    sathiyo es machine me Circuit 1 ka compressor Grounding ho gya tha jis se pure building ki power trip kar rahi thi.jab Grounding ka issu ho to wah part change hi karna padta hai. es liye mai machine ka #briston compressor change kiya jo 124 LRA ,220V ,3PH ,R-22 ka tha.ya pura Machine 118000 BTU/h ka hai jisme 124 LRA ka 2 Compressor laga hai.
    jab ham comressor change karte hain to liquid line me laga Drier bhi change kerte hain kyo ki naya lagane se gas ka flow 100 % clear hota hai aur koi blocking ki samsya bhi nahi hoti .
    yah dono change jerne ke bad achhe se vaccume karke Gas dala jo labghag 3.86 kg leta hai .
    last me 55 psi LP aur 280-290 psi aur 15 amp per machine ko hold kar kam khatm kar diya.
    pura video dekhne ke liye ap sabhi ka thanks

ความคิดเห็น • 20

  • @shabbirahmed5166
    @shabbirahmed5166 8 หลายเดือนก่อน

    ustad good work

  • @projaprotiahmed402
    @projaprotiahmed402 ปีที่แล้ว +1

    Good job bro..

  • @saurabhchauhan8055
    @saurabhchauhan8055 ปีที่แล้ว +1

    Sir ap Ney evaporator ko flush nhi kiya....??
    Sir mai ap sey puch sakta hoo ke filter ...key dushri side jo ke evaporator ko jatee hi...to hum same process ek nrv .or excess valve laga ker agar flush kertey hi to evaporator nichey kisi room mey laga ho ga to kya evaporator ka oil ...uper aa jaiye ga....

    • @teacheverythings3895
      @teacheverythings3895  ปีที่แล้ว

      Han same process hota hai pipe line aur evaporator ko flush kerne ka .
      Hamare pass enough N2 nahi tha jisse flush nahi kiya .
      Dusri bat ki kya Flushing ke bad oil uper ajat hai to ye bat sahi hai ki oil uper ajata hai jab N2+ R11 use kerke pressure ko 200 ya 300 psi per release kerte hain to.
      Lekin LG pe ak thodi prblm hai ki indoor FCU unit me evaporator ke inlet line me jo device lagi hoti hai wo 7 pacailay ya 9 ya 14 capillary hoti hai jise jyada pressur dene se unke ander laga metal filter fatne ka chance hota hai es liye koi bhi Flushing ka kam karne se pahle mai yah dekh leta hun.
      Thanks for asking asking questions Sir🙏

    • @saurabhchauhan8055
      @saurabhchauhan8055 ปีที่แล้ว +1

      @@teacheverythings3895 thnx for replay sir...
      Sir kya ap humey koi number dey saktey hi jis sey Mai koi problem ho to ap sey puch saku ... video ap ka dekhta hoo...

    • @teacheverythings3895
      @teacheverythings3895  ปีที่แล้ว

      +918528517115 whtsap number

  • @khanshadab7864
    @khanshadab7864 8 หลายเดือนก่อน +1

    Bhai aap Kahan job kar rahao ho

  • @khanshadab7864
    @khanshadab7864 8 หลายเดือนก่อน +1

    Aap na in door ke to feleshing ke nahi

  • @ostingpanansaran9997
    @ostingpanansaran9997 ปีที่แล้ว +1

    did you remove the txv while flushing sir or not?

    • @teacheverythings3895
      @teacheverythings3895  ปีที่แล้ว +1

      I did not flush pipe line and indoor.
      Actually in this machine have 7 capillary set type Expansion on evaporator

    • @ostingpanansaran9997
      @ostingpanansaran9997 ปีที่แล้ว

      @@teacheverythings3895 ah ok sir...i guess it has a txv...thanks sir.. good job

  • @AmitAmit-yy5md
    @AmitAmit-yy5md 9 หลายเดือนก่อน +1

    Aapke compni me aana hai

    • @teacheverythings3895
      @teacheverythings3895  9 หลายเดือนก่อน

      Jarur lekin ajkal adhikter gulf company technician gulf ke hi dusre compny se hi le rahi hain.mai khud pahle binladen company me tha pahle

  • @AmitAmit-yy5md
    @AmitAmit-yy5md 9 หลายเดือนก่อน +1

    Aap kha par ho sir

    • @teacheverythings3895
      @teacheverythings3895  9 หลายเดือนก่อน

      Filhal mai ghar aya hu.india me

    • @AmitAmit-yy5md
      @AmitAmit-yy5md 9 หลายเดือนก่อน

      Sir aapka ghar kha hai aapse milna hai

  • @CristianoRonaldo-q6j2k
    @CristianoRonaldo-q6j2k ปีที่แล้ว +1

    Mujhe Kam sikhna hai apna contact number do