Frozen Air Conditioner Multiple Issues

แชร์
ฝัง
  • เผยแพร่เมื่อ 28 ส.ค. 2024
  • I am on a no air-conditioning service call. As I arrive and look at the unit I find the air handler evaporator coil is all iced up. I shut the unit off and go outside and check the AC Condensing Unit. Ice is outside on suction line until it reaches the compressor. Therefore, I pull the disconnect and test contactor, verifying it didn’t get stuck. Next I go inside and find a zoning panel. Then I find a zone damper that a wire fell off. I fixed the loose wire on the HVAC systems zone damper. I return the next day to find refrigerant charge low. I leak search the unit and locate leak on condenser coil. I recharge the system for temporary cooling. Then sell them a née condensing unit.

ความคิดเห็น • 98

  • @mhvacr_
    @mhvacr_ 3 ปีที่แล้ว +4

    Always good to hear you fixed a problem that has been existing for years. Great job

    • @thehvachacker
      @thehvachacker  3 ปีที่แล้ว

      It’s why customers should tell a tech there for maintenance that a problem is present. If not most won’t do much than clean and test air handler.

    • @mhvacr_
      @mhvacr_ 3 ปีที่แล้ว

      @@thehvachacker absolutely, it has the potential to open the door for additional corrections and extra earning potential

  • @leosthrivwithautism
    @leosthrivwithautism 3 ปีที่แล้ว +28

    Hacker is on the same league of champions in the hvac field as other channels on here. How come this man does not have half the amount of subs that them other guys have? Hacker always makes quality videos!

    • @thehvachacker
      @thehvachacker  3 ปีที่แล้ว +14

      Thanks, I think it could be the name. I don’t think I am listed or considered an hvac channel. Oh well I just put my vids out for those who enjoy.

    • @rendel2358
      @rendel2358 3 ปีที่แล้ว +1

      Ya I watch Hacker and the other guy. I think other guys advertise on TruTech, other websites, and seek out sponsorship. Hacker says he won't promote any ads on his show. Plus its a lot of hours spending time editing videos. I like Hacker he does Residential and Commercial.

    • @WeatherNut27
      @WeatherNut27 3 ปีที่แล้ว

      He will get up there eventually if he's honest, not obnoxious and uses a tripod. Speaking of honest... did you see the latest? Crazy shit out there! th-cam.com/video/hxnfRiq23Zg/w-d-xo.html

    • @davidlopan6649
      @davidlopan6649 3 ปีที่แล้ว

      @@thehvachacker I think its the name. Your vids are as good as the other guys on TH-cam. Keep em coming.

    • @WeatherNut27
      @WeatherNut27 3 ปีที่แล้ว

      @@homeserve9292 NJ and NY (southern NY).. nobody likes people with bad attitudes. Lol.

  • @sknight0391
    @sknight0391 3 ปีที่แล้ว +5

    Ahhh, the beloved micro channel leak! Dang I hate that stuff. I cannot believe that's the direction the whole industry is going in. Everybody's starting to use micro channel.
    And that was a beautiful frost ball on the line set. I had one that looked just like that last week. At first when I came around the back of the condos I thought someone had laid a piece of PVC pipe over it because it was so pretty and Snow White .

    • @proanswers
      @proanswers 3 ปีที่แล้ว +1

      Pros and cons with micro channel- but that office should be on a cleaning maintenance schedule. No excuse for that level of dirty condenser regardless of micro channel.

    • @sjefoekel6058
      @sjefoekel6058 3 ปีที่แล้ว +1

      +1 cant stand the microleakchannel!

    • @thehvachacker
      @thehvachacker  3 ปีที่แล้ว

      They are set up for a coil cleaning and ac maintenance next week. Due to COVID they didn’t have maintenance last year

  • @bill944
    @bill944 3 ปีที่แล้ว +5

    Good find. Life would be so much easier if install crews knew how to operate a Sharpie marker and put a few notes on the air handler/furnace. I know, most of them will never see the equipment again and what they install will never drive them nuts.

