TXV Troubles... HVAC Service Call

แชร์
ฝัง

ความคิดเห็น • 84

  • @juntang72
    @juntang72 ปีที่แล้ว +19

    I learned from someone that pulling out outdoor fan during whole system is running, head pressure should go up , low pressure stays same level for awhile, Txv is good. If low pressure goes up at meantime, telling Txv is bad. Thank you for sharing your knowledge with us.

  • @robertcherry4971
    @robertcherry4971 3 ปีที่แล้ว +23

    Low air flow would of made your super heat low,not high.It has the correct amount of refrigerant,look at that sub cool.Let’s see good on charge but superheat is off....What controls superheat?TXV check why it is underfeeding. Even more so low air flow would of made your delta t higher .

  • @leonardbalaban8791
    @leonardbalaban8791 3 ปีที่แล้ว +3

    Great, great video! thank you so much Josh for taking the time to record in such detail and explain. You’re a very nice and caring person!

  • @rocajive
    @rocajive 2 ปีที่แล้ว +4

    Hey man I appreciate how to really explain and how you explain in detail what you do. New tech here and actually learning about txv has been a bit challenging

  • @hrdworkin7633
    @hrdworkin7633 2 ปีที่แล้ว +1

    Great Video.....outstanding tip on verification of TXV trouble shooting!

  • @wisdomwisdom817
    @wisdomwisdom817 4 หลายเดือนก่อน

    Thank you so much for your time brother, , you are very kind and caring.

  • @jrh86
    @jrh86 ปีที่แล้ว

    Great service call diagnosis very precise informative and useful...thanks bro 👍👍👍

  • @jaimedpcaus1
    @jaimedpcaus1 ปีที่แล้ว +1

    I like the probes you're using. Cool video.

  • @terrygrant8126
    @terrygrant8126 2 ปีที่แล้ว +1

    Thanks for the fundamentals friend!

  • @ricoswavae512
    @ricoswavae512 3 ปีที่แล้ว +11

    Definitely TXV it’s slightly restricted, that’s why you have a high subcool when you started to add more refrigerant you have more liquid outside on the liquid line because it can’t get through that TXV kind of backed up. Suctions low like you said and your superheat is slightly high. It’s pretty much starving the evaporator and stimulating sort of like a low on charge that’s also why your delta T is low, not enough refrigerant going through the evaporator.

    • @themrmoy40
      @themrmoy40 ปีที่แล้ว +1

      where are the videos Rico?

  • @th-wt5pn
    @th-wt5pn 3 ปีที่แล้ว +3

    Good video yeah i agree those txv have a mind of their own lol can’t wait to see the follow up video.. hvac for life lol 🤙🏽

  • @SombraLocs
    @SombraLocs 3 ปีที่แล้ว +1

    Great video!

  • @actechformallyyomama746
    @actechformallyyomama746 3 ปีที่แล้ว +1

    You did good on this. I’m sure people will learn proper techniques from this video. I’ll be a new subscriber. I have videos as well you can learn from.

  • @Robyrich2377
    @Robyrich2377 7 หลายเดือนก่อน +1

    Note for the official record, you should’ve taken the bulb off in the first place of the TV and put it in a warm bucket of water before adding refrigerant. That would be the simple solution to the problem as well is a timesaver as well.

  • @TheThorRs
    @TheThorRs 3 ปีที่แล้ว +1

    i learned so much in this video. thanks lol

  • @sergiocruz5617
    @sergiocruz5617 ปีที่แล้ว +1

    Great explanation

  • @alejandromorales8359
    @alejandromorales8359 2 ปีที่แล้ว

    Great video

  • @kcomfortsystemshvac7060
    @kcomfortsystemshvac7060 3 ปีที่แล้ว

    Great video,,,,i think the TXV ,,non modulating how is should be,,,,!,,,

  • @hvacworkshop4791
    @hvacworkshop4791 11 หลายเดือนก่อน +3

    I have never seen a blower fan capacitor of 40 MFD. Usually 5-10. 40 is like the size of the compressor

  • @SombraLocs
    @SombraLocs 3 ปีที่แล้ว +1

    Those Fieldpiece wireless probes look nice, but it would be nice if they had bigger temperature clamps.

