Ano ang tamang breaker para sa ROOM AIRCONDITION UNIT MO?

แชร์
ฝัง
  • เผยแพร่เมื่อ 4 ต.ค. 2024
  • Ito ang tamang computation ng pagkuha ng amperahe or setting ng circuit breaker para sa room aircon mo,mapa window or split type aircon man ito

ความคิดเห็น • 189

  • @AmandoBriello
    @AmandoBriello 6 หลายเดือนก่อน

    ANG GULO MO MAGPALIWANAG!!! panoorin mo nga muna yung ibang vloggers na ganun ding topic ang pinaliliwanag para matuto ka kung paano maglecture!

  • @BarkoTv
    @BarkoTv 4 ปีที่แล้ว

    Dami matulongan at detalyado.ayusss idol

  • @galawangelectrical
    @galawangelectrical 4 ปีที่แล้ว

    very detaiiled sa pag paliwanag lods, salamat
    maka tulong to sa karamihan.
    support para sa mga ka baro. enjoy blogging lang.

  • @juniorcajes4210
    @juniorcajes4210 2 ปีที่แล้ว

    nice tutorial! very educatinal sir! more power! 2 your channel

  • @w32gold
    @w32gold 2 ปีที่แล้ว

    Nice.. swak na pala yung 20A CB sa 2.5 HP split type A/C...tnx

  • @wyeth008
    @wyeth008 3 ปีที่แล้ว +6

    Fyi..if ang 175% gagawin mong decimal the correct one should be x1.75 only without % sign..why dahil technically as engineer, yung sinulat mo na factor na 1.75% ang kalalabasan nyan ay x0.0175 and this is way too different..so please be careful and review your units

  • @WardensCorner
    @WardensCorner 4 ปีที่แล้ว

    very informative.. keep on sharing videos sir

  • @JunPVlog
    @JunPVlog 3 ปีที่แล้ว

    Salamat sa pag share sir new supporters here

  • @willycanlas9393
    @willycanlas9393 2 ปีที่แล้ว

    thanks lodi sa tutorial👏

  • @thetitasdeclassifiedsurthr4864
    @thetitasdeclassifiedsurthr4864 4 ปีที่แล้ว

    Very informative! Thanks!

  • @cedricranoy439
    @cedricranoy439 3 ปีที่แล้ว +1

    boss maguunder size ka nyan.. use table 4.30.14.2 para sa full load current ng mga motors.. 1.5HP = 10A
    multiply mo nalang sa 2.25 para sa starting current.
    if gusto mo naman ng computation:
    [(HP x 746) / (230)(P.F.)(EFF)]

    • @eugeniogozon7440
      @eugeniogozon7440 ปีที่แล้ว

      Sir, assumption lang po ba yan ng PEC na sa 2.25 covered na ang starting current ng lahat ng motors?

  • @JEFFHUNK17
    @JEFFHUNK17 4 ปีที่แล้ว

    Thnkz very informative

  • @kcidadlapir8488
    @kcidadlapir8488 3 ปีที่แล้ว +9

    Para sa mabilis na computation ang sabi ng PEC ang 1.5 HP ay my FLC 10ampers at kapag conteneuos Load times mulang sya sa 1.25% 10ampers x 1.25% = 12.5 ampers use 3.5mm THHN 90°

    • @nestorlaguna8840
      @nestorlaguna8840 3 ปีที่แล้ว

      Malaki na po ba Yong wire na 25.5 mm at 90°c sa room air-conditioning na 1hp?

    • @MajesticRecaps23
      @MajesticRecaps23 3 ปีที่แล้ว

      @@nestorlaguna8840 Baka po 5.5 mm hindi 25.5 mm?? Ang 25.5 mm ay kasing laki na ng 1inch parang tubo ng faucet na po yan kalaki. Ang wire po na para sa aircon ay 3.5 mm (20 Ampere breaker) or 5.5mm (30 Ampere breaker). Kung malala mo yung wire ng charger ng cellphone ganun lang po kalaki.