    • @thehvachacker
      @thehvachacker  3 ปีที่แล้ว +1

      Yes life would be easier. Also if t-stat wire and all other wires weren’t ran in bx. Harder to trace and follow wires when lots of armored cables ran together all over

  • @Ted_E_Bear
    @Ted_E_Bear 3 ปีที่แล้ว +3

    The Hacker is great on repairing complex issues !

    • @thehvachacker
      @thehvachacker  3 ปีที่แล้ว +1

      Just enjoy taking care of problems

  • @davidnull5590
    @davidnull5590 3 ปีที่แล้ว +4

    Congratulations Bill, so you're the first real HVAC tech they have seen in a million years? Nice work,

  • @roberts1159
    @roberts1159 3 ปีที่แล้ว +1

    Nice troubleshooting and being through with looking at all the possibilities for a frozen unit.

    • @jamescordes8673
      @jamescordes8673 3 ปีที่แล้ว

      So many guys would have just shut it off and come back later. Very few techs actually check out the mechanical stuff on a frozen coil. So lazy.

  • @bobgallo2178
    @bobgallo2178 3 ปีที่แล้ว +2

    Wow, sure glad I don't have to work on that one. I feel for you young men. Condenser doesn't look that old, I guess they are making junk these days. I am an old guy who is retired.

  • @baobui7104
    @baobui7104 11 หลายเดือนก่อน +3

    You are a smart ac tech sir

  • @WeatherNut27
    @WeatherNut27 3 ปีที่แล้ว +4

    I had frozen coils on mine once and it was because condensate drain was blocked and water leaked onto the AH filter. Usually frozen lines = a refrigeratant leak, low on charge, or bad filter. In my case it was a wet filter.

    • @thehvachacker
      @thehvachacker  3 ปีที่แล้ว +1

      Wet Filter blocks airflow the same as a dirty plugged up filter. Frozen lines are from the symptoms you listed. With one added scenario: system left on long time after the evaporator froze. Many don’t shut down the system when it’s not working.

  • @billnipp2309
    @billnipp2309 3 ปีที่แล้ว

    I did commercial service work for several years. Last 18 years Ive been working at one large site but I do miss the detective work required to find the issues and dealing with different types of people...

  • @billsimpson604
    @billsimpson604 3 ปีที่แล้ว +1

    I see where they are phasing out HFC refrigerants. Glad I stocked up on 134a on Amazon for the old Expedition. You know the price will begin to go up now.
    I recently bought a Chinese made window unit for AC backup to be run by a generator in case of power loss during a hurricane. It warns not to puncture it due to possible fire hazard.

    • @thehvachacker
      @thehvachacker  3 ปีที่แล้ว

      I should stock up in some 134 for my Astro.

    • @Bryan-Hensley
      @Bryan-Hensley 3 ปีที่แล้ว

      @@thehvachackerI've used propane in mine in the past when I was broke. It works pretty good

    • @stevee7774
      @stevee7774 3 ปีที่แล้ว +1

      @@Bryan-Hensley - I’ve heard of using propane on older R-12 systems because pressure/temp relationships pretty close but I’ve never heard it used in a R-134 system.

  • @1keykneedeep
    @1keykneedeep 3 ปีที่แล้ว +2

    Good work Hacker. There on the Zero maintenance program.

  • @deathrawphantasma
    @deathrawphantasma 3 ปีที่แล้ว +2

    When customers just yap away
    “They only go here, I’m serious, like yeah I don’t know how many times they came and they only go here and there I’m serious”

  • @dr.comforthvacr8889
    @dr.comforthvacr8889 3 ปีที่แล้ว

    Wow you are amazing hacker! Good job on safety diagnostics as well!

  • @caru3257
    @caru3257 3 ปีที่แล้ว +1

    I did find one with intermittent cooling. The compressor was dirty and the indoor coil was plugged. I had a whole day of work at a storage place as a follow up and another unit had a transformer burned out.

