Hi, I have to program a G120 CU240E in a grafcet so it can control the speed of a washing machine motor, the point is I can't figure out which are the words in need to make this possible as it to make the G120 switch to an ON state we use 16#47E, which registers do we use to increase or decrease the motor speed?
Hi dear, As per your mail, check below details. For control word : check I/O's address of PLC & first pass 16#47E , after for enable pass 16#47F For speed reference : pass 1word value on IO's address. Example : My s7-300 PLC if I take free Telegram then it will assign starting 256 address. So, -first pass 16#47E in pwq256. -After second cycle pass 16#47F in again same PQW256. -Next loop take memory or analog value iw64 & pass to PQW258. In short for Speed reference take second word of IO address. If you still facing problem, feel free to contact me. Thanks & Regards, Dhaval Vora
hello Brother, firstly thank you for your efforts, I tried to apply your instructions carefully to my G120 drive, but the motor remain stopped, knowing that i didn't have any communication issue, i was able to pass to the online mode without problem, to make sure that the telegrams pass to the drive i opened the drive diagnostic window (in online mode), just to watch the control word, and there i realised that although i move the hex value to the address, the control world remain in it's prior value, it doesn't change ..., so please if there is something that i should do with the drive, perhaps some prior configuration... please tell me, i'm stucked in this point..
If your value is not change. Means communication not done properly. Plz. Again check. Inside drive check communication paramer. That should be process field bus....
@@DhavalVoratechsystems yes it doesn't change, but when i start the drive from the local button (the green) the motor run, and moreover i can perseive that the first bit of the control word pass to 1 (from the diagnostic window), so as you said maybe i missed something in the communication parameter, but how can i get into this parameters and how can i edit it, (do you talk about the p1000 ? )
hi Dhaval, i want to run drive from control panel but when i click the drive on(green button) i m getting this alarm Switch on disable active (ISCOA: 30020) The switch on disable of the drive is active! how can i solve this problem ?
hello i have a s7 1200 and g120. here u generate hexcode for controling of drive. but how i can control using individual bit of control word and how to send this from plc to drive with profinet communication. what will be the input and output.
Change Number 9586779044
thank you sir for this tutorial
please can you give me your facebook page to contact you please
Hello sir can u give Siemens training???
Thanks..keep uploading full course...with scada
Thank you sir.....
Your video has been a support for us....
Thank you sir for your precious efforts
Thanks dear
Hi, I have to program a G120 CU240E in a grafcet so it can control the speed of a washing machine motor, the point is I can't figure out which are the words in need to make this possible as it to make the G120 switch to an ON state we use 16#47E, which registers do we use to increase or decrease the motor speed?
Hi dear,
As per your mail, check below details.
For control word : check I/O's address of PLC & first pass 16#47E , after for enable pass 16#47F
For speed reference : pass 1word value on IO's address.
Example :
My s7-300 PLC if I take free Telegram then it will assign starting 256 address.
So,
-first pass 16#47E in pwq256.
-After second cycle pass 16#47F in again same PQW256.
-Next loop take memory or analog value iw64 & pass to PQW258.
In short for Speed reference take second word of IO address.
If you still facing problem, feel free to contact me.
Thanks & Regards,
Dhaval Vora
Fine Sir, Please make a videos about servo control and stepper motor control using simatic manager and tia portal
sir can you share video regarding non siemens device connect on profinet with siemens PLC how read and write input and data register
hello Brother, firstly thank you for your efforts,
I tried to apply your instructions carefully to my G120 drive, but the motor remain stopped, knowing that i didn't have any communication issue, i was able to pass to the online mode without problem,
to make sure that the telegrams pass to the drive i opened the drive diagnostic window (in online mode), just to watch the control word, and there i realised that although i move the hex value to the address, the control world remain in it's prior value, it doesn't change ..., so please if there is something that i should do with the drive, perhaps some prior configuration... please tell me, i'm stucked in this point..
If your value is not change. Means communication not done properly. Plz. Again check. Inside drive check communication paramer. That should be process field bus....
@@DhavalVoratechsystems yes it doesn't change, but when i start the drive from the local button (the green) the motor run, and moreover i can perseive that the first bit of the control word pass to 1 (from the diagnostic window), so as you said maybe i missed something in the communication parameter, but how can i get into this parameters and how can i edit it, (do you talk about the p1000 ? )
@@DhavalVoratechsystems the actual value of p0700 is 0, is this correct, because i saw in another video that it should be fixed at 6?
@@youssefalaoui6894 it should be 6
hi Dhaval,
i want to run drive from control panel
but when i click the drive on(green button) i m getting this alarm
Switch on disable active (ISCOA: 30020)
The switch on disable of the drive is active!
how can i solve this problem ?
Hi , How to change the set point ?
❤
Hi
Can you tell me how to control position with digital encoder?
hello
i have a s7 1200 and g120.
here u generate hexcode for controling of drive. but how i can control using individual bit of control word and how to send this from plc to drive with profinet communication. what will be the input and output.
Please share us how to use DI and Do of Sinamics Drive Through TIA Portal
hi dhaval,
Can u please upload g120 technology object programming.How to use that. And Positioning block.
Hi did you get you answer ? If yes can you please share it. Thanks
sir please make video G120C with plc & HMI communication
How did you assign ip address to drive in this project
For IP address double click on Drive port and in properties you will find
Video is good but what's wrong with the voice? Its really inaudible and irritating.
CAN YOU TELL ME WHY ((..16#47E =10001111110///// BUT IN THIS VIDEO 16#47E=0111111000100000)))) PLEASE...THANKS IN ADVANCE..
you can count from high bit 15 to 1= 0000010001111110= 47E
Can you send me this material?
THANKS
voice is very low......
please reply ASAP