WALK IN FREEZER NOT WORKING

แชร์
ฝัง
  • เผยแพร่เมื่อ 5 ก.พ. 2025
  • This was a call on a walk in freezer that was not working properly, I found that the unit was iced up but it was only the top half of the evaporator coil, I diagnosed a bad txv based off of the ice pattern and an extremely high superheat. I replaced the txv along with some door hinges and the unit is now working properly.
    To support my videos please visit Patreon
    Patreon / hvacrvideos
    TOOL LINKS
    FieldPiece JobLink probes amzn.to/2WfQTRI
    Samsung Tablet amzn.to/2EOYL1U
    Fieldpiece SC660 Wireless Swivel Clamp amzn.to/2JXji7I
    One way screw removal tool amzn.to/2ZlGlgP
    For Optimizing my videos I use Tube Buddy
    www.tubebuddy....
    Please consider subscribing to my channel and turning on the notification bell by clicking this link goo.gl/H4Nvob
    Social Media
    Facebook / hvacr-videos. .
    Instagram / hvacrvideos
    For any inquiries please contact me at hvacrvideos@gmail.com

ความคิดเห็น •

  • @cranium33333
    @cranium33333 5 ปีที่แล้ว +28

    Dude watching your videos. Any customer would be lucky to have you as the tech that comes out. So thorough and precise! Such amazing work ethic! You rock!

  • @lemualthomas5670
    @lemualthomas5670 ปีที่แล้ว +3

    Wow, I'm totally impressed. We have an walk-in- Freezer repair coming up. Seeing this make me appreciate the time they spent working on it. Thanks.

  • @imafatfatpig
    @imafatfatpig 5 ปีที่แล้ว +3

    Another awesome video. The proper torque setting is when your bad wrist clicks. 👍

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว

      Exactly

    • @captainkirk7702
      @captainkirk7702 5 ปีที่แล้ว +1

      But he was using the other, all I heard was a German torque, goodintight!

  • @garywarren5800
    @garywarren5800 4 ปีที่แล้ว +3

    I have found to braze those fittings that have the ability to fall off , easier to braze if I first squeeze the fitting, while on the pipe, just barely enough to get out of round ( and I mean barely, where its almost impossible to see with naked eye) then turning the fitting half a turn so it binds and can not fall off. Old pipefitters trick.

  • @jarheadshooter6452
    @jarheadshooter6452 4 ปีที่แล้ว +4

    I did a time comparison on my guys and me trying to defrost with the fans an motors in place compared to removed. We gained an average 30 minutes removing the fans and motors. And it also cost me 3 motors by not removing them!

  • @gravis346
    @gravis346 5 ปีที่แล้ว +4

    Love your videos and that fact that you are honest person and are thorough when diagnosing a repair. BTW, tell 'em to make shakes with the drippy soft serve, lol.

  • @mainj54
    @mainj54 5 ปีที่แล้ว +6

    When I have to insulate a suction line and it is cut loose from the coil I slip the armaflex on line and compress it and hold it in place with a tubing cutter. That way you have no seams and potential for leaks. Also it looks clean.

    • @proamlito07
      @proamlito07 5 ปีที่แล้ว

      Very clever , thanks for the tip

  • @josephsantos7047
    @josephsantos7047 5 ปีที่แล้ว +1

    Again amazing. My work has a unit like this and since I signed up for classes ( I start in December for HVAC) I’ve been looking at the unit, and find it more and more fascinating! You’re a big help.

  • @sparkytech8787
    @sparkytech8787 5 ปีที่แล้ว +3

    I find when unsweating I grab the pipe to be removed when i see the solder shine or start melting I find it speeds up the heat transfer to the solder, by holding early the pliers absorb a lot of heat, especially in confined places. you will half the time.great job master.

    • @proamlito07
      @proamlito07 5 ปีที่แล้ว +1

      I do the same bro , cheers

  • @rafaelgomez4304
    @rafaelgomez4304 5 ปีที่แล้ว +3

    Good repair! Had same issue this week and order the same parts. Unfortunately the repair has to be quoted and approved before I do it.

  • @arthouston7361
    @arthouston7361 4 ปีที่แล้ว +2

    It would be so smart if they used a TEV where the head could be replaced. The Carrier slab coil units have so many of those valves failing, and they are such a pain to replace them. It's always during the hottest week of the year when they approve the work, too. On a Lennox L series, I can just change the head and clean the rod, and done!

  • @justinkearney8679
    @justinkearney8679 5 ปีที่แล้ว +1

    I usually valve off the liquid line service valve so you can still monitor high side pressure on the receiver. Just winging that out there to ya. Great videos, Great work ethic!
    ✌✌✌

  • @soloryderrr
    @soloryderrr 5 ปีที่แล้ว +3

    Difficult repair... I can see that was not a easy one. Good to see you going the extra mile and redoing that suction line and the solenoid. Most techs would look at that and not redo.. I feel similar on installs and repairs that I do.. Try and do extra work to give yourself a higher percentage of first time success which saves time and stress and saves customer money.

  • @petethefridge
    @petethefridge 5 ปีที่แล้ว +1

    Dan D. I think using steam over hot water will be more economical in both power and water. I used it for years. Incidentally it was shown to me by my son, also in the trade. You never stop learning.

  • @delta_airsystems
    @delta_airsystems 5 ปีที่แล้ว +1

    Brilliant video and explained like a pro.👍One thing I noticed is that why is the wiring all over the place on the outdoor units. Here in the uk I always run cables in copex or use SY cable which is like a flexible armoured cable and not easy to chew by mice & rats...

  • @Robyrich2377
    @Robyrich2377 5 ปีที่แล้ว +1

    You’re a very good tech and have a tons of knowledge I look up to you and I salute you sir

  • @walkingfreak
    @walkingfreak 5 ปีที่แล้ว +5

    Funny enough me being someone that lives in the north, i kind of hate working in a walk in freezer. I'd rather do medium temp all day long haha. It amazes me at how long some of these jobs can take but to be expected.

  • @FlyEaglesFly19111
    @FlyEaglesFly19111 5 ปีที่แล้ว +3

    I've had more emerson TXV vs all others over the years fail. They stink cause you cannot rebuild them. At this time sporland is all I use and always have great results. Different cartridges make the magic. Chris have them empty out the shelves..work smarter and safer. Be safe out there!

  • @benfarid1493
    @benfarid1493 3 ปีที่แล้ว

    nice work mate, good on you.
    warm greetings from Australia

  • @joevinski1
    @joevinski1 5 ปีที่แล้ว +13

    Heard the elbow click !!!! Know it’s torqued correct

  • @tonystrollo193
    @tonystrollo193 5 ปีที่แล้ว +2

    Should have a trap on SL, that's why the oil in SL, no P trap, to increase velosity and carry oil up the SL. Heard you say 8 to 10 degrees superheat, for freezer ? thats a bit high. And please make sure you have proper ventilation when using a open flame inside any closed Walkin's." Phosgene gas " very deadly. I realize you were working in difficult circumstances, been there many times. Very Good job, well done Chris

    • @prettycureforever7102
      @prettycureforever7102 4 ปีที่แล้ว +1

      8-12 is perfect for both super heat an subcool you don't want any higher than that

    • @jersonmontero2710
      @jersonmontero2710 4 ปีที่แล้ว

      8 a 12 ala salida del evaporadol

  • @KashMan91
    @KashMan91 5 ปีที่แล้ว +3

    1000% on taking the motors blades and the mounts out

  • @snoopyjc
    @snoopyjc 4 ปีที่แล้ว +2

    Nice adjustable torque wrench dude! :-)

  • @johnsmithjr5498
    @johnsmithjr5498 5 ปีที่แล้ว +1

    You can use your tubing cutters to hold the pipe still when brazing like you were. It also adds weight to keep the pipe from falling.

