HVAC - Cooling coil + Calculations ❄️❄️❄️

แชร์
ฝัง
  • เผยแพร่เมื่อ 1 ต.ค. 2024

ความคิดเห็น • 68

  • @EngineeringMindset
    @EngineeringMindset  7 ปีที่แล้ว +8

    ⚠️ *Found this video super useful?* Buy Paul a coffee to say thanks: ☕
    PayPal: www.paypal.me/TheEngineerinMindset

    • @masterchef6694
      @masterchef6694 7 ปีที่แล้ว

      The Engineering Mindset I would like to buy you a coffee....but in my country pay Pal is not available

  • @kingkongtiger
    @kingkongtiger 7 ปีที่แล้ว +6

    Thanks for the great video. Please make more videos on HVAC system designs with calculation in different buildings. (May be start with something like single zone design with cooling load & fresh air requirement etc)

  • @اوسحسن-م7ت
    @اوسحسن-م7ت ปีที่แล้ว

    hi..i have a question in different subject if you can help
    in evaporative cooling...is it useful to decrease the temp of water spry or water washer
    ex: if out air 36c,60%rh..on psy with 90% evaporative efficiency.h ll get a 28c db and 90%rh..
    so if i enter a 7c cold water to the washer .will i get a cold air temp....with knowing that in 100%humidity the db is about 27c
    thanks

  • @EngineeringMindset
    @EngineeringMindset  5 ปีที่แล้ว

    Learn *COOLING LOAD CALCULATIONS* here: th-cam.com/video/0gv2tJf7nwo/w-d-xo.html

  • @honestman276
    @honestman276 ปีที่แล้ว

    We can make industries but the citizens, politicians and bureaucrats are utterly corrupted in Bangladesh. So I don't dare to make and to run the business on it. Thanks from Bangladesh.

  • @trisafesales9392
    @trisafesales9392 7 ปีที่แล้ว +5

    Hi Paul, superb illustrations and explanations..Just one small doubt Do we have to get RH of 100% for air coming out from the cooling coil in order to achieve the desired cooling effect...

    • @Hum4292
      @Hum4292 2 ปีที่แล้ว

      I was also thinking of the same matter. Unless we use to humidify the cool air after evaporator coil, the RH will not rise to 100% RH.

    • @jeffreyfontenot8803
      @jeffreyfontenot8803 ปีที่แล้ว

      Yes, you want it to "rain" on the coil, wringing all that water out of the air. That way when you warm 55 F 100% RH air up to 75 F it is at 50% RH.

  • @robertingersoll5289
    @robertingersoll5289 4 หลายเดือนก่อน

    Good lesson. Small correction - the condensate water term should be negative.
    energy in = energy out
    h ent air = Q coil + Q condensate + h lvg air
    Q coil = Delta air h - Q condensate

  • @nse08
    @nse08 3 ปีที่แล้ว +1

    Hi, I believe that your formula for Q should not include mw*hw, because this latent heat is included in ma*(h2-h1), am I wrong?

  • @JayMehta60
    @JayMehta60 7 ปีที่แล้ว +3

    Hi, thanks for the video!
    How do you select a coil to be used in order to achieve a desired cooling capacity? In other words I would like to understand how must I design the coil geometry to achieve certain cooling capacity, with the water inlet & outlet temps. known, air entering temp known etc.

    • @EngineeringMindset
      @EngineeringMindset  7 ปีที่แล้ว

      Coil geometry and design gets very complex. It takes hours of calculations, you should google the formula Q=U*A*DT as a starting point

  • @ramamanikantadondapati1043
    @ramamanikantadondapati1043 6 ปีที่แล้ว +1

    Sir you are saying the relative humidity is 100 persent. But human comfort is 50-55 percent. And also please make an video about relative humidity, specific humidity, dewpoint.

  • @chriscoop9
    @chriscoop9 5 ปีที่แล้ว +1

    0.9m3/kg entering? not 0.887m3/kg? confused....

  • @bhushanpawar8855
    @bhushanpawar8855 5 ปีที่แล้ว +1

    Sir water inlet temp.to.the cooling coil in ahu is same as chiller set point temperature for calculating kw of cooling coil

  • @wojtek_sanitarnik
    @wojtek_sanitarnik 6 ปีที่แล้ว +1

    Do you have video about BF & CF fsctors of cooling coil. That would be interesting video. Thanks!

  • @basilhamdy542
    @basilhamdy542 6 ปีที่แล้ว +1

    Please can you tell us what is the next step after calculate the cooling coil capacity , how to select the correct coil for your application

  • @NadeemKhan-lh6vv
    @NadeemKhan-lh6vv ปีที่แล้ว

    How did you find water out temp 15c

  • @jeffreyfontenot8803
    @jeffreyfontenot8803 ปีที่แล้ว

    What about coil efficiency? Are we assuming 100% efficient heat transfer? What is a typical cooling coil efficiency?

