How to Size a Control Valve for Liquid Flow

แชร์
ฝัง
  • เผยแพร่เมื่อ 5 ต.ค. 2024

ความคิดเห็น • 13

  • @banyatniyomvas
    @banyatniyomvas 3 หลายเดือนก่อน

    Thank you

  • @garymceuen5069
    @garymceuen5069 11 หลายเดือนก่อน

    At approximately 1:44 of the video, the K1 equation is used. d (nominal pipe size) and D (internal diameter of pipe) are used. d is shown as 3 (the nominal pipe size), but D is shown as 7.98. Shouldn't D be 3.068 inches? Please explain.

  • @satyarahul8007
    @satyarahul8007 11 หลายเดือนก่อน

    to calculate the necessary resistance coefficients needed when the upstream and downstream pipe sizes are the same: At 1.44 during these the PIPE line size is 8 inches but D1 is taken as 7.98? can you please explain Y?

  • @PsyrenZero
    @PsyrenZero 2 ปีที่แล้ว

    Is the flow STP or actual conditions for reference?

  • @sutanalif5392
    @sutanalif5392 3 ปีที่แล้ว +2

    from whre can i get data that showing "100%cv=121"

    • @balajiarni
      @balajiarni 7 หลายเดือนก่อน

      Even I have same question?

  • @devinaismaya4831
    @devinaismaya4831 4 ปีที่แล้ว +1

    how do you know the percent valve open for new Cv is about 75%?

    • @FisherControlValve
      @FisherControlValve  4 ปีที่แล้ว +1

      We compare the calculated Cv to the valve manufacturer sizing table for an NPS 4 globe valve with =% trim. The table gives us the Flow Coefficients at the valve opening - percent of total travel.
      The Fisher valve sizing tables for a NPS 4 with equal percentage trim can be found here: www.emerson.com/documents/automation/catalog-12-en-1630608.pdf#page=119
      For the purposes of this example some of the numbers were generalized.

    • @danielbest98
      @danielbest98 3 ปีที่แล้ว

      @@FisherControlValve I have a few questions. I am new to this so bare with me if you don't mind. Why is this 75% significant? And how exactly do I find this 75% using a Cv value of 116.2 I thought it would be under 70% on the table? It's possible I'm reading the table wrong it is page 119 correct?

    • @danielbest98
      @danielbest98 3 ปีที่แล้ว

      Also I understand that generally when sizing a valve I need it to be within a (20 - 80)% open. How does this information or does this information indicate that?

    • @vaishnavacharya9572
      @vaishnavacharya9572 ปีที่แล้ว

      Hello, I really didn't understand that from where the value of D i.e 7.98 is derived?

  • @prabhumuthusubramanian8843
    @prabhumuthusubramanian8843 2 ปีที่แล้ว

    How to size control valve for supercritical fluid

  • @43SunSon
    @43SunSon ปีที่แล้ว +1

    pikapika