PAGKAIBA NG (ADDRESSABLE )SA ( CONVENTIONAL) PAGDATING SA FIRE ALARM SYSTEM..

แชร์
ฝัง
  • เผยแพร่เมื่อ 2 ต.ค. 2024

ความคิดเห็น • 198

  • @emmanuellimjoco4709
    @emmanuellimjoco4709 3 ปีที่แล้ว +6

    Iba talaga paliwanag kapag ka may actual experience ka sa site, I salute to people like you Sir..

  • @noelespireto3891
    @noelespireto3891 3 ปีที่แล้ว

    thanks for the tutorial idol....

  • @hoowardluckidara3826
    @hoowardluckidara3826 3 ปีที่แล้ว

    Salamat sa pagsagot sir,,pero sir diko talaga gets,,kasi close.system diagram With four smoke detector,,salamat sa sasagot,,god blz u always

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว

      sir diagram... lang na apat na devices yan pero innactual pwede ka magdagdag... yan ay reference mