls
Low oil pressure aa rha h
I tried to off emergency switch but still showing same thing
Then you take one KG 934 V2 display then change old display to new then look it will not show E S-Lockout after it will not show means your old display software crake so change one.
Hi sar
Alarm setting closed is not a solution bro.... fill require ...
I know alarm closed is not solution but sometimes we have follow that bro.
AGF low volt VR alarm come
Tku
A gf alarm problem
AGF VOLT HIGH FAULT AA RHA H KYA KARE
First off all look at Amper in which phase Amper goes high after then disconnected green wire which connected with city ratio coil on R phase then run dg set it will be normal.
alarm problem
Crank rest
1st Look at first on / off switch is loose or tight
2nd on / off switch back side 4 wire continuti check
All panel AGF los
Howw ccan ii ssolve loow agff volt