  • @garywarren5800
    @garywarren5800 4 ปีที่แล้ว +2

    What are you using to get the gauges to go to your Samsung device? Do you have to use the job link transmitter or does it do it by itself using Bluetooth and download onto Samsung device? Thanks ahead, I have subscribed to your tools but have not seen anything yet. Thanks in advance my friend.

  • @Happyoldfashionfamily
    @Happyoldfashionfamily 5 ปีที่แล้ว +3

    Can you please do a short video on how to install the bulb clamps? I have seen many seasoned techs that can not do them properly, either they are loose or just zip tied.

  • @treverkirk8110
    @treverkirk8110 5 ปีที่แล้ว +13

    That defrost pattern would make me initially suspect incomplete defrosting(assuming the element is on the bottom of the coil). Curious why you didn’t do down that route at all?

  • @CHOMAHOMA
    @CHOMAHOMA 3 ปีที่แล้ว

    I wonder if just changing the piece of copper for the Suction line and reattaching the sensing bulb would have had a better result on the evaporator? Just for giggles to confirm if txv is bad.

  • @dynorat12
    @dynorat12 4 ปีที่แล้ว +1

    i use to keep a old filter and sight glass and use them for welding the tubing holding it all together i got tired of caring it around so i just made up a bypass tube for welding it up

  • @blainereed917
    @blainereed917 11 หลายเดือนก่อน +1

    What do you say when the facility staff comes in and acts like there's a problem with the flame if they see this process while your working?

  • @dandfgarage986
    @dandfgarage986 5 ปีที่แล้ว +1

    It looks like they JB welded that joint😂😂😂

  • @Spector_NS5_RD
    @Spector_NS5_RD 5 ปีที่แล้ว +12

    Will all that ice cream now have a burnt compressor oil flavor??? LOL Try our new toasted POE sundae swirl!!

    • @davidmiller9485
      @davidmiller9485 3 ปีที่แล้ว +1

      @@georgephillips6521 yes they will. The secret is that when it's originally made they flash freeze it to give it a "light" and "creamy" texture. (both myself and my Grandfather worked in dairy. Me with cows and my Grandfather at Bordens where he retired. )

  • @harrydickson4575
    @harrydickson4575 5 ปีที่แล้ว +1

    Excellent job 👍👍👍

  • @commanderosis435
    @commanderosis435 5 ปีที่แล้ว +7

    The back of that coil looked like it frosted up pretty quick. Was there a lot of moisture in there? I'm assuming that's why you fixed the door

  • @theackid7887
    @theackid7887 5 ปีที่แล้ว +1

    Thanks for the video Chris

  • @DW-bo3qw
    @DW-bo3qw 5 ปีที่แล้ว +1

    Also do you think the oil could have played some part in the funky icing pattern

  • @petethefridge
    @petethefridge 5 ปีที่แล้ว +10

    When I was working I would defrost an iced up evaporator with a domestic steam wallpaper stripper steam would condense on the ice so no mess and was quick.

    • @dand1486
      @dand1486 5 ปีที่แล้ว +1

      would u say its quicker than using plain old hot water from a garden hose? or some what the same? i want to try ur idea, sounds good

    • @44R0Ndin
      @44R0Ndin 4 ปีที่แล้ว +2

      @@dand1486
      For which one's faster, I looked at thermodynamics. It doesn't look good for the steam wallpaper stripper.
      To melt ice, you need energy, not temperature. A gallon of hot water carries less energy than that same gallon of water turned to steam at 212F, sure, but that steam will now take up 106.5 gallons of space. Steam is a lot less dense, meaning it takes longer to deliver it assuming the same flow rate as the hot water hose.
      So with those assumptions, the hot water hose carries higher thermal energy per second into the ice (energy per unit time is power, so we could simply say that the hose carries higher thermal power).
      Also, last time I checked a steam wallpaper stripper runs off a standard 15A 125V circuit, so you can only get a max of 1875W of heat into the steam, whereas the water heater the hot water hose is connected to might run off gas (lotsa power) or a 40A 240V circuit (9600W), so even if you "run out of hot water" you're still delivering AT LEAST 9600w of heat into that ice using the hot water hose.
      I don't really need to do the math to know that I'm right, simply because a pound of steam takes up so much more room than a pound of water.
      This means that the hot water hose is better in both respects, but feel free to use the steam wallpaper stripper if you have a restricted drain or are getting paid by the hour.