    • @nestorlaguna8840
      @nestorlaguna8840 3 ปีที่แล้ว +1

      @@MajesticRecaps23 naayos ko na po sir, gauge 12 Lang po para sa 20 amps.

    • @eugeniogozon7440
      @eugeniogozon7440 ปีที่แล้ว

      Sir, di po ba pasok sa 2.0mm2?

  • @PangasinanVlog
    @PangasinanVlog 3 ปีที่แล้ว

    dto sa middle east, ang rated current ng 1.5 ton, nagrarange ng 8.5 or 8.7 Ampere. jan sa pinas, ang 1.5 hp, ang rated current na lumalabas 8.5 to 8.7 ampere din...samantalang 1 ton=4.76 hp....anglaki ng deperensya

  • @georgebels8806
    @georgebels8806 4 ปีที่แล้ว

    Nice master...

  • @johnreysaguagan2554
    @johnreysaguagan2554 2 ปีที่แล้ว

    Lods okay ba ipag sama ang refregerator at room airconditioner sa isang breaker lang?..30A yong breaker lods at #12 THHN naman yong wire.
    Sana po mapansin..🙏

  • @dms3813
    @dms3813 3 ปีที่แล้ว +1

    Gamitin mo ang 250% Inverse time circuit breaker.May contradiction kasi sa pag specify ng OCPD sa hermetic refrigerant motor-compressor between using PEC. Table 4.30.4.2 and the stated size from PEC 4.4.3.2 (175%-225%) which is wala sa Table 4.3.4.2. Sana magets mo. INVERSE TIME CIRCUIT BREAKER 250%

    • @eugeniogozon7440
      @eugeniogozon7440 ปีที่แล้ว

      Sir, in short, ano po size ng wire at breaker gagamitin dito sa 1.5hp AC. At kung pwede pang humirit, 1.0hp, 0.75hp at 0.5hp. sana gumawa kayo ng video, o kahit sa comments na lang dito. Salamat po.

  • @mabinisabigan7685
    @mabinisabigan7685 ปีที่แล้ว

    boss sa ilaw ay 15 ampher na breaker,pwede ba na no. 12 na wire ang gamitin.

  • @quaterpound2616
    @quaterpound2616 ปีที่แล้ว

    sir nasa 27sqm meter yung area ng house with 2small kwarto average of 2.3M ang Height ng cieling , ginawa ng installer sa indoor 2HP aircon is almost 2inch yung clearance sa cieling tama lang ba ito ? kasi after benta parang pinabayaan na kami.

  • @roneloantimano6941
    @roneloantimano6941 2 ปีที่แล้ว

    Ok lng po ba na khit hindi na i off ang breaker? Kc gabi gabi nmn po nmn gngamit?

  • @saffronbesanaiii4863
    @saffronbesanaiii4863 2 ปีที่แล้ว

    Tanong ko lang master kung 2.5 HP ang aircon ko pasok pa rin ba sa 20 amp ang gagamitin kong breaker...maraming salamat po sa sagot🙏🙏

  • @daniloangeles6968
    @daniloangeles6968 3 ปีที่แล้ว

    Boss anong wire size at breaker ang dapat gamitin sa 2hp at anong wire size naman sa 2 1/2 hp both non inverter?thanks

  • @nestorlaguna8840
    @nestorlaguna8840 3 ปีที่แล้ว

    Pwede bang humanity Ng 30 amp na circuit breaker sa room air-conditioning na 1hp Kung may kasama Syang ibang load?

  • @ardocfire3543
    @ardocfire3543 2 ปีที่แล้ว

    Boss ayos lng ba toh main breaker q sa dalawang 1.5hp na AC ay 20amps pero pagdating dun sa room ay tig isa nmn cla ng 20amps na breaker yung may saksakan sa ilalim❓

  • @melfordricachonda509
    @melfordricachonda509 3 ปีที่แล้ว

    Sir. Tanung lang po regarding sa install ng 0.5hp na aircon. Kc po ung ginamit kung breaker is 20amp
    Pero naka tap sa 30amp. Kc puno na ung panel ko.meaning wala bakante. Ung 30 amp. My kasamang mga 5 0utlet sir. Ok lang ba ito. Thanks sa sagot.

