    Hello! I have 2x Deye 5k inverters (and I want them to work in parallel), a single-phase grid and one single-phase generator with start-input (NO relay) for solar inverters. And I have a couple of questions:
    1. How should I connect generator to inverters? Should I connect it to only one of them or to both (GEN-port)? How should I connect G-V out of each inverter (should I connect them in parallel) to start the generator?
    2. What is powered from generator when grid is de-energized? Only battery charger or backup load directly also? (I mean: how critical is frequency stability of generator and what about it's power?)
    3. Am I right that I should configure "rated power" of generator as 1/2 of actual generator's rated power on each of 2 inverters?
    Thank you!

  • @JammNatlada
    @JammNatlada 13 วันที่ผ่านมา

    Can these be done without using battery?

  • @jermainwhyte6894
    @jermainwhyte6894 10 หลายเดือนก่อน

    Do you have a 12kw split phase 120/220 volt USA version that they are selling on alibaba? I want to get that size for Jamaica. I want to make sure it’s 120/220 volt split phase and not 220/230 volt. Thank you. Also do you have an official site I can buy from?

  • @Kiril_Bulgaria
    @Kiril_Bulgaria ปีที่แล้ว

    Hello, could in the three phases parallel diagram CT to be replaced with smart meter?

  • @obusobusson736
    @obusobusson736 10 หลายเดือนก่อน

    Why is all the three , three-phase hybrid inverters, connected in parallel marked as master in the video? Shouldn't it be master --> slave--> slave?

  • @ZanaAwni
    @ZanaAwni ปีที่แล้ว +1

    hello , can i connect only two single phase inverter in parallel for a three phase load? and if yes how to do that.

    • @houcineamaidi499
      @houcineamaidi499 ปีที่แล้ว +1

      no u can't becouse the load need three phase not two phase for example (motor electrical )

    • @ZanaAwni
      @ZanaAwni ปีที่แล้ว +1

      @@houcineamaidi499
      thank you so much for your help

    • @DeyeInverter_official
      @DeyeInverter_official  ปีที่แล้ว

      Hi.No you can't, you must use three phase inverters

  • @Black74c
    @Black74c ปีที่แล้ว

    Need help on connecting 2x 8kw Deye Inverter in parallel, after programming the inverter do I merge the Load output cables ? Example: Master Live cable to Slave Live cable...am overthinking

    • @makunan
      @makunan ปีที่แล้ว

      Yes, the diagram are the same for home load/grid output wires (same connector) and backup load wires, you need merge in their specific busbar. One for homeload/grid Line, other for neutral and other for Ground and the same configuration for backup load.

    • @DeyeInverter_official
      @DeyeInverter_official  ปีที่แล้ว +1

      Hi,the load cables also need to be connected in parallel

  • @aldymcpndg14
    @aldymcpndg14 3 หลายเดือนก่อน

    Hi deye, why is it on 16kw hybrid parallel connection setup, the master battery and slave battery isn't connected and only the master battery is connected to master deye hybrid inverter?

  • @sanyapatm
    @sanyapatm 10 หลายเดือนก่อน

    Can we do parallel 8kw deye hybrid with 5kw deye hybrid

  • @munkhnasan5589
    @munkhnasan5589 9 หลายเดือนก่อน

    Hello, How to connect the CAN wire to 5 inverters in parallel?

    • @DeyeInverter_official
      @DeyeInverter_official  8 หลายเดือนก่อน

      This can't be done, the battery only communicates with the master

  • @FMG-MicroGas
    @FMG-MicroGas 5 หลายเดือนก่อน

    Can I parallel 16KW and 10KW hybrid inverter?