  • @stevencarrillo3615
    @stevencarrillo3615 3 ปีที่แล้ว

    I also learned a lot thanks the video was 👍

  • @gas_man1565
    @gas_man1565 2 ปีที่แล้ว +11

    good video, there was a better way of testing for the txv being bad. without wasting refrigerant. block the condenser and the SH shouldnt change if it does, then you got yourself a bad txv.
    very informative video. im a new subscriber. keep the videos coming.

    • @maxxflowtv876
      @maxxflowtv876 ปีที่แล้ว

      thanks, just learned this from a video I watched earlier today

    • @ziongiahn
      @ziongiahn ปีที่แล้ว

      Do you mean like covering the top of the condenser?
      Would it work if you disconnected the fan motor and taped a cardboard box ontop?

    • @jaybro1046
      @jaybro1046 11 หลายเดือนก่อน +1

      @@ziongiahnyes, I think disconnect fan wire , to see the SH change

    • @butlerstouchHVAC
      @butlerstouchHVAC 2 หลายเดือนก่อน

      @@jaybro1046what should happen when you disconnect fan motor?

    • @ryannapier7059
      @ryannapier7059 2 หลายเดือนก่อน

      Disconnecting the old fan will make your pressures spike fast, I would rather put something on top to block the fan

  • @ChrisChrisKris-ol7vh
    @ChrisChrisKris-ol7vh 2 ปีที่แล้ว +4

    Awesome video! I know I’m super late to the party but I agree the TXV is out of range and should be replaced. The only extra step I would have added is shutting down the system and watching the TXV equalize. Sometimes that will be a dead giveaway.

    • @SickaMorStyle
      @SickaMorStyle 2 ปีที่แล้ว +3

      Can you further explain about equalization? Would it not equalize? I’m asking because I had one, and after I shut the system down for a bit I noticed there wasn’t equalization or it didn’t happen as quick as I thought it should. Thanks for the response

    • @acrservicesmathewr7565
      @acrservicesmathewr7565 4 วันที่ผ่านมา

      @@SickaMorStylewhen you shut down the system, the txv senses suction temp, so the suction line warming up will cause txv to open up hints equalizing the pressures

  • @beefing313
    @beefing313 หลายเดือนก่อน

    Thank you b

  • @melvinwillingham233
    @melvinwillingham233 3 ปีที่แล้ว +13

    you should have a 9/16 wrench for the flare nuts. I’m old school and never use pliers on nut and bolts.

    • @zacharyreed45
      @zacharyreed45 2 ปีที่แล้ว +1

      I use an Xtra small crescent brand adjustable wrench, it's the most ridiculous $12 but, somehow I find a way to use it everyday.

    • @salvenezia1817
      @salvenezia1817 2 ปีที่แล้ว +4

      Why do we always have to give our two cents. Let the man do what he wants. It’s not wrong.

  • @markkoppisch705
    @markkoppisch705 3 ปีที่แล้ว +3

    great info, i heard of putting the txv bulb in hot water not cold.

    • @edwardgarza5104
      @edwardgarza5104 2 ปีที่แล้ว

      You can do both hot or cold. Hot water would open txv to allow more refergerant in causing lower super heat, cold water would close valve causing superheat to raise

    • @CarlosEduardo-ci6iz
      @CarlosEduardo-ci6iz 11 หลายเดือนก่อน

      Would this also work on elctrinic sensors?

  • @lucaswhite3411
    @lucaswhite3411 2 หลายเดือนก่อน

    You could also as a precaution check the temperature across your filter dryer. Looks like a small liquid restriction, possibly from someone not purging the system and not brazing with nitrogen causing oxidization that could clog the txv screen, or the filter dryer. Sensing bulb may also not be secured properly or insulated.
    That said looks like your on the right track.

  • @armandopineda5148
    @armandopineda5148 2 ปีที่แล้ว

    Thanks

  • @JOSERization
    @JOSERization 3 ปีที่แล้ว +8

    Measure quick is way better for probes you should try it out

  • @itsnotfar
    @itsnotfar ปีที่แล้ว

    Thanks for showing the numbers. Most youtubers don't or will show on a tiny cellphone. Dang, you got nice tools for the job. Maybe some day I will too.
    What do you think of putting the txv bulb in cold water then hot to see if its adjusting.