  • @jeromemacarayan9980
    @jeromemacarayan9980 ปีที่แล้ว

    Sir halimbawa mag additional aircon pasok pa ba ang 20 amps

  • @JonelCamos-kk8sn
    @JonelCamos-kk8sn ปีที่แล้ว

    Boss pano po kung ang ginamit na wire nung nag install ng aircon eh #10 ano pong wire gagamitin papuntang panel

  • @edgardeiparine
    @edgardeiparine 3 ปีที่แล้ว

    ano ba dapat gamitin na avr para sa 1.5 hp na electric motor

  • @budzjala7975
    @budzjala7975 3 ปีที่แล้ว

    Ano ang difference sa mga tawag ng inverter na may dual, triple, smart at digital inverters? At ano ang maganda sa mga ito. Ty sir.

  • @rahmyssun1690
    @rahmyssun1690 3 ปีที่แล้ว

    Nalito ako sa padulo ahahaha.... idol napansin ko kasi yung dito samin 30amp ginamit ang balak ilagay dun isang 1hp na arcon... ngayon po napansin ko na yung line nya may nakasama na isang maliit na heater sa banyo at dalawang outlet.... ililipat ko pa po ba yung iba?

  • @benedictgalang4699
    @benedictgalang4699 3 ปีที่แล้ว

    Sir dalawang room po Tig 1hp , pero isang linya lang po ac outlet na 20 amp circuit breaker po ..pwde po b?

  • @elmersoberano3765
    @elmersoberano3765 2 ปีที่แล้ว

    balik po Tau ng high school sir..he he..Kung convert nyo po Ang 175% to decimal 1.75 lang po..Wala na po % sign..ty

  • @roycedian03
    @roycedian03 2 ปีที่แล้ว

    Boss pwede ba Yung 40 ampere para sa 1.5 HP window type ac?

  • @macalvin3502
    @macalvin3502 4 ปีที่แล้ว

    Good Nice one

    • @BigGMind
      @BigGMind  4 ปีที่แล้ว

      Salamat sa supporta....nakadalaw n ko sa bahay mo

  • @gabrilaberogos1199
    @gabrilaberogos1199 3 ปีที่แล้ว

    Idol pg 3 pcs n aircone 1.5 hp ilang circuit breaker ang gamitin individual ba na my breaker t. y

  • @jmstv6851
    @jmstv6851 4 ปีที่แล้ว

    Galing..

  • @hermiebenting9360
    @hermiebenting9360 3 ปีที่แล้ว

    Sir tanong ko lang po
    Ang breaker ko sa room ay 30amp. Pwede ko ba e load ang gang outlet na 20amp. Tapos don ko e kabit ang aircon ko
    Hindi ba sya magkaroon ng prblema?

  • @jrbp8875
    @jrbp8875 2 ปีที่แล้ว

    Pwede po 30A circuit breaker for 3hp aircon?

  • @robertmancillajr8197
    @robertmancillajr8197 2 ปีที่แล้ว

    Sir ok lang ba ang 30amp circuit breaker sa 1HP Aircon?

  • @jerrycasimero2380
    @jerrycasimero2380 3 ปีที่แล้ว

    Aplicable ba yan boss na computation sa dc inverter aircon ..pareha lng ba yan sa hindi inverter..

  • @kristyangrey1162
    @kristyangrey1162 5 หลายเดือนก่อน

    Sir parehas lng ba ng computation ang split type at window type?

    • @BigGMind
      @BigGMind  4 หลายเดือนก่อน

      Yes po

  • @papachoktv8251
    @papachoktv8251 5 หลายเดือนก่อน

    nag tataka ako sa ibang vlog na electrical..sa2hp aircon 30amps daw dpt ang breaker .pero wala naman mabilhan na outlet na 30amps .sunog na ung outlet d pa dij mg ttrip ung breaker

    • @BigGMind
      @BigGMind  11 วันที่ผ่านมา

      20 amps,3.5mm2 n wire

  • @melchorgodinez
    @melchorgodinez ปีที่แล้ว

    Ser pwede ba dalawang aircon sa isang breaker

  • @ironfist4541
    @ironfist4541 2 ปีที่แล้ว

    Sir 3 tonner na aircon anong tamang breaker saka wire tnx po?

