नमस्कार।आप इस महत्वपूर्ण विषय पर गंभीर होकर तत्काल CT RATIO &burden के लिए प्रेक्टिकल कैलकुलेशन का विडियो बना कर हमे दिखाए।आपको इस विडियो केलिए बहुत बहुत धन्यवाद।आप सभी मीडिया मित्रगण टीम सहित स्वस्थ रहे सुरक्षित रहे सजग रहे,,,!
very good explanation ABHISHEK SIR.....बर्डन से releted 1 question हे sir please give me answer Q1 * यदि CT BURDEN 5va हे और connected load 1va हे जो 1 analog meter हमने लगा रखा हो जो 5va से बहुत कम हे क्या इससे meter की reading पर कोई effec t *Q 2 अगर ans नही हे तो क्यो नही पड़ेगा please explain ?
Sir kuch mechnical valve equipment k upar video banaye..jaise ki turbine , mop , aop, jop kyunki 3 min ka video v bahut jyada impact wla hota hain..plz me steel industry me fresher hun bht jyada doubt ata hain bahut kuch chijo ko leke.
Ji sir janta hun mechanical topics but app kuch basic v batade inn sabke bare me bahut help ho jayega..sir apka explanation bahut acha haii..plz try kijiyega sir..
Sir what's about in high voltage line like 66kv, 132kv in industries where load is 6 to 7 MW , how can we decide CT burdon I am very confused about this
Sir mujhe 3 phase and neutral se puri building ka 220 load 70% and 440load 30 % chalana hai to load calculation ,power calculation,and wire selection kaise karen please ek vedio banaden .pure you tube par is tarha k vedio mujhe nahi milraha.sab sirf balance load calculation par vedio milraha hai.please please help me 🙏
Sir good afternoon Unbalanced load hai 3phase meter laga hai 1)R-17.90 ,Y-24 , B-15.20 am. Phase voltage 258,259,258 Watt kitna aayega sir Note -CT meter hai 2) only 3 phase meter input/output aaya hai gya hai R-13.10 Y-2.90 B- no load connected Phase voltage 238 ,239 hai Watt kitna aayega sir
Agar CT burden connected load se kam hai to aapko accuracy nahi milegi. Meter se monitoring proper nahi hogi. Jo values aap meter mein dekhoge usme error hoga. Isliye proper Burden hona jaruri hai.
The total burden = instrument VA given by manufacturer + 2* lead wire R*i + ( reserve VA) The reserve VA shall be 50% of {instrument VA + lead wire VA} This should be taken into consideration. The industry use mostly 5 Amp secondary current CT
नमस्कार।आप इस महत्वपूर्ण विषय पर गंभीर होकर तत्काल CT RATIO &burden के लिए प्रेक्टिकल कैलकुलेशन का विडियो बना कर हमे दिखाए।आपको इस विडियो केलिए बहुत बहुत धन्यवाद।आप सभी मीडिया मित्रगण टीम सहित स्वस्थ रहे सुरक्षित रहे सजग रहे,,,!
😂
Thanks for the vital knowledge in electrical engineering..helpful video..
Thank you Deepraj..
Also watch playlist for videos related to Drawing, Calculation, Motor, Transformer, Power Factor Correction and many more..
Dear sir
your technical knowledge is super sir
very good explanation ABHISHEK SIR.....बर्डन से releted 1 question हे sir please give me answer
Q1 * यदि CT BURDEN 5va हे और connected load 1va हे जो 1 analog meter हमने लगा रखा हो जो 5va से बहुत कम हे क्या इससे meter की reading पर कोई effec t
*Q 2 अगर ans नही हे तो क्यो नही पड़ेगा please explain ?
Very good sir
Explanation ka saath practical ho tho accha lagega
Sir ct aur rellay ke connection ko explain kar dijiye
Thank you sir, Very helpful knowledge 🙏
Nicely explained
Thank you...
Sir,if you make a video related to CT ratio selection, it would be more helpful for us..thank you..
Thanks sir .plz discribe type of c.t. & controlling c.t
Han sir jarur banaye video
Okay Prashanta..
Solid explanation
Sir CT KA ADDITIVE AND SUBTRACTIVE POLARITY PAR VIDEO BANA DIJIYE.
Okay Ajit..
as per in video digital meter burden is 0.5 so can we use 2.5va for digital meter ?
Nice explanation sir, ct accuracy class ka vedio banavo sir
Sir ek vedio positive negative zero sequence fault ke uper bnaye ye ht motor me kyu use hota hi ? Btaye
Dear, what does 1.5(6) mean? It is the current rating and normally it is written on CT Meters. Thanks
What if we connect -/5 metr to CT having secondary 1amp..I think there won't be any changes in MF..but error will be disturbed
Waiting for ur vedio
Can you suggest me please that, how to calculate CT Burden
Ct ka secondary voltage kaise nikale uspe video banaye
Please make video on multiplication factor
Sir kuch mechnical valve equipment k upar video banaye..jaise ki turbine , mop , aop, jop kyunki 3 min ka video v bahut jyada impact wla hota hain..plz me steel industry me fresher hun bht jyada doubt ata hain bahut kuch chijo ko leke.
Pranav ye to mechanical topics hai..