    • @johnlira3316
      @johnlira3316 2 ปีที่แล้ว

      How did u clean the compressor

  • @tonydelgrego2906
    @tonydelgrego2906 3 ปีที่แล้ว +1

    Nice troubleshooting

    • @thehvachacker
      @thehvachacker  3 ปีที่แล้ว

      Thanks i enjoy solving problems

  • @baobui7104
    @baobui7104 11 หลายเดือนก่อน +3

    My Mac once in a while froze like that one you work on I turn off the compressor because it kept running and power off and on the thermostats and it work again
    Is that what I suppose to do sir because expert ac guy don’t know

  • @Mike-cc3bc
    @Mike-cc3bc 3 ปีที่แล้ว +2

    I'm gonna recommend changing this perfectly fine functioning contactor.....

    • @thehvachacker
      @thehvachacker  3 ปีที่แล้ว +4

      Contactor was overheating and starting to pit. I never got to recommend that since the whole unit had to be replaced.

    • @RobertL78
      @RobertL78 3 ปีที่แล้ว +2

      It’s called “preventative maintenance” for a reason.

  • @NerdThingsAndMore
    @NerdThingsAndMore ปีที่แล้ว +1

    Thanks for the info and video.

  • @Jozamendo
    @Jozamendo 2 ปีที่แล้ว +2

    Compressor leak is what froze pipes, the other thing was extra .. 👍

  • @joeymac221
    @joeymac221 3 ปีที่แล้ว +5

    The unit is a micro channel.........JUNK. That's why the unit is freezing up. It's low on refrigerant.

    • @thehvachacker
      @thehvachacker  3 ปีที่แล้ว +5

      Yea it’s junk, too bad it’s all the manufactures, want to make these days

    • @mazhariqbal26
      @mazhariqbal26 3 ปีที่แล้ว +1

      Yes, I agree with you

  • @Eddy63
    @Eddy63 3 ปีที่แล้ว +2

    Hackster making NJ cool one unit at a time ... Lol ... Good troubleshooting ...

    • @thehvachacker
      @thehvachacker  3 ปีที่แล้ว

      Thanks I enjoy interesting calls

  • @rickdaystar477
    @rickdaystar477 3 ปีที่แล้ว

    You think maybe you support the armorflex cable with a strap to relieve any tension on the control wires so they don't get tugged loose from the connector block?

  • @SoutheastHVAC
    @SoutheastHVAC 3 ปีที่แล้ว +1

    Just one damper not opening can cause it to freeze up? I believe you. But could you explain how? Is it because the thermostat for the area couldn’t ever satisfy?

    • @thehvachacker
      @thehvachacker  3 ปีที่แล้ว +2

      If you have no air flow what happens to the evap coil? It freezes. Therefore if all zones are closed and the ac is running you have no airflow. That causes the coil temp to drop below freezing and start icing. Yet that was a symptom. Not the main reason for system freezing. The main reason was revealed later in the video

    • @jamescordes8673
      @jamescordes8673 3 ปีที่แล้ว

      Not enough air flow over the inside coil will cause it to freeze so if that zone is calling and no others are then the air is going nowhere and will freeze the coil. Lucky for her other zones seem to be calling more but the system would never shut off too.

  • @Wolfhound.
    @Wolfhound. 3 ปีที่แล้ว +1

    8 years wow that red and green light been off for a long time

    • @thehvachacker
      @thehvachacker  3 ปีที่แล้ว

      I think the lady was over exaggerating. Yet it was what I was told. That is the reception area printers and about 6-10 people at all times

  • @bubcity9448
    @bubcity9448 ปีที่แล้ว +2

    Could a leaky Schrader valve cause the compressor to not work

  • @mark.r8900
    @mark.r8900 3 หลายเดือนก่อน

    Great video. My suction line is frosting up. Indoor temperature is 75F and outdoor ambient is 70F. It's r410a with low suction pressure. The low side saturation temp is 28F. I am getting low superheat but normal subcooling with fixed orifice. Filter is clean and air flow is good. The coil has no frost but frosting just before service valve at outdoor condenser. All amp draws are good. I tried adding some refrigerant but the low side pressure would not rise. I just can't figure this one out. Any help would be greatly appreciated. Thank you.