  • @ferdinandcastor3232
    @ferdinandcastor3232 3 ปีที่แล้ว

    salamat po sir may alam na ako sa aircon 20ampers para sa aircon 3.5mm pwde gamitin

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว

      Welcome sir...check din some of my video baka makatulong

  • @samdelacerna7518
    @samdelacerna7518 2 ปีที่แล้ว

    Halimbawa 3 aircon ilan ba ang dapat na breaker...

  • @SuperDarknyt26
    @SuperDarknyt26 ปีที่แล้ว

    Depende sa wire ng aircon napapansin ko maninipis na parang size 14 awg na kaya na ng 15amp cb

  • @conieenaldo7111
    @conieenaldo7111 4 ปีที่แล้ว

    good job

  • @johnniccoloasoro2122
    @johnniccoloasoro2122 ปีที่แล้ว

    boss 30 amp gamit ko sa breaker sa samsung ac splits type d lumalamig

  • @pablodumo4984
    @pablodumo4984 3 ปีที่แล้ว

    air condition unit is a continuous load, at ang circuit breaker n 30 amp can handle from 12 - 19 ... while circuit breaker 15-20 ampere can handle only 8 - 11 amp. for continuous... accdg to PEC

  • @JhunLagasca-f2l
    @JhunLagasca-f2l 7 หลายเดือนก่อน

    Sir pede po bang gamitin yung 5.5mm sa 20 ampears

    • @BigGMind
      @BigGMind  7 หลายเดือนก่อน

      3.5mm2

  • @jerseyvinluan8055
    @jerseyvinluan8055 3 ปีที่แล้ว

    Boss paano naman kung ang breaker ay 30amps tapos dalawang aircon ang sinusuplayan sabay na ang hp ay .5,,pwede kaya yon boss sa iisang 30amps breaker??salamat po..

  • @madeldivinagracia5597
    @madeldivinagracia5597 2 ปีที่แล้ว

    hi sir ilang AMP po ba bagay sa .75hp na aircon salamat po sa sagot .

  • @PangasinanVlog
    @PangasinanVlog 3 ปีที่แล้ว

    boss, baqt hp ang ginagamit at hind ton?base sa breaker mo at amperahe mo, pang 1.5 ton na ac unit..1 ton=4.76hp..ibig ba sabihin yang 1.5 hp mo ,0.36 ton lng?sobrng liit na nyan...

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว

      Tama ka sir may point ka...
      Pero ang required ng code is minimum 20amps cb for ac kahit maliit ang load computation ng a/c....

  • @marcosjuancordova5906
    @marcosjuancordova5906 7 หลายเดือนก่อน

    Sa 1.5 at 1 hp na dalawang aircon, kaya ba sa 30amp breaker❤

    • @BigGMind
      @BigGMind  7 หลายเดือนก่อน

      Yes po

  • @chigoragasanbanakakabiliit8998
    @chigoragasanbanakakabiliit8998 2 ปีที่แล้ว

    Ano ba ang tamang gamit ng 70 amperes sa panel board

  • @SonnyGabrieljr-s8m
    @SonnyGabrieljr-s8m ปีที่แล้ว

    Ilang aircon paganahin Ang 30 amp

  • @ryancollado2333
    @ryancollado2333 3 ปีที่แล้ว +1

    boss sa isang 30amp na breaker pwede ba ang 2 aircon dun? isang .5 at .6 hp na window type?

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว +1

      Mas maganda sir individual 20amps

  • @glenngalpo7482
    @glenngalpo7482 3 ปีที่แล้ว

    Nasa table ang rated current ng motor kung walang nameplate ang unit

  • @remzcipriano8048
    @remzcipriano8048 3 ปีที่แล้ว

    paano po kung ang nakalagay na recommended na breaker ng manufacturer mismo nung aircon eh 15A lang? gagawin mo pa din bang 20A yung breaker? paano ang warranty claim mo sa aircon kung sakaling kailanganin mo mag-avail ng warranty? Thanks.