  • @zeegohar8352
    @zeegohar8352 3 ปีที่แล้ว

    Does the relative humidity affect the enthalpy?
    According to the air properties i find 99 kJ/kg for h1. But paul uses 78 kJ/kg. What is the reason for this?

  • @levierdragon
    @levierdragon 7 ปีที่แล้ว +3

    You sound Aussie. I assume you're a mech engineer working in HVAC. How's the HVAC job market? I'm planning on heading back to uni to study engineering.

    • @EngineeringMindset
      @EngineeringMindset  7 ปีที่แล้ว +5

      Hey Roy, I'm not Aussie, but I have a mixed accent that often confuses people. I'm a dual mechanical and electrical engineer, working in building services consultancy. In my opinion HVAC is a great career path. You will likely be a mobile engineer and move around different sites meeting very interesting people, plus a lot of equipment is on the roof so you get great views over cities. It's also a job which will be less affected by the automation revolution, and it's in growing demand. No matter how the financial markets affect the world, there will always be the need for an engineer in a building.

  • @kylevencer7709
    @kylevencer7709 5 ปีที่แล้ว +1

    hello. how to get the cooling water mass flow rate?

  • @keithwo1
    @keithwo1 2 ปีที่แล้ว

    good day kind question for this group, i just want to know if there is a formula for cooling capacity which fcu is converted from dx to chilled water or how many percent does of cooling load will be lost if converted?, thank you who ever answers,

  • @malikshehryar7145
    @malikshehryar7145 6 ปีที่แล้ว +1

    Pual my question is when three way valve is activated then in this situation how much water enters into the cooling coil ? Or water completely bypass the cooling coil and goes back in to return line.

    • @EngineeringMindset
      @EngineeringMindset  6 ปีที่แล้ว +1

      depends on the system, you can check the valve manufacturers documents to see the correlation between position and flow rate

  • @mohammadalshaikhhasan5091
    @mohammadalshaikhhasan5091 2 ปีที่แล้ว

    Perfect and useful.
    I wish new videos about cooling coil water pressure drop and air pressure drop.
    but for the latent heat cooling load calculation, you assumed hw = hf ( heat of vaporization vs heat of saturated liquid)..why?

  • @kuleyedi
    @kuleyedi 4 ปีที่แล้ว

    Could you also explain heating coil capacity? As far as ı know , at heating capacity we should not add humidity counts to Q and Other hand When we cool room , sometımes ıt concludes excessive humidity problems, how we get rıd of it technically. Thanks for efforts🙏🏻

  • @ismailmasoodshaikh7757
    @ismailmasoodshaikh7757 2 ปีที่แล้ว

    Thanks for this very useful information, can you please let me know the water side pressure drop of cooling coil and the refrigerant required in DX coils for 1 TR of cooling

  • @butchruelos4070
    @butchruelos4070 5 ปีที่แล้ว

    The specific humidity unit in the condensate water mass flow rate calculation is wrong. It should be in kg/kg.

  • @mohammadalshaikhhasan5091
    @mohammadalshaikhhasan5091 5 ปีที่แล้ว

    Thanks for the great video.. so helpful
    In case we have AHU designed and the evaporator coil sized to specific capacity, can we increase the airflow to achieve higher capacity?
    A chiller designed to specific capacity and connected to AHU to achieve a certain indoor temperature and air change rate, whats could happen if the AHU coil changed to another one smaller with the same high air flow?
    The face velocity will be higher?
    The effects on sensible capacity?
    The effects on latent capacity?
    Thanks again

  • @00ABBITT00
    @00ABBITT00 ปีที่แล้ว

    A better teacher than the $3200 class my union provides.

  • @jayhaantharumugam6703
    @jayhaantharumugam6703 6 ปีที่แล้ว

    How to calculate the Airout Temperature? How did you arive at 15 Deg C. Please provide calcs?

  • @amitstorm500
    @amitstorm500 3 ปีที่แล้ว

    can you give calculations steps for immersed helical coil in a stationary water tank carrying hot air?

  • @alimarzooq5051
    @alimarzooq5051 5 ปีที่แล้ว

    Thanks for this helpful video. I have a question about the air pressure drop, how to calculate it? If you can provide me with some sources it will be better

  • @mohammedowais4793
    @mohammedowais4793 7 ปีที่แล้ว +1

    Hii sir....... Waiting for new videos

  • @Aznd007
    @Aznd007 7 ปีที่แล้ว +1

    Our Indoor design will be 23*C , RH - below 60 % .
    in this case the air which coming out from coil air having almost 100% RH !!! Here how will you control this RH Level??

    • @EngineeringMindset
      @EngineeringMindset  7 ปีที่แล้ว +1

      It's just an example. You can sub cool it and then reheat but a more efficient way is to use a Desiccant
      Dehumidification unit.

