no cool call havc not working, Carrier RTU roof top unit troubleshooting with Belimo economizer controller scroll compressor in reverse or running backwards #d2dnyac #hvac #hvactech #commercialhvac
Hi. I noticed that the control transformer is connected to the 240 VAC, from the factory. Is it not supposed to be connected to the 208 VAC.? due to the fact that your meter shows only 204.
Always enjoy your content 😊
Thank you for my friend
I installed one of those belimo controls on a new carrier install pretty cool setup
Thanks for stopping by
D2D NY Iam writing from ANGOLA-AFRICA, Iam also a tec. HVAC-R. I LOVE YOUR WORK
Shout out to ANGOLA and thanks for watching
Thank you sir I heard the difference of the compressors.Thanks keep up the good work !
Thanks for watching
You are the man
Thanks for watching
Very helpful!!!!!!
Thanks for watching
Don King 👑 right here 😁
🤣🤣🤣
Hell yeah !
Thanks for watching
Was it a new unit? They are lucky the compressors survived running backwards like that
😥 first summer
Hi.
I noticed that the control transformer is connected to the 240 VAC, from the factory.
Is it not supposed to be connected to the 208 VAC.?
due to the fact that your meter shows only 204.
Yes sir absolutely
What did you do to the Alarm call from the Belimo module?
Once I got the compressor going those alarms never came back
Carrier is using belimo now? Awesome
I was as surprised as you 🤣
I think Belimo is now joining the ranks of Honeywell , Johnson Controls , and seimens
@D2DNYAC Belimo is the Cadillac of controls, I'm happy to see that in there, and of course. Thank you for the video.
What did you do to the Alarm call from the Belimo module?
so can the system work properly for a long time with the compressor going the wrong way?
Nooooo... in fact all you will be doing is destroying the compressor that's all, mean while the system not cooling @ all
How did startup not get the phasing correct so weird
The unit was started up in the winter time!
Similar to Jade
Thanks for watching
DUUUUDE
Right
Just do it like Nike 😂😂😂😂😂
😂
That’s what happens when electrician powers your phased unit
I guess
Economize
Thanks for watching