    • @supercye5533
      @supercye5533 3 ปีที่แล้ว

      Minumum naman po sinasabi kalimitan ng manufacturer sir as their safe side. Maavail parin ang warranty kung sakali kasi nasa batas natin yun na 20amp dapat for 1hp at least.

  • @mhackclavecillas4230
    @mhackclavecillas4230 3 ปีที่แล้ว

    Boss ask ko lng d2 kz sa bahay ko nka 60amp. Ako main breaker tpos 30amp. Sa aircon at ref. Ko magkasama sila sa 30amp..ok lng ba sila magsama boss o bibigyn ko pa sila ng tig isang breaker mlpt sa outlet nila..???

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว

      Lagyan mo na lang yung sa aircon ng solong breaker pang ac.....20amps

  • @ezrasambrano7166
    @ezrasambrano7166 3 ปีที่แล้ว

    Boss pag .8hp AC bale 20A parin na breaker then #12 parin dahil both minumum for outlet yun no?

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว

      Yes sir tama

  • @enriqueacupan2979
    @enriqueacupan2979 3 ปีที่แล้ว

    Idol ask ko lang po kc naguguluhan po ako kung aan galing yung 1.75 a baguhan lan po ako sana po mapansin po ninyo message ko salamat po

  • @gabrilaberogos1199
    @gabrilaberogos1199 3 ปีที่แล้ว

    Idol pg sa refrigerator anung size ng wire ang gmitin at circuit breaker ilang amperes t. Y

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว

      20amps
      3.5mm2/#12 wire

  • @Heartnicole007
    @Heartnicole007 3 ปีที่แล้ว

    500 watts na aircon pwede na ba isaksak sa convenience outlet ng para sa mga appliances

  • @boybravo689
    @boybravo689 3 ปีที่แล้ว +1

    Boss mukang di ata tama yong pagcompute mo sa flc ng 1.5 hp ang alam ko ang flc nyan ay 10 amp base sa pec sir

  • @Misis_LTVlogs
    @Misis_LTVlogs 3 ปีที่แล้ว

    ano po ang size ng wore na gagamitin if 1.5hp ang unit ng split type?

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว

      3.5mm2 /#12 wire

  • @altheat6838
    @altheat6838 3 ปีที่แล้ว

    Pano po pag nagbrown out tapos nkasindi po aircon, di po ba masisira pag pinabayaan ko lang na bumalik? Pahingi po ng tips kung paano po makaiwas masira ac po pag brown out. Thank you..

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว

      Hindi naman po agad masisira yan....
      Pero ang sudgest ko po sa inyo na once na mag brownout.....i unplug nyo or switch off ang breaker ng aircon....tapos iset nyo kung may temp knob adjustment sa off position.....pag bumalik ang power...saka nyo lang i plug or on ang breaker ng aircon....sana makatulong

  • @jrmonte3002
    @jrmonte3002 2 ปีที่แล้ว

    Magkaiba kayo ng computation sa isa kong napanood dahil nag multiply pa sya sa 125% after then 250%. So sino sa inyo ang tama?

  • @bigdadysmall1659
    @bigdadysmall1659 2 ปีที่แล้ว

    My outlet ako boss tpos dun nag splice yung gumawa d2 samin para mag ka line para sa breaker na my out para sa aircon ok lang ba yun

    • @edwarddelarosa2096
      @edwarddelarosa2096 2 ปีที่แล้ว

      Eh sa oulet cya kmuha ng supply tpos aircon p

  • @carlmanubay1440
    @carlmanubay1440 3 ปีที่แล้ว

    Sir question. Kung maliit lang po ang aircon .5hp important pa din po ba maglagay ng ciruit breaker?