Ji sir janta hun mechanical topics but app kuch basic v batade inn sabke bare me bahut help ho jayega..sir apka explanation bahut acha haii..plz try kijiyega sir..
Okay Pranav..👍
Sir ct knee point ke bare me video banaye
Nice video sir,
Please make a video on CBCT
Okay Rajendra..👍
Sir 11KV line ke liye PT ka burden voltage kitna hota hai
Sir, if CT burden -20 VA but total burden connected 25 VA then, please describe most major effect in CT
Transmission line ke baren main details please video.
Saroj Maine transmission line pe banaye hai.. Aap wo dekh sakte hai..
Nice......
Sir commissioning ke waqt motor ka solo run test ka video upload kijiye
Dear sir,
How to calculate multiplying factor from CT and PT for 22kV
Transformer me power factor nhi hota h asa kyu aur hum Transformer me power factor correction kyu nhi krte
Sir breather may oil keep kyu use ki jati h is per vedio bana digiye
Balkishan, oil cap air ko insert hone se rokne ke liye lagate hai.. mai ispe ek video bana dunga.
Awesome 👌👌
Thank you sir 🙏
Most welcome KK..
Sir what happened when we selected high burden ct which can be use many output devices
Thanks sir
Ct burden ka calculation kese karte h sir plz make video
Sir what's about in high voltage line like 66kv, 132kv in industries where load is 6 to 7 MW , how can we decide CT burdon
I am very confused about this
What if we Select Higher VA Burden of CT?
🎉🎉
Very nice video 👍😊😊
Thank you...
good
Thank you Surinder..
Whether burden will be summation of all the cores?
Burden will be summation of load connected..
Also watch playlist for videos related to Drawing, Calculation, Motor, Transformer, Power Factor Correction and many more..
Thank you
Too gud video
Thank you Samvedna..
Transducer par ek video banaye please
Sirji....
Can we connect 1 No. Analog meter (1VA) and 1 No. MFM (0.5 VA) together to a single 1.5 VA CT..?
Sir mujhe 3 phase and neutral se puri building ka 220 load 70% and 440load 30 % chalana hai to load calculation ,power calculation,and wire selection kaise karen please ek vedio banaden .pure you tube par is tarha k vedio mujhe nahi milraha.sab sirf balance load calculation par vedio milraha hai.please please help me 🙏
Sir good afternoon
Unbalanced load hai 3phase meter laga hai
1)R-17.90 ,Y-24 , B-15.20 am.
Phase voltage 258,259,258
Watt kitna aayega sir
Note -CT meter hai
2) only 3 phase meter input/output aaya hai gya hai
R-13.10 Y-2.90 B- no load connected
Phase voltage 238 ,239 hai
Watt kitna aayega sir
Nice video sir
Thank you Rajesh..
Also watch playlist for videos related to Drawing, Calculation, Motor, Transformer, Power Factor Correction and many more..
suppose total meters burden =2.5VA
Then what will be CT burden rating?
Sir CT Knew point Q karte hain is k upor ek video banaiye.
Explain about CT & PT name
Sir 100/5 A KA CT HAI TOA VA KITNA HINA CHAHIYE .
MCCB BHI 100A ka hai.
Ct ka 2nd yeary side me load kyun lagayenge ?
Which types of load .
Load means ammeter, multifunction meter, relay..
CT ka secondary monitoring device and protective devices se connect kiya jata hai..
@@electricalwithabhishekjoshi burden VA maximus hoga to kya pronlem hoha
@@electricalwithabhishekjoshi ct ka burdrn maximum kitna hona chahiye
Agar CT burden connected load se kam hai to aapko accuracy nahi milegi. Meter se monitoring proper nahi hogi. Jo values aap meter mein dekhoge usme error hoga. Isliye proper Burden hona jaruri hai.
😊❤
How to select ct ratio 5 or 1
Sir name plate me burdon kaha mention hota hai
The VA due to lead wire loop lengths and resistance is also important and to be added while calculating VA along with connected meters VA
Thank you..
The total burden = instrument VA given by manufacturer + 2* lead wire R*i + ( reserve VA)
The reserve VA shall be 50% of {instrument VA + lead wire VA}
This should be taken into consideration.
The industry use mostly
5 Amp secondary current CT
Yes sir
Please show an example always
How to calculate ct retio
Playlist?
How to select ct ratio X/1 or X/5?
We will make video on this..👍
@@electricalwithabhishekjoshi Thank you sir..
Most welcome Raghav..
Burdun value kese nikale ge sar
Burden find kaise krte h sir
Praveen we will make video on this.
भाई लोगों आप लोग वीडियो को डिसलाइक कैसे, कर लेती हो यार,
Burden cluction kase kare
300/600/1 ct ka burden kitna hoga
Yes
Ct.ratio set kitna karna chahiye
Full load current ka ek range jyada ka CT lena chahiye.
Also watch playlist for videos related to Drawing, Calculation, Motor, Transformer, Power Factor Correction and many more..
Sir please next video mein ik example de dena ct burden pe🙏🙏
CT me 0.2 , 0.5 ya 0.2s , 0.5s aisa kyu hota hai. Aur PT me a ku nahi hota hai
🌟🌟🌟🌟🌟🌟🌟🌟🌟🌟🌟🌟🌟
Bina chart dekhe
CTPT sechuat kya he
Thanks sir