    • @dand1486
      @dand1486 4 ปีที่แล้ว

      @@44R0Ndin yep

    • @dand1486
      @dand1486 4 ปีที่แล้ว

      @@44R0Ndin man, maybe get a girl friend or some thing, u seem kinda angry or something, lol u just spent like 30min typing that lol...we all took the course, ok, ok, u win, lol. ....slow clap hahahaha

    • @dand1486
      @dand1486 4 ปีที่แล้ว

      also, have u ever poured water onto a ice up coil in a freezer were it sticks out futher than the drain pan? using a hose, it pours onto the floor. using buckets kinda work, but it will freeze to the floor and u have to use a small steam of water, but of course u know that? depending how bad it is of course

  • @articairrefrigeration9142
    @articairrefrigeration9142 5 ปีที่แล้ว +1

    Tight spot to workin good job

  • @mikhailkurylenak1515
    @mikhailkurylenak1515 5 ปีที่แล้ว +4

    Installers should reduce the size of a vertical portion of a suction line to increase refrigerant velocity for proper oil return so it wont sit at the evap.

  • @shine-cg9uf
    @shine-cg9uf ปีที่แล้ว +1

    When brazing inside walkin box n some have sprinkler systems do u need to shut them off b4 brazing ?

  • @elplevonrooo395
    @elplevonrooo395 5 ปีที่แล้ว +25

    No P-trap on that suction line ?

    • @FlyEaglesFly19111
      @FlyEaglesFly19111 5 ปีที่แล้ว +3

      Or inverted trap on roof

    • @Greg-202
      @Greg-202 4 ปีที่แล้ว +2

      I thought the same thing!!

  • @xelaju8
    @xelaju8 5 ปีที่แล้ว +1

    Thanks for the good video.

  • @paulherring8208
    @paulherring8208 5 ปีที่แล้ว +1

    Chris love your brother 1 reefer technician to the next

  • @dieselchevette
    @dieselchevette 5 ปีที่แล้ว +2

    I love that flaming poe. Nothing makes a green guy have a brown moment like that.

    • @throttlebottle5906
      @throttlebottle5906 5 ปีที่แล้ว +1

      they learn to keep their face and body out of the line of fire real fast that way :)

  • @mattzurzola4664
    @mattzurzola4664 5 ปีที่แล้ว +1

    Awesome job

  • @shine-cg9uf
    @shine-cg9uf 5 ปีที่แล้ว +1

    great video n great feedback.

  • @HardKnocks101
    @HardKnocks101 5 ปีที่แล้ว +3

    Hey Chris, I’ve noticed and commented that some of the jobs you are on do not have pee traps at the evap coil. I’m betting your oil issue is what caused the txv failure. There should have been a trap on that system. Furthermore, since you were already removing the boogered section of suction line for the bulb - you should have installed a trap! You still wouldva needed a place for the bulb but heck since you were doing all that work anyhow, why not add the additional piping and do it right. Just curious...love your videos and watch them all.

    • @primetime758
      @primetime758 5 ปีที่แล้ว +2

      who says it doesn't? just because there is no P trap inside the freezer maybe it doesn't go directly up ... you only install a P trap on vertical rise 6ft and up for Larger pipes P trap heights change

  • @engineer1793
    @engineer1793 5 ปีที่แล้ว +1

    Nice work

  • @aivey7737
    @aivey7737 5 ปีที่แล้ว +1

    Hey just wanted to give a shoutout. Been watching your videos for around a year now and they have been a tremendous help. What nitrogen regulator do you use when your brazing??

  • @FlyEaglesFly19111
    @FlyEaglesFly19111 5 ปีที่แล้ว +3

    How about door gaskets? They looked like they were beat.

  • @shanebehm8251
    @shanebehm8251 5 ปีที่แล้ว +1

    There wasn't a p-trap. Just curious, why didn't you add one?

  • @Hvac_Cool_Jay
    @Hvac_Cool_Jay 5 ปีที่แล้ว

    Do you have a video on why you choose to use field piece instead of testo

  • @alvaroturrubiartes76
    @alvaroturrubiartes76 5 ปีที่แล้ว

    Why not use soft solder on the suction line? Lower melting point.

  • @rookierefrigeration4357
    @rookierefrigeration4357 5 ปีที่แล้ว +1

    Great job.

    • @AlexGarcia-vv4ux
      @AlexGarcia-vv4ux 5 ปีที่แล้ว +2

      Rookie Refrigeration hey man , miss your videos. hope to see new ones soon .

    • @rookierefrigeration4357
      @rookierefrigeration4357 5 ปีที่แล้ว +1

      GhostFace NoFace I’ll have one Tomorrow I think. Thanks for watching bro.

  • @georgeolmo7710
    @georgeolmo7710 5 ปีที่แล้ว +1

    Love the vids..keep em coming...
    Question..why dont you use csg combo...sight glass and drier already assembled?

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว +1

      because than when you have to change the drier again you need another csg, more or less a personal preference.

  • @Marctheshark22
    @Marctheshark22 5 ปีที่แล้ว +1

    hands of steel man

  • @cod_leon_yt7415
    @cod_leon_yt7415 5 ปีที่แล้ว +4

    That’s my mentor

  • @ΗλιαςΜπελος-σ1ψ
    @ΗλιαςΜπελος-σ1ψ 5 ปีที่แล้ว

    Hey Chris nice job,and i have two questions why don't you install an oil trap and the second is that the pressure sense of txv is connected after temp sensor of txv not before. Any way keep on man!

  • @Crabawizky
    @Crabawizky 4 ปีที่แล้ว

    Can you refer somewhere to buy a complete cooling unit for walk in freezer that has been stripped of all parts\

  • @superiorcomfortheatingairl3373
    @superiorcomfortheatingairl3373 5 ปีที่แล้ว +1

    Just curious on those flare adapters that you brazed on, are those actually good flares from the manufacturer? I never trust manufacturer flares on line sets for ductless units, you can always count at least one bad flare.

  • @kylelickfelt2804
    @kylelickfelt2804 2 ปีที่แล้ว

    Y didnt u put a suction trap at the evap

  • @anthonyfish3772
    @anthonyfish3772 5 ปีที่แล้ว +1

    Have you every used a turbo torch? I prefer them as you only need an acetylene tank. I find it works well for Residential HVAC.

    • @jimbeam7248
      @jimbeam7248 5 ปีที่แล้ว +1

      Not enough heat I find, can’t get a proper braze

  • @throttlebottle5906
    @throttlebottle5906 5 ปีที่แล้ว +1

    I'm starting to wonder if a small "steam machine" would be a great setup for coil deicing.
    lol, as I was typing this I seen someone else commented the same thing earlier and sounds like they've tried it

  • @russell4309
    @russell4309 5 ปีที่แล้ว +4

    How come it didn't have a suction ptrap in the box?

    • @primetime758
      @primetime758 5 ปีที่แล้ว +1

      who says it doesn't? just because there is no P trap inside the freezer maybe it doesn't go directly up ... you only install a P trap on vertical rise 6ft and up for Larger pipes P trap heights change

  • @alicepet1994
    @alicepet1994 5 ปีที่แล้ว +1

    No nitrogen purge?

  • @ritchieortiz5610
    @ritchieortiz5610 5 ปีที่แล้ว +1

    What kind of wand is that for your hose?

  • @marriagepartnersministry5942
    @marriagepartnersministry5942 5 ปีที่แล้ว +1

    Where can I get one of those solenoid magnets?

  • @DW-bo3qw
    @DW-bo3qw 5 ปีที่แล้ว +1

    Do you ever worry about oil logging of the evap without having a trap on there?

    • @cranium33333
      @cranium33333 5 ปีที่แล้ว

      D W Oil trap usually on to of box. At least that’s how I’ve always done it. That way keep as little piping down below as possible.

  • @tdgreenbay
    @tdgreenbay 5 ปีที่แล้ว +1

    That joint looked fugly... what grade silver solder you use there...

  • @adrianquezada5416
    @adrianquezada5416 5 ปีที่แล้ว +1

    What are good HVAC apps for finding superheat/subcool psig etc

  • @jaymesrod4209
    @jaymesrod4209 5 ปีที่แล้ว +2

    Chris. You ever seen a walk in freezer where the time clock is mounted in the walk in. I recently went to a new call where this is the case. My question to you is, is this acceptable. I've never seen one like this.

  • @lovintrump5755
    @lovintrump5755 2 ปีที่แล้ว

    why dont you use nitrogen while you unsweat the joints ?

  • @anthillmobstars
    @anthillmobstars 5 ปีที่แล้ว +1

    Long videos! Oh yeah. Nice and Good!

  • @zekenzy6486
    @zekenzy6486 5 ปีที่แล้ว +1

    you use hot water or cold water for defrost those ice in freezer ?

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว +1

      Preferably hot water but cold water works fine too

  • @Georges3DPrinters
    @Georges3DPrinters 3 ปีที่แล้ว

    5:48 XD lol. They where short on copper and used scraps lol.

  • @krz8888888
    @krz8888888 3 ปีที่แล้ว +1

    Hahaha what a junkyard wars grade connection

    • @krz8888888
      @krz8888888 3 ปีที่แล้ว +1

      Not yours I mean the multiple braises

  • @ninamcclure2193
    @ninamcclure2193 3 ปีที่แล้ว +1

    Hello and love learning the trade from you. I am coming from the automotive side and wanted to share a tool that you may already know about. It is a ratcheting tube cutter. Used it a lot on brake lines with no room. Check it out if you haven't yet. Thanks for the high quality vids.

  • @goginenirajashekar5618
    @goginenirajashekar5618 4 ปีที่แล้ว +1

    Good

  • @stephenconnell
    @stephenconnell 5 ปีที่แล้ว +1

    How much stock was lost? Seeing the Ice Cream was melting

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว

      They didnt throw anything away........

    • @stephenconnell
      @stephenconnell 5 ปีที่แล้ว +1

      Thats an outstanding result considering what the job threw at you and how long it took to get it all running well again. Your tech skills are great and your work ethic is of the highest quality.

    • @captainkirk7702
      @captainkirk7702 5 ปีที่แล้ว +1

      It’s been running like that for a good while, see it all the time. A lot of the customers I see keep theirs also when they have an issue with the w/I freezer.

  • @417HVAC
    @417HVAC 5 ปีที่แล้ว +1

    I’m sorry if you’ve answered this already. But what size is that rosebud tip?

    • @cranium33333
      @cranium33333 5 ปีที่แล้ว

      Shawn Price For oxy torches there’s really only 2 sizes small and large. Small for 1/4 to to 7/8’s large for 1” and up.

    • @417HVAC
      @417HVAC 5 ปีที่แล้ว

      There are plenty of sizes. I believe they range from 4-10. They also make dual tips. Used to braze 3/16” to 8” copper.

  • @SCOTTYD2031
    @SCOTTYD2031 3 ปีที่แล้ว

    Stainless steel - yup!

  • @nathanhill4680
    @nathanhill4680 5 ปีที่แล้ว +1

    You know its a tight space when you are sweating in a freezer lol

  • @shadowsiren3058
    @shadowsiren3058 5 ปีที่แล้ว +1

    That’s sad they lost it all

  • @throttlebottle5906
    @throttlebottle5906 5 ปีที่แล้ว +1

    5:49 looks like line set was reused multiple times on evap changes and turned into a cobbled up mess, yeehaw

  • @shadowsiren3058
    @shadowsiren3058 5 ปีที่แล้ว +1

    Did they had a backup freezer

  • @Tjita1
    @Tjita1 5 ปีที่แล้ว +1

    Ha! "It's hot!"
    Now, how could that possibly be? :'D

  • @salahudeenshaikh7566
    @salahudeenshaikh7566 5 ปีที่แล้ว +1

    Lol....pain in butt ..is this also include in demo. ..

  • @ConservTab-sv3kx
    @ConservTab-sv3kx 5 ปีที่แล้ว +1

    Tough day

  • @jo6520
    @jo6520 5 ปีที่แล้ว +2

    And you cleaned the evaporator coil
    while defrosting

    • @FlyEaglesFly19111
      @FlyEaglesFly19111 5 ปีที่แล้ว +2

      Frozen boxes usually never have issues. Its usually med temp boxes to get filthy

    • @jo6520
      @jo6520 5 ปีที่แล้ว

      @@FlyEaglesFly19111 it never hearts to clean anything!

  • @TheCrystalGlow
    @TheCrystalGlow 5 ปีที่แล้ว +1

    Does that solder you use already have flux? I’ve never seen you use any flux paste before when soldering. Just wondering. :)

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว +5

      No flux needed because it is 15% silfos on copper to copper just clean the metals and apply heat. If I am working on dissimilar metals than I will use 56% silver solder with a silver paste flux

    • @dieselchevette
      @dieselchevette 5 ปีที่แล้ว

      Ever try using 6? I find it flows much easier without needing as much heat.

    • @TheCrystalGlow
      @TheCrystalGlow 5 ปีที่แล้ว

      I am personally in electronics technician so most of the time flux is needed so we don’t burn the board since it aids in more efficient heat transfer without needing as much heat. I wasn’t aware that that was actually possible for soldering pipe. But then again I’m not an HVACR technician yet. If all else fails I’ll probably be looking into getting into the field. I do know a bit about it and more so thanks to your videos. so who knows?

  • @southwestmechanicalinc1550
    @southwestmechanicalinc1550 5 ปีที่แล้ว +1

    👍👍

  • @petethefridge
    @petethefridge 5 ปีที่แล้ว +2

    Should say steamer with a nozzle rather than the plate thingy.

  • @michaeldomansky8497
    @michaeldomansky8497 5 ปีที่แล้ว +1

    The Dark Side Of The Frost .....

  • @SeanLeonDrumz
    @SeanLeonDrumz 5 ปีที่แล้ว +1

    reupload? or deja vu?

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว +1

      I work on a ton of the same stuff so probably dejavu....

  • @dynorat12
    @dynorat12 4 ปีที่แล้ว +1

    FIRE !!!! lol smoking

  • @gas_man1565
    @gas_man1565 5 ปีที่แล้ว +1

    not sure if you actually paying attention the coil was still freezing the same way 30:22 txv didn't fix the problem

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว +1

      At 30:22 I said it looks good and had an even frost pattern vs when i got there it was only frosting up on the top. The coil was not frosting the same way, these walk in freezers are expected to frost up like it did at the end of the video especially under the load it was trying to cool down

  • @alexferia3323
    @alexferia3323 2 ปีที่แล้ว

    Torque setting = Does not leak

  • @timothystevenson7907
    @timothystevenson7907 5 ปีที่แล้ว +1

    For the amount of promo you do for big blue you would think they would sponsor you at some point.

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว +4

      Ha ha what can I say I genuinely like their products. I can sleep easy knowing I'm not endorsing a product simply because I'm getting paid.....

  •  7 หลายเดือนก่อน

    All that oil is from no oil return trap problem.😵

  • @IFIXCASTLES
    @IFIXCASTLES 5 ปีที่แล้ว +1

    Had a similar icing up on 404a freezer. I added defrosts problem solved.

    • @FlyEaglesFly19111
      @FlyEaglesFly19111 5 ปีที่แล้ว

      How many defrosts?? No more than 2 a day @45min