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว

      Kailangan sya na may breaker....pero pwede mo din sya iplug na may kasamang ibang appliances .....base sa code dapat na 50percent lang ng load ng ac.....hindi mo pwede pagsabayin ang plat iron at aircon sa iisang breaker....

    • @carlmanubay1440
      @carlmanubay1440 3 ปีที่แล้ว

      @@BigGMind salamat po sa advice ninyo. =)

  • @cesarsantiago5931
    @cesarsantiago5931 2 ปีที่แล้ว +1

    Wrong application of Electrical computation
    Rated HP is the power output of the motor
    We are calculating input power

  • @alvindizon227
    @alvindizon227 3 ปีที่แล้ว

    boss sa 1.5hp split aircon yong ginamit ko 30amper. yong wire 5.5mm #10 tama ba yun?

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว

      20amps lng ...
      3.5mm2/#12 wire

  • @becerelthis5238
    @becerelthis5238 3 ปีที่แล้ว

    while reading mga comments, napansin ko nagkaroon ng pagkakaiba sa sagot mo sa .6hp, sa isa comment mo 20amps dun nmn sa isa na pensonic 30amps sagot, pakilinaw nga po, ano dapat na amps na need sa circuit breaker. Confusing.

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว +1

      Kc sir magkaiba ang tanong nila....yung isa wala pang 20amps na breaker
      Yung isa naman may 30amps main breaker at bukod na 20amps for aircon
      Yung isa pinapalagyan ko ng 20amps....yung isa naman may naka abang na 20amps.
      Sana nakatulong

    • @becerelthis5238
      @becerelthis5238 3 ปีที่แล้ว

      @@BigGMind thank you sa pagbibigay linaw, 0.6hp kc nabili namin ac at wala pang breaker, ndi din kc namin alam na need ng breaker, akala namin pwede derecho saksak na lang parang electric fan.p

  • @wenzv9470
    @wenzv9470 3 ปีที่แล้ว

    sir anong mangyare if # 10 thhn ang ginamit ng electrician for 2 hp aircon at # 10 thhn sa 1.5hp at 30 Amp each circut breaker.? anong dapat gawin if oversizes to ?

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว

      Kung #10thhn ang wire mo..oversize yan.....pati breaker mo...
      Dapat #12/3.5mm2 thhn wire @20amps breaker...each aircon
      Pero mas maganda if naka install na ang wire....gawin mo na lang 20amps ang breaker ng aircon mo each....

    • @wenzv9470
      @wenzv9470 3 ปีที่แล้ว

      sir,mahirap n kc palitan ang wire na #10 thhn kc n install na s Conduit.. u mean ok lng na #10 thhn ang wire tpos 20Amps ang breaker? para kasing hndi sya balance..

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว +2

      Yes...ok lang malaki ang wire kaysa breaker....wag lang malaki ang breaker kaysa wire..

    • @flamecaster23
      @flamecaster23 3 ปีที่แล้ว +1

      Mas maganda na malaki ang ampacity ng wire kesa sa breaker tandaan nyo nyan, very safe. Yung cost lang kaya ginagawang equal yung 2. Para bang" bakit ka gagamit ng sobra pede naman sakto?

  • @azwra1th
    @azwra1th 3 ปีที่แล้ว +1

    Can I use 30amps sa 1hp? Or strictly for 1.5hp?

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว +3

      20amps for 1hp even 1.5hp...

    • @azwra1th
      @azwra1th 3 ปีที่แล้ว

      @@BigGMind Thank you!

  • @rosalindapangilinan1645
    @rosalindapangilinan1645 3 ปีที่แล้ว

    Boss ang linwa. Boss sab. .6 hp. Na pensonic window type ano dapat getting breaker at size ng conductor wire? Salamat kung masagot mo

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว

      Dipende sir kung anong voltage....pero assume natin na single phase 230vac
      Hpx746/v=19.4amps
      Base sa article 4.40.3.2
      Not exceeded 175%
      19.4x1.75=33.95amps
      Used 30amps cb

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว

      5.5mm2 conductor base sa table 3.10.2.6(b)16

  • @edguantero9188
    @edguantero9188 3 ปีที่แล้ว

    Bakit naman masusunog bahay mo pag gagamit ka ng 30amps ? Para mag trip ??
    Pag malaki ba size breaker gagamitin sa mga appliances nakaka cause ng sunog ?

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว +1

      Oo naman....kapag ang
      .6hp na aircon mo nagka problema at nag init ang compressor ng aircon pwede mag cause ng fire yan.....tingin mo mag titrip ang 30amps breaker mo?sisirain muna aircon mo nyan at yan ang iniiwasan natin

  • @kcidadlapir8488
    @kcidadlapir8488 3 ปีที่แล้ว

    1 HP ay mayron FLC 8 ampers 8ampers X 1.25% = 10ampers. Para sa isang 1 HP

  • @JP-rw7xs
    @JP-rw7xs 3 ปีที่แล้ว

    Boss 1hp nka 32amp breaker ako with #12 na wire. Ok lang sya nun?

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว +1

      Ang laki ng breaker mo...pang welding machine na yan....pag nag karoon ng problem ang ac mo...hindi mag titrip ang breaker
      Palitan mo ng 20amps breaker mo
      Dahil base sa code..minimum na breaker ay 20amps for appliances
      15amps naman for lightings
      Tama na yang 3.5mm2 or #12 na wire

    • @JP-rw7xs
      @JP-rw7xs 3 ปีที่แล้ว

      Salamat sa info boss. Cge po palitan ko. May isa akong breaker magkasama 1hp aircon at shower heater 32amp

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว +1

      Ok lang yan....magkasama aircon at heater shower...32amps

    • @JP-rw7xs
      @JP-rw7xs 3 ปีที่แล้ว

      Salamat boss. Malaking tulong

  • @francorazon2555
    @francorazon2555 3 ปีที่แล้ว

    Sir pwd ba Diritso panel board yung ircon Diritos sa breaker nya don sa loob

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว

      Yan ang mas maganda sir...saka mas safe....

  • @casianoorlinajr.2948
    @casianoorlinajr.2948 3 ปีที่แล้ว

    Sir pag sa 1hp na window type 230v ano tamang circuit breaker

  • @franciscoromero3176
    @franciscoromero3176 3 ปีที่แล้ว

    Ano main breaker pag may motor at aircon ilaw outlet

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว

      Pa check po sa iba ko pang videos...nandoon po lahat ng sagot sa katanungan ninyo....

  • @toyomansi1297
    @toyomansi1297 2 ปีที่แล้ว

    Pano pag 2.5hp ilang amps ang recommended? Thankyou

  • @edisonolangco975
    @edisonolangco975 3 ปีที่แล้ว

    BOSS KUMIM MO SA TABLE NG PEC YUNG FLC OR FULL LOAD CURRENT 1.5HP DUN KA BUMASE NG SIZE NG CB AT WIRE MO MALI PO YAN

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว

      Sir check some article in this video ..lahat yan galing sa PEC 2017

    • @yuzz5004
      @yuzz5004 3 ปีที่แล้ว

      Mag base ka sa table ni pec ng motor load. Unless other wise naka indicate yung full load current ni motor sa name plate rating. Not totally 746 watts ang equivalent ng acu sa 1hp. Dahil meron pa siyang mga fan sa loob.

  • @sidsmags6810
    @sidsmags6810 4 ปีที่แล้ว

    nice

  • @arielcunanan4994
    @arielcunanan4994 ปีที่แล้ว

    Alin ba tama yung iba 250% ang DF na ginagamit bkit ikaw 175%

  • @glennhanselcoralde6609
    @glennhanselcoralde6609 3 ปีที่แล้ว

    Boss. Ilan amperes ang 1hp na inverter Aircon.

  • @adobo-tw7zz
    @adobo-tw7zz 2 ปีที่แล้ว

    Thanks sir..

  • @athansagarino8891
    @athansagarino8891 3 ปีที่แล้ว

    Sir gd ev, may tanong po ako, 60amps ma main circuit breaker ok lang ba pag may dalawang window type na aircon, isang reef at tv. Pero ang dalawang aircon may tag iisa silang 20 amps, at iba naman ang outlet sa tv. Ang ibig sabihin ko po, pag sabay sila ginagamit ok lang ba sa 60 amps na main breaker?

  • @benjamindalere203
    @benjamindalere203 3 ปีที่แล้ว

    Boss sa 2HP na splittype pwede po ba ang 30Amp

    • @displaylou
      @displaylou 2 ปีที่แล้ว

      Gamit ko 40amp na breaker tapos wire no.10 para sa 2hp inverter Daikin. Yan ang recommendation ng electrician sakin .

  • @ronaldoarcala2726
    @ronaldoarcala2726 3 ปีที่แล้ว

    Idol pwede b s 1hp ang 15amp?

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว

      Nope......dapat 20amps
      3.5mm2conductor/#12 wire
      Kc ang 15amps ay para lang sa lighting

    • @ronaldoarcala2726
      @ronaldoarcala2726 3 ปีที่แล้ว

      Salamat idol you re the best.

  • @jasonvitan2145
    @jasonvitan2145 3 ปีที่แล้ว

    Sir window type inverter 1hp pwede ba 20amp?

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว

      Yes....20amps ocpd
      3.5mm2 wire/

  • @eduardsuliva1696
    @eduardsuliva1696 3 ปีที่แล้ว

    Pag dalawa aircon ilang dapat Ang ampirahe

  • @carmelogalojr9694
    @carmelogalojr9694 3 ปีที่แล้ว

    Kailangan ba sa isang aircon ay tig isang breaker?

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว

      Yes para pag on service ang isa...yung other aircon ay hindi madadamay dahil may sarili syang breaker

    • @eugeniogozon7440
      @eugeniogozon7440 ปีที่แล้ว

      @@BigGMind Sir, nung ni repair AC namin, unplug siya. Mas safe kung unplug. Hindi kinailangan i off ang breaker. Baka iba ang dahilan bakit separate ang breaker

  • @bwayne6441
    @bwayne6441 3 ปีที่แล้ว

    paps 0.6hp lang bibilhin kong ac, sabi ng magkakabit 30amps daw bihin kong breaker yung may outlet na. tama ba yan?

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว

      20amps lang......
      3.5mm2/#12 wire

    • @bwayne6441
      @bwayne6441 3 ปีที่แล้ว

      @@BigGMind thank you po!

    • @bwayne6441
      @bwayne6441 3 ปีที่แล้ว

      lods pwede kaya yung source ng breaker ko yung isang outlet sa kwarto ko? dalawa kasi outlet sa kwarto ko na nakaconnect sa branch ng main breaker.

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว

      Yes pwede yun basta dumaan sa breaker....safety yun

    • @bwayne6441
      @bwayne6441 3 ปีที่แล้ว

      @@BigGMind Thank you lods. dabest ka talaga!

  • @conieenaldo7111
    @conieenaldo7111 4 ปีที่แล้ว

    👏👏👍👍

  • @gemmaromero4433
    @gemmaromero4433 3 ปีที่แล้ว

    Saan mo kinuha yan 1.75% dba 1.25%.

  • @RhennArce
    @RhennArce ปีที่แล้ว

    Edi gawin mung 30 to 40 amp para safe ganun ka simple

  • @evangelynalabaso732
    @evangelynalabaso732 3 ปีที่แล้ว

    Pwede po ba sir yung ginawa ng electrician na yung 1.5hp na aircon..ginamitan nia ng 5.5 na wire at 32 amp na breaker wala po ba magiging problema don

    • @BigGMind
      @BigGMind  3 ปีที่แล้ว

      Pang welding machine na yang wire mo at breaker kc 1.5hp lang yan..
      Palitan mo yung breaker ng 20amps kc ang full load current lang ng 1.5hp ay 10amps lang tapos 32 amps breaker mo....
      Palitan mo ng 20amps cb
      Dapat 3.5mm2/#12 wire..
      Pero kung naka install na ang wire..wag mo na palitan....
      Breaker na lang para safe