    • @thehvachacker
      @thehvachacker  2 หลายเดือนก่อน

      Is the system overcharged? Low superheat seems like an airflow problem or overcharged. Is evap coil possibly dirty? Subcooling not that important with fixed orfice. Superheat is used for charging piston systems.

    • @mark.r8900
      @mark.r8900 2 หลายเดือนก่อน

      Thank you.

  • @proanswers
    @proanswers 3 ปีที่แล้ว +2

    5:54 Nice diagnosis. If you want to be a great technician or scientist- slow down- think- work the cause and the effect. One of your better vids. Get the wago lever connectors brand (germany ) by them from an electrical supplier store unless you can verify the amazon seller (there's china knock-off wago's). That HZ2432 board was installed in an inappropriate service area, IMO. On another note a doctors office should have better clean air manage ment standards- can only imagine the bacteria, virus, mold etc in the air handler/duct system.

  • @realestateservicessaleshea99
    @realestateservicessaleshea99 3 ปีที่แล้ว +4

    Looks like micro trash I mean channel👀🏌🍇
    Stay safe.
    Retired (werk'n) keyboard super tech.
    Wear your safety glasses.

    • @thehvachacker
      @thehvachacker  3 ปีที่แล้ว

      I should wear those glasses but with mask even the fog free ones build up condensation

  • @heroknaderi
    @heroknaderi 3 ปีที่แล้ว +2

    Your amazing 🤩 wow incredible find😎🤩

  • @HsingSun
    @HsingSun 3 ปีที่แล้ว

    I just fixed up the ac line frozen because the renter set up the wrong temperature two hours ago. I took less than one hour to turn ac on.

  • @monkeesniper1834
    @monkeesniper1834 3 ปีที่แล้ว

    Haven’t watched video but contacter is either stuck or defrost board is bad! Run it in cool with no g call it’ll defrost it

  • @lzgamer8133
    @lzgamer8133 3 ปีที่แล้ว

    I suggest pulling out the entire terminal, tighten wire, reconnect terminal.

  • @ulisesmiron6838
    @ulisesmiron6838 3 ปีที่แล้ว +2

    Leaking

  • @moonlightacmaintenance3232
    @moonlightacmaintenance3232 3 ปีที่แล้ว

    You didn’t offer to clean the condenser?

    • @thehvachacker
      @thehvachacker  3 ปีที่แล้ว +1

      I didn’t have enough hose, needed 300 ft. Don’t carry that much unless I am pressure washing coils

  • @enriquemontenegro5222
    @enriquemontenegro5222 3 ปีที่แล้ว +1

    Wait soo why did it become frozen ? Bc the contractor started to go bad ?

    • @dantemariscal8679
      @dantemariscal8679 3 ปีที่แล้ว +3

      No, the zone control was stuck closed because of the fallen wire and it causes an airflow restriction which causes units to ice up. The burned contactor isn’t necessarily a problem because it’s still kicking in and out when he takes off the thermostat wires but it is an indicator that something is over amping and 90% of the time it’s the fan motor

    • @johnlira3316
      @johnlira3316 2 ปีที่แล้ว +1

      Can a bad thermostat cause freezing?? If so how?

  • @elmerramirez1215
    @elmerramirez1215 3 ปีที่แล้ว +4

    Stuck contactor

  • @steveblake8766
    @steveblake8766 3 ปีที่แล้ว +1

    #21 Thumbs uP

  • @97Napkins
    @97Napkins 3 ปีที่แล้ว +4

    Another York micro channel disaster 😑😕. Worst leaker awards Olympic style. Gold medal goes to Yorks micro channel, silver metal goes to Lennox and there 2014 class action coil law suit and there still leaking 😆 and bronze goes to Goodman/Amana because there still crap.

