  • Modulating Run Mode
    If the function selection switch has been set to one of the four
    modulating control settings - and if the actuator is wired
    correspondingly (see Fig. 10) - then as soon as operating
    power is applied, the shaft adapter will run first completely
    counterclockwise and then completely clockwise (see also
    section “Adaption”), after which it will run according to the
    control signals applied.
    Table 1 describes, for the floating mode, the shaft adapter
    behavior (“stops,” rotates “CCW,” or rotates “CW”) in
    dependence upon the control signals applied to terminals 3
    and 4 and upon the function selection switch setting.
    Table 2 describes, for the 2-position mode, the shaft adapter
    behavior (“stops,” rotates “CCW,” or rotates “CW”) in
    dependence upon the control signals applied to terminals 3
    and 4 and upon the function selection switch setting.
    Table 3 describes, for the modulating mode, the shaft adapter
    behavior (“stops,” rotates “totally CCW,” rotates “totally CW,”
    runs to “proportional” position, or runs to “50%” of max. stroke)
    in dependence upon the control signals applied to terminals 3
    and 4 and upon the function selection switch setting.
    Supply voltage: 24 Vac/dc -15%/+20%, 50/60 Hz.
    Nominal voltage: 24 Vac/dc, 50/60 Hz.
    All values stated hereinafter apply to operation under nominal
    voltage conditions.
    Power consumption:
    MN7505: 5 VA / 2 W.
    MN7510: 5 VA / 2 W.
    Control signal:
    Modulating: 0)2...10 Vdc.
    Floating/2-Position: 24 Vac/dc.
    Ambient limits:
    Ambient operating limits: -5...+140° F (20...+60° C).
    Ambient storage limits: -22...+176° F (-30...+80° C).
    Relative humidity: 5...95%, non-condensing.
    Safety:
    Protection standard: IP54.
    Protection class: II as per EN 60730-1.
    Overvoltage category: II.
    Lifetime:
    Full strokes: 60000.
    Repositions: 1.5 million.
    Mounting:
    Round damper shaft: 3/8 in…5/8 in. (9.5...15.9 mm).
    Square damper shaft: 1/4 in…1/2 in. (6.4...12.7 mm);
    45° steps.
    Shaft length: min. 1-5/8 in. (41.3 mm).
    End switches (when included):
    Rating: Class II.
    Triggering points: 5° / 85°.
    Torque rating: 44 lb-in. (5 N·m) / 88 lb-in. (10 N·m).
    Runtime for 90°:
    mod. (dc / 50/60 Hz ac) 90 sec.
    floating (dc / 60 Hz ac) 90 sec.
    floating (50 Hz ac) 110 sec.
    Rotation stroke: 95° + 3°.

ความคิดเห็น • 14

  • @himalaya5754
    @himalaya5754 หลายเดือนก่อน

    nice vedio

  • @kv848
    @kv848 หลายเดือนก่อน

    Bro, who will do this connection , electri or mech engineer ?

    • @EXPLORINGPIPING
      @EXPLORINGPIPING  29 วันที่ผ่านมา +1

      HVAC engineer can do it, very simple .
      Down load wiring diagram or go through TDS

  • @PinkyKumari-xf7tp
    @PinkyKumari-xf7tp ปีที่แล้ว

    Good morning sir 😊

  • @smali558
    @smali558 ปีที่แล้ว

    Good morning sir
    Sir I wanted to talk to you for only 10 minutes.about project planning and management etc please give me your valuable 10 minutes. Hope for your precious response,
    thank you
    regards
    Ali mep engineer

  • @immucreation29
    @immucreation29 ปีที่แล้ว

    Hlo sir/bhai maine mail kiya h aapko please reply kijiye