    • @Aznd007
      @Aznd007 7 ปีที่แล้ว

      The Engineering Mindset Thanks for your advice!

    • @moneeshs8127
      @moneeshs8127 6 ปีที่แล้ว

      The air off the coil will be 100% rh , on entering the room i.e air off the grill it will mix with the room condition to make 60%rh i.e 13dec will mix with room condition so it will make 23dec c..since the dbt increase simultaneously the rh tends to reduce

    • @moneeshs8127
      @moneeshs8127 6 ปีที่แล้ว

      The Engineering Mindset for maintaining 50-60 rh any ancillary is not required for comfort application

  • @ZeeshanKhan-fg7ry
    @ZeeshanKhan-fg7ry 5 ปีที่แล้ว

    Can u tell me about coil in ahu..
    Meaning of 4/6 row coil..
    When we'd day this ahu is 4 row or any row???

  • @Mateoshful
    @Mateoshful 6 ปีที่แล้ว

    Hello The engineering mindset. I would like to study more about HVAC system. And planning to study abroad. Is there any recommendation which is good university or course? Hope you will reply asap Thank you

    • @EngineeringMindset
      @EngineeringMindset  6 ปีที่แล้ว

      Depends where you would like to study. Try courses approved by CIBSE and ASHRAE, which cover building services.

  • @ravikumarginne1125
    @ravikumarginne1125 4 ปีที่แล้ว

    i want to calculate my cooling coil capacity for adding condensing unit more.

  • @congthinh3979
    @congthinh3979 7 ปีที่แล้ว +1

    you teached me, HVAC and English. thank you!

  • @engineersingulf6968
    @engineersingulf6968 6 ปีที่แล้ว

    here you subtract latent heat why? in the equation above it is adding

  • @partha636
    @partha636 7 ปีที่แล้ว

    In the cooling load calculation , Q_dot should be negative i.e. -78.5 KW. Why have you taken it positive?

    • @EngineeringMindset
      @EngineeringMindset  7 ปีที่แล้ว

      partha sarathi Das over time engineers find short cuts and this is one of them, in the real world no one asks for a negative 75kW heat exchanger. You're right it is a negative value though.

  • @lukeallison6618
    @lukeallison6618 6 ปีที่แล้ว

    Dont you need the Dt to be able to ascertain the 4.67kg/s? How would you have this info without knowing the delta to begin with?

  • @jfasjfas
    @jfasjfas 7 ปีที่แล้ว +1

    esp calculation pls

  • @rezanoormohammadi6914
    @rezanoormohammadi6914 3 ปีที่แล้ว

    How can we calculate cooling water mass flow?

  • @babaksp4235
    @babaksp4235 7 ปีที่แล้ว +1

    Beautiful, excellent

  • @elliotmott1869
    @elliotmott1869 6 ปีที่แล้ว

    what if you have a building with hundreds of FCU's in, there must be a quicker way then this

  • @imiuli1304
    @imiuli1304 ปีที่แล้ว

  • @tiagoferreira6713
    @tiagoferreira6713 7 ปีที่แล้ว

    Hi! Thank you for your great job! You really understand a lot of things about hvac systems and their components! Please don't stop and continue the great job!
    Just gonna suggest some themes that I find interesting to understand better so you can maybe had to your list, if you find them interesting:
    - the various psychometrics evolutions of the air passing through the coils and other components (water cooling and heating coil, dx heating and heating coil, just an electrical resistance, humidification and dehumidification, and maybe others)
    - how a boiler works and main components (domestic ones (traditional and condensation ones) and industrial ones as you show in one of the videos)
    - how other type of cooling towers works
    - the tabs systems (thermo active building systems)
    Thank you once again and sorry for possible bad english
    Best regards

  • @SubhamCreative.613kviews
    @SubhamCreative.613kviews 5 ปีที่แล้ว

    ok

  • @dantheman9909
    @dantheman9909 6 ปีที่แล้ว +2

    How come you have 100% RH when the air has been conditioned through the cooling coil? Keep up the good videos 👍

    • @LM_25_11
      @LM_25_11 4 ปีที่แล้ว

      At lower temperatures vapour gets saturated even at lower partial pressure. So for a vapour it's easy to attain high relative humidity ,since relative humidity is the ratio of partial pressure of vapour and partial pressure of vapour at saturation.

  • @mathewsvarghese6146
    @mathewsvarghese6146 7 ปีที่แล้ว +1

    Can you please upload the duct installation videos based on shop drawings

  • @jasonanderson7343
    @jasonanderson7343 7 ปีที่แล้ว +1

    Great stuff. Hope to see more about HVAC calculations in the coming videos. Well done

  • @ibrahimosman3393
    @ibrahimosman3393 7 ปีที่แล้ว +1

    Never stop