Hello dear thanks for asking.... If you notice that current level reduces as voltage goes high... For LT side to calculate MCB SC capacity current we need that.
Bhai , Mai Solar plant me hu , or mera plant double circuit pe run krta hai , pr kuch time pehle SS ki ek CT burst ho gyi thi , Av CT change krne k bad line parallel charge krne k bad Current 2 phase me zero hojarha pr Single circuit me brabar Chal rha hai.
Dear sir, as referred to msg...As per prima facia plz check below 1. Check P1 & P2 of CT - whether properly aligned. 2. CT - S2 connections specially neutral looping. 3. Whether current is ok at bus bar or not. Check before CT.
@@electricaldesigningbasics all things checked & found ok. 1) both line work when plant charge on single circuit. 2) when both Circuits charged pallarly R phase current of one line completly transfer to R phase of other line. 3) checked all the Jumphers but all things are ok.
wao amazing videos for designing students...keep going sir...eagerly waiting for more such informating videos for giving clear understanding of the topics..
Very informative sir❤
❤
thanks
33 kv system is also connected to 132 kv system, is system fault level needed or not for 11 kv/415 v volt side fault level calculation?
Hello dear thanks for asking.... If you notice that current level reduces as voltage goes high... For LT side to calculate MCB SC capacity current we need that.
आप बात कर रहे है actual system fault level ki ,ये कैसे सम्भव है
I am talking about maximum system fault current.
Bhai , Mai Solar plant me hu , or mera plant double circuit pe run krta hai , pr kuch time pehle SS ki ek CT burst ho gyi thi , Av CT change krne k bad line parallel charge krne k bad Current 2 phase me zero hojarha pr Single circuit me brabar Chal rha hai.
Dear sir, as referred to msg...As per prima facia plz check below
1. Check P1 & P2 of CT - whether properly aligned.
2. CT - S2 connections specially neutral looping.
3. Whether current is ok at bus bar or not. Check before CT.
@@electricaldesigningbasics all things checked & found ok.
1) both line work when plant charge on single circuit.
2) when both Circuits charged pallarly R phase current of one line completly transfer to R phase of other line.
3) checked all the Jumphers but all things are ok.
@@RohitKumar-bp4cc plz provide sizes of both cable.
@@electricaldesigningbasics painther & dog
@@electricaldesigningbasics from bus to gantry painther & then dog . in boyh the lines
❤
आप बात कर रहे है actual system fault level ki ,ये कैसे सम्भव है