    • @sknight0391
      @sknight0391 3 ปีที่แล้ว +3

      You hit the nail smack dab on the head with that comment Patrick. You are exactly right. In that exact order too. How has it been this many years and Lennox has still not fixed their indoor coal issues? They deserve to be sued. It is ridiculous how bad the issue is and has been for so many years. 😎👍

    • @97Napkins
      @97Napkins 3 ปีที่แล้ว +3

      @@sknight0391 around here builders have built many new neighborhoods with all lennox unit. Guess I can't be to upset. It's work all the way till I retire and I'm 38. 😆🤣😂

    • @thehvachacker
      @thehvachacker  3 ปีที่แล้ว

      I the new aluminum coils seem to hold up a lot better. I think electrolysis could be a factor. Most Lennox leaks are back corner opposite of drain side near bottom. Right where the copper goes through the steel. We will see. I don’t think the class action lawsuit was 2014, units covered many years after that. I think 2014 was the Copeland compressor sludge that took out many txv’s on Lennox units. Yet time goes so fast it could of been both.

    • @sjefoekel6058
      @sjefoekel6058 3 ปีที่แล้ว

      @Eric M alu tube and fin type are somehow ok ish. But the microcrap is a disaster.

  • @RaptorInNewMexico
    @RaptorInNewMexico 3 ปีที่แล้ว

    "Yo Ninzio the Dampa was unplugged.... ohhhh!

  • @andypysadee8260
    @andypysadee8260 3 ปีที่แล้ว

    Low gas

  • @daltonvandenberg6764
    @daltonvandenberg6764 3 ปีที่แล้ว +1

    first

  • @chrisbrown5336
    @chrisbrown5336 3 ปีที่แล้ว +2

    Definitely a hack. You never turn off unit untill you know whats wrong with it.

    • @Thermoelectric7
      @Thermoelectric7 3 ปีที่แล้ว +1

      All he did by pulling the disconnect was turn the compressor off. Control side was still calling for cooling, which he demonstrated by testing the contactor.
      There was no benefit to leaving that unit running, as it being that frozen up would cause low pressures and hide the refrigerant leak. Best to turn off the compressor and let it melt as soon as you can.
      Obviously doesn't apply to all situations.

    • @thehvachacker
      @thehvachacker  3 ปีที่แล้ว +2

      Won’t apply to a furnace fault. Most modern high efficient systems will save their precious 5 or so faults. Yet a frozen system can’t be worked on.

    • @thehvachacker
      @thehvachacker  3 ปีที่แล้ว +6

      I love how people think I am really a hack. Then show off their lack of knowledge/ experience. As they try to prove what I do as wrong. Everything I do is by code, or what’s best for my customer.

    • @potatolew4495
      @potatolew4495 3 ปีที่แล้ว +3

      Pretty damn obvious that the unit is frozen. The unit has to thaw before refrigerant side is serviced. Yes a low charge can cause this but a shorted contactor, blower motor issues, etc could cause this. Hacker did a great job, stick to whatever it is you do and leave the technical HVAC to us professionals. WELL DONE HACKER, DON'T LET THE ARMCHAIR MASTER TECHS RUFFLE YOUR FEATHERS. CHEERS FROM L.B.I.N.J.

    • @jamescordes8673
      @jamescordes8673 3 ปีที่แล้ว

      Wtf are you talking about? Lmao. Shit is frozen. You don’t need the compressor running. Clearly it’s working cause if it wasn’t it wouldn’t be frozen 😂😂😂😂. I hope you don’t work on AC

  • @carlosambriz4507
    @carlosambriz4507 3 ปีที่แล้ว +2

    Bla bla bla not my problem 👎🏻👎🏻👎🏻👎🏻

    • @thehvachacker
      @thehvachacker  3 ปีที่แล้ว +3

      Snowflakes will hate. I did all I could for this unit.

    • @curtisjackson3556
      @curtisjackson3556 3 ปีที่แล้ว

      @@thehvachacker condenser on its last legs for sure. You did all you could🤙🏻 let them hate bro. cookie cutter techs all sound the same🤡