A vlog on desooting boilers would be great. Do you use any of the products on the market or just time and brushes. Also how long does it take to burn of the excess in your experience? (before you get a decent smoke number)
Hi. sorry for the delayed reply. We have a de sooting of a boiler video. Just hoover, scrapers and brushes. I normally do a smoke test to check and go back next day to stick kit in. But i would wait a good half hour plus if you did it on the same day but smoke gun first. The better you clean it the faster it burns off. Have a good week. Rob
Hi Rob wondering if you could shed some light on an issue I’m having with a warmflow boiler with an rdb burner. The length of pipe run from the tank is about approx 25- 30 metres and tank sits about 2 metre drop behind a wall. Boiler runs great for about 20 - 30 mins then it loses oil pressure, cuts out and goes to lock out. I changed the nozzle, cleaned the oil pump filter as they’d ran out of oil and cleaned the filter at the tank thinking this would cure it but no. I blew down the pipe line with my compressor and changed tiger loop and now it’s still dropping and fluctuating oil pressure and cutting out and re igniting. The tiger loop bubbles and froths when she’s dropping the oil pressure. She’s going but not going right. Just asking is there anything else I could try. Would a burner with a danfoss oil pump be better than a Riello. Sorry about the long message but I don’t know anyone else to turn to. All the best.
Hi. If the tiger loop froths then air all day long. Check all joints and flex oil lines. If all ok i would change the pump first to be honest. Hope this helps , ps you dont need to put a diff burner on.
Thankyou so so much for your help you’ve no idea how appreciative I am of you getting back to me so promptly. That makes so much sense, you’re such a top bloke.
Hi rob. It has to be said you’re a very good engineer. Anyone working along side you would learn a lot I’m sure. Interesting vlog 👍🏻
Glad you liked it and thanks for the lovely comment mate. Have a good week!
So do you do everything one handed now 😁
Sorry for delay Stuart. Just imagine if we could work one handed all the time, With 2 hands think of all the work you could do! HAve a good week.
A vlog on desooting boilers would be great. Do you use any of the products on the market or just time and brushes. Also how long does it take to burn of the excess in your experience? (before you get a decent smoke number)
Hi. sorry for the delayed reply. We have a de sooting of a boiler video. Just hoover, scrapers and brushes. I normally do a smoke test to check and go back next day to stick kit in. But i would wait a good half hour plus if you did it on the same day but smoke gun first. The better you clean it the faster it burns off. Have a good week. Rob
Great video again rob . Can you tell me where is the best place to get rellio burner motor bearings from
Hi Mate. Abgo Spares. They are great. Have a great week and sorry for the delay! Rob
Would you know correct pressure and nozzle to convert riello40 G20 to run hvo ??
HI. It would bepend on the output of the boiler. most manufactuers should be able to tell you. But i would not know yet unless i rang them. Rob
We wanted to see it working 😭😭😭
Sorry i wanted to show it running but just out of time! I will do one with a bit of flame soon!
Hi Rob wondering if you could shed some light on an issue I’m having with a warmflow boiler with an rdb burner. The length of pipe run from the tank is about approx 25- 30 metres and tank sits about 2 metre drop behind a wall. Boiler runs great for about 20 - 30 mins then it loses oil pressure, cuts out and goes to lock out. I changed the nozzle, cleaned the oil pump filter as they’d ran out of oil and cleaned the filter at the tank thinking this would cure it but no. I blew down the pipe line with my compressor and changed tiger loop and now it’s still dropping and fluctuating oil pressure and cutting out and re igniting. The tiger loop bubbles and froths when she’s dropping the oil pressure. She’s going but not going right. Just asking is there anything else I could try. Would a burner with a danfoss oil pump be better than a Riello. Sorry about the long message but I don’t know anyone else to turn to. All the best.
Hi. If the tiger loop froths then air all day long. Check all joints and flex oil lines. If all ok i would change the pump first to be honest. Hope this helps , ps you dont need to put a diff burner on.
Thankyou so so much for your help you’ve no idea how appreciative I am of you getting back to me so promptly. That makes so much sense, you’re such a top bloke.
Looked like NGK bearings to me.
Correct !! 10 out of 10 for that. Have a good week mate!