  • @smacleod69
    @smacleod69 ปีที่แล้ว +1

    I can see a huge problem on that furnace. The return should came in from both sides of the furnace. With that filter as dirty as it is raises static pressure and lowers CFM and can simulate a bad TXV.

  • @ParabellumX
    @ParabellumX ปีที่แล้ว +1

    I would've checked airflow first before checking the charge, but that's just me.
    After all, EAR.
    E-lectrical
    A-ir flow
    R-efrigerant
    Great video otherwise. Keep 'em coming. 😏

  • @davidbotello7383
    @davidbotello7383 2 ปีที่แล้ว

    What type of brand is that

  • @carlviele4228
    @carlviele4228 หลายเดือนก่อน

    What brand of tools are you using

  • @ArcolaBridge
    @ArcolaBridge 12 วันที่ผ่านมา

    Is it possible to clean a txv? Or do need replacement?

  • @biblebloopers946
    @biblebloopers946 3 ปีที่แล้ว +9

    I'm 7 minutes in and screaming that you're super heat is high. How could you have an airflow problem? But i knew you would figure it out

    • @salvenezia1817
      @salvenezia1817 2 ปีที่แล้ว +2

      We got a smart guy. Come on. We all think different. Ian’s it’s fine. Just because you saw that fast. All you can see is his screen. He was probably looking at other things. We always want to show that we are smart. Instagram humble ourselves and maybe even say I learned something today. Or at least give a compliment or great video.

    • @Rccrdawgs
      @Rccrdawgs ปีที่แล้ว +4

      Low air flow definitely would make everything colder...refrigeration 101

  • @jeremyg8568
    @jeremyg8568 ปีที่แล้ว

    I know I'm late to the video but shouldn't you try the cold/warm water first to try and free it up?

  • @user-hu4hx6bm6m
    @user-hu4hx6bm6m 2 ปีที่แล้ว +1

    Piston should be charged by superheat . Txv by subcooling.
    Your delta T is 11 it tells you right away you have a system restriction.
    Filter dryer, or system contamination or .
    You must check first if all your mechanic components are clean then see if you have a piston or TXV .
    You cant charge or measure a TXV system based on superheat it have to be on subcooling.

  • @michaelharris1653
    @michaelharris1653 ปีที่แล้ว +2

    Test txv. Disconnect cond fan and watch to see if txv modulates as it should.

    • @sdsd4284
      @sdsd4284 5 หลายเดือนก่อน

      What should happen at that moment

  • @renecuevas4128
    @renecuevas4128 ปีที่แล้ว +1

    Lennox old furnace with 40 mfd blower cap. Wow never seen it that high.

  • @allanbrito13
    @allanbrito13 2 ปีที่แล้ว +1

    Looks like the sensing blub is loosing its charge and causing the restriction

  • @sknight0391
    @sknight0391 3 ปีที่แล้ว

    Older Lennox furnaces loved to use those big ole 40 mf'ers . Ever since the pulse furnace days. Good diagnosis. 👍

  • @original8879
    @original8879 29 วันที่ผ่านมา

    You know…..
    This TXV n 410A
    Have caused more problems n forced homeowners to spend more money…. Pain and frustration.
    Of course it keeps field technicians busy…but not all technicians have adequate knowledge of how to address n fix it….
    Specially in sunbelt area it’s not easy to work in hot 100+ attic.
    To a point it’s not worth it!

  • @godz1llaki11azzzz3
    @godz1llaki11azzzz3 2 ปีที่แล้ว +3

    Just had this problem literally today and same results normal to high subcool high superheat low delta T did a bulb test with the txv and turns out bulb had lost its charge

  • @troyb9609
    @troyb9609 2 ปีที่แล้ว

    You can pull the power wier on the condinsing fan and watch the hi side pressure climb and the suction line pressure will stay the same indicates a bad txv

    • @HVACTechTips
      @HVACTechTips  ปีที่แล้ว

      That’s a great way of doing it. I’ve never been shown that or thought of it. Thank you!! I’m gonna give it a try.

    • @butlerstouchHVAC
      @butlerstouchHVAC ปีที่แล้ว

      can you explain to me how to check for a bad txv? new tech learning need better understanding

  • @TheThorRs
    @TheThorRs 3 ปีที่แล้ว +1

    I guess i wanna ask the chat here if anyone could help me out if thats ok. How does one know which pressures are appropriate? is it like written on the/a general rule of thumb that your suction and head pressures should be or is it some calculations needed. I can just google this but i see so many different answers and methods it gets kinda overwhelming to filter. Thank you

    • @HVACTechTips
      @HVACTechTips  3 ปีที่แล้ว +2

      There is a general idea for the right suction and head pressure according to which refrigerant you’re using. Although sub cooling will change depending on the manufacturer. And superheat is always figured by a general chart.

    • @HVACTechTips
      @HVACTechTips  3 ปีที่แล้ว +2

      Arrange for suction and head pressures will also go up and down depending on the temperature outside. It can get a little confusing LOL

  • @HNIC86
    @HNIC86 3 ปีที่แล้ว +1

    I've heard those TXV goes out faster

  • @vatslavorlov7441
    @vatslavorlov7441 11 หลายเดือนก่อน

    someone explain it to me; i thought with a TXV it tries to hold superheat constant, so why would adding it here result in a change? and how does that help to diagnose a restriction here

    • @gabrielblake4191
      @gabrielblake4191 หลายเดือนก่อน

      Txv should hold constant, if it doesn’t then it’s not holding SH properly

  • @5822huron
    @5822huron 3 ปีที่แล้ว +1

    Look at your suction temp also.. thats a dead giveaway

  • @jamesgutierrez8606
    @jamesgutierrez8606 2 ปีที่แล้ว

    It's wise to discharge the capacitor B4 checking it thanx brainiac out🤔🤪

  • @miguelperdomo786
    @miguelperdomo786 ปีที่แล้ว +1

    If you want to know if your txv is working, you need to change conditions. The easiest way is to disconnect the outdoor condenser fan, a properly working txv will keep superheat and suction pressure the same or just a little higher. But if it begins to climb then txv needs replacement.

  • @jackcline1581
    @jackcline1581 3 ปีที่แล้ว

    Can you just change the TXV to a piston an be done with it?

    • @HVACTechTips
      @HVACTechTips  3 ปีที่แล้ว +1

      Yes you can and we will do that sometimes

    • @williamryan181
      @williamryan181 ปีที่แล้ว

      It depends on the system. Single stage condensers, yes you can. 2 stage and above, no. TXV is required to regulate super heat.

  • @erichorton1440
    @erichorton1440 ปีที่แล้ว +1

    Wow, an hvac video that wasn't recoreded with a potato.

  • @redneckways1617
    @redneckways1617 5 หลายเดือนก่อน

    Could be as simple as bad bulb placement

  • @renecuevas4128
    @renecuevas4128 ปีที่แล้ว

    40 mfd for a blower motor. Is it a 110 volts EFM. Cause here 20 mfd is used for 1 HP up to 25 nothing higher than that.,,,,,,,,I kno Lennox Furnace install 40 mfd from Factory

  • @mikemalone6103
    @mikemalone6103 7 หลายเดือนก่อน

    First, never replace a Capacitor with the one you pull out, that might not be the right one in there. Get the data off the motor tag.
    Secondly, the superheat is much too high. See if the TXV has an adjustable post, it just might be just a bit of spooge in it. The test with the bulb is to put it in your hand to warm it up, fooling the TXV to feed and then see if the superheat comes down.
    However, the diagnosis was correct, Weak TXV, …

  • @ares3914
    @ares3914 ปีที่แล้ว

    I hate residential equipment when the have txvs that are not adjustable. Txv is done bro.

  • @abcdefghi2175
    @abcdefghi2175 ปีที่แล้ว

    IS THAT A SNAKES RATTLER TO THE RIGHT I AM OUT OF HERE 🐍🐍🐍🐍🐍🐍🐍🐍🐍🐍 😱😱🚑🚑🏥

    • @HVACTechTips
      @HVACTechTips  ปีที่แล้ว

      Lol I didn’t notice! I’ll have to go back and look. 🤦‍♂️

  • @alfonsobenitez8574
    @alfonsobenitez8574 ปีที่แล้ว

    The sound wasn't to clear. Maybe cause of the condenser. I had it full volume still couldn't hear it loud enough.