How do you correctly size a surge protective device (SPD) for your power system?

แชร์
ฝัง
  • เผยแพร่เมื่อ 15 ต.ค. 2024

ความคิดเห็น • 47

  • @lg3053
    @lg3053 2 หลายเดือนก่อน +1

    This is by far the absolute best video explaining these devices. However, what would have made it even better would have been to show how to connect the actual devices, and explaining that these are a onetime use for a large spike and they can't be reset.

    • @phocos-global
      @phocos-global  หลายเดือนก่อน

      @@lg3053 thank you for the feedback

  • @MrJohnTherat
    @MrJohnTherat 2 ปีที่แล้ว +2

    This is an amazing description of how to select and utilise an SPD, very informative and very helpful. Just to add, that I did not know that SPD's are none resettable once tripped.
    Thumbs Up.

    • @daniellawrence9065
      @daniellawrence9065 2 ปีที่แล้ว +1

      Except for the Current Technology product line. The selenium modules are not fully sacrificial and can take many hits without failure.

  • @mahlogonolomashilamokaba2675
    @mahlogonolomashilamokaba2675 11 หลายเดือนก่อน +1

    It is great information you give us, as you said we must make sure that our SPD a rated at specific value e.g if your PV is 95v is best to install SPD of 100v, what i will like to know is it recommended AC also to have 5v different or it can be more

    • @phocos-global
      @phocos-global  11 หลายเดือนก่อน

      According to our tech team, Acceptable SPDs for PV are the Citel DS240-350DC / Phoenix Contact VAL-SEC-T2-2+0-380DC-FM for the 230V models, and the Citel DS240-220DC / Phoenix Contact VAL-SEC-T2-2+0-220DC for the 120V models.
      For AC input, acceptable example SPDs are Citel DS41S-230 / Phoenix Contact VAL-MS 230 for the 230V models, and the Citel DS41S-120 or Phoenix Contact VAL-SEC-T2-1S-175-FM

  • @michaelchane2593
    @michaelchane2593 หลายเดือนก่อน +1

    i really appreciate your explaination which i have been looking for a long time...I do have an inverter with 450 vdc input and i notice even with the spd, the dc input alway get burn, now I understand that i have been using over rated spd of 500v and above

    • @phocos-global
      @phocos-global  หลายเดือนก่อน

      @@michaelchane2593 thank you for saying so!

    • @michaelchane2593
      @michaelchane2593 หลายเดือนก่อน

      @@phocos-global i have been unable to see spd of 450vdc.....what should i do

  • @BlueSky-cy5nw
    @BlueSky-cy5nw 4 หลายเดือนก่อน

    I have 12 panels connected in series, the total open circuit voltage of the panels is 578v DC. Would a 600V DC SPD be sufficient to protect my setup? Also what about the wire gauge of the ground wire, I am using 9AWG ground wire.

  • @jamrockrobby5219
    @jamrockrobby5219 3 ปีที่แล้ว

    Great info. I currently have solar array with Voc of 320. Could you recommend a spd device

    • @phocos-global
      @phocos-global  2 ปีที่แล้ว +1

      Hello, we apologize for the late reply. Assuming you are using a PSW-H-3KW-230/24V or PSW-H-5KW-230/48V, the manual recommends the Citel DS240-350DC or Phoenix Contact VALSEC-T2-2+0-380DC-FM. However, this is assuming the full 450 Voc is being used for PV. As this is not the case for you, choosing an SPD with a Uc rating (max. operating voltage) of you actual PV array Voc (consider coldest temperatures in winter) will actually provide better protection (the SPD will start to act at a lower surge voltage). With a Uc of 350 Vdc, the Citel DS240-280DC would be best suited for your PV array. Always use DC-rated SPDs for solar arrays. See our video th-cam.com/video/joFCSb8OLFw/w-d-xo.html for more details.

    • @jamrockrobby5219
      @jamrockrobby5219 2 ปีที่แล้ว

      @@phocos-global thank you

  • @johnnyambi550
    @johnnyambi550 2 หลายเดือนก่อน +1

    How to calculate soze of ac spd for type2

  • @samueladedeji301
    @samueladedeji301 3 ปีที่แล้ว +1

    Thank you, Alessio for the video

  • @XchakGearz
    @XchakGearz ปีที่แล้ว +2

    figuring out the right SPD for a sys is a challenge I think I'm still trying to figure it out 🤔😯

  • @sambathbunkh
    @sambathbunkh ปีที่แล้ว +1

    Very good explanation ❤

  • @paulomock3741
    @paulomock3741 8 หลายเดือนก่อน +1

    How many strings can I connect with one SPD.
    For instance, can I install three strings of 95V into one SPD of 500Uc

    • @phocos-global
      @phocos-global  8 หลายเดือนก่อน

      Thank you for reaching out, There should be at least one SPD per MPPT input to the Inverter. The PSD is to protect the PV input, according to our tech team.

  • @sabilza
    @sabilza 2 ปีที่แล้ว +1

    Great explanation but I'm still confused. Isn't it better to pick SPD that has highest capacity? Because 500 or 1000v won't make any difference if most of lightning has 30-100 million volts

    • @phocos-global
      @phocos-global  2 ปีที่แล้ว +1

      Hello, the end goal is to protect your Any-Grid inverter from voltage spikes. The SPD needs to be rated so that it protects the hardware limitations of the inverter but also allow it to perform. SPDs are specifically designed for this purpose in mind. We only need to make sure we pair them to equipment correctly.

    • @mahlogonolomashilamokaba2675
      @mahlogonolomashilamokaba2675 11 หลายเดือนก่อน

      For how much input of PV because the very with system because must people upgrade they PV by adding panels

  • @I_ammm_mojojojo
    @I_ammm_mojojojo ปีที่แล้ว

    I have a 220v/125amp 60HZ main breaker panel (GE Homeline) in my Condo.
    How do I size a "whole house" breaker type suppressor for this application?

    • @phocos-global
      @phocos-global  ปีที่แล้ว

      Hello, thank you for your question. We are eager to offer support. Please reach out directly to our technical department here: www.phocos.com/contact/#contactech

  • @alanblyde8502
    @alanblyde8502 ปีที่แล้ว +1

    Very well explained 👌🇦🇺

  • @fahadmukhtar1124
    @fahadmukhtar1124 ปีที่แล้ว +1

    Excellent !!!

  • @flinfaraday1821
    @flinfaraday1821 ปีที่แล้ว +1

    I get so much conflicting information with regard to "uc" and "up" values. Would be great if you could shed a light. Even OpenAI's chatgpt is giving me information that seem opposite to this.

    • @phocos-global
      @phocos-global  ปีที่แล้ว +3

      Hello, thank you for engaging with us! According to our engineering team..
      Uc refers to the maximum continuous working voltage of the SPD when not active. Above this voltage, the SPD will begin to conduct energy towards ground. This voltage needs to be sized to the equipment, and should match the maximum working voltage of the system that it is meant to protect. This is the most important value when sizing an SPD.
      Up is the voltage protection level of the SPD. This is the maximum voltage across the SPD when it is actively dissipating energy to ground.
      The range between Uc and Up is the range of operating voltages of the SPD when it is active and dissipating energy to ground. The voltage may be lower than Uc - but the device will not become active until the voltage has surpassed Uc.
      Hopes this helps!

    • @flinfaraday1821
      @flinfaraday1821 ปีที่แล้ว

      @@phocos-global Thank you!

    • @yellownev
      @yellownev ปีที่แล้ว

      So for my learning in a series of say 5 panels rated at 50 voc the spd would need to be rated at 250v dc just over …. Is there a multiplayer for the safety cap between the string voltage and the SPD limit ? Thanks for the very concise video

  • @rongainigelchikanya112
    @rongainigelchikanya112 3 ปีที่แล้ว +1

    Powerful thank you sir

  • @dewshangayanka4855
    @dewshangayanka4855 4 หลายเดือนก่อน +1

    Thanks

  • @matoscu
    @matoscu ปีที่แล้ว

    I thought the excess power was supose to go to neutral. Which is correct

    • @oldgringo66
      @oldgringo66 ปีที่แล้ว

      The over voltage goes to ground. In panels where the common and ground are connected it is the same.

  • @meghrajbasnet55
    @meghrajbasnet55 ปีที่แล้ว

    Can we use same earthing for spd and other system?

    • @phocos-global
      @phocos-global  ปีที่แล้ว

      Hello, we apologize for the late reply. For assistance, please reach out to our technical team by filling out a short form here: www.phocos.com/contact/#contactech

  • @myanmarcloud2858
    @myanmarcloud2858 2 ปีที่แล้ว

    Can use 500 v spd ( UC 500 V) for PSW-H-5KW-230/48V?

    • @phocos-global
      @phocos-global  2 ปีที่แล้ว

      Hello, the PSW-H 5kW 230/48V can accept a maximum PV input of 450Vdc which means that with an SPD rated at 500Vdc would not offer adequate protection. An SPD rated at 500Vdc would only begin to act after the maximum PV input voltage of the PSW-H has been exceeded, at which point the MPPT component of the PSW-H may already have been damaged. To ensure adequate protection, the SPD device should be rated to 450Vdc (Uc 450V), examples of suitable devices would be Citel DS240-350DC or Phoenix Contact VAL-SEC-T2-2+0-380DC-FM.
      Further information regarding AC surge protection devices can be found on pg 3 of the PSW-H manual, which can be downloaded from our website here: www.phocos.com/wp-content/uploads/2019/10/Any-Grid_PSW-H_EN-manual_2022-02-21.pdf

  • @roderickgorby1234567
    @roderickgorby1234567 3 ปีที่แล้ว

    I’ve seen it said that you can just plug your panels in series into the built in mc4 connectors on the psw-h 48v 5kw unit. Are you saying you would still need an spd on the panels? SPD… isn’t that a German political party?

    • @phocos-global
      @phocos-global  3 ปีที่แล้ว

      Hello, the surge protective device (SPD) is strongly recommended regardless of the PV setup. By their nature, solar panel arrays are installed outside and are therefore liable to pick up voltage surges during thunderstorms, which the SPD is designed to mitigate to some extent, protecting the equipment connected to it, the PSW-H in this case.

    • @fahadmukhtar1124
      @fahadmukhtar1124 ปีที่แล้ว

      @@phocos-global I want to add something which is very important, always Install a device(breaker) in series with SPD because sometimes SPD becomes shot-circuited after getting faulty & can damage other equipment as well .

  • @BlazeByte21
    @BlazeByte21 3 ปีที่แล้ว

    Is it okay to connect SPD ground wire to ground rod of solar panel? Thanks

    • @phocos-global
      @phocos-global  3 ปีที่แล้ว

      Hello, this may or may not be permitted, depending on your local electrical code. But if the PV grounding rod is correctly installed and has an adequately low resistance to ground, then there is nothing fundamentally wrong with this approach.

  • @SandiSchantz-m8c
    @SandiSchantz-m8c 11 หลายเดือนก่อน +1

    dont understand and am more confused

    • @phocos-global
      @phocos-global  11 หลายเดือนก่อน

      Please if you have any questions reach out to our technical team for clarity. www.phocos.com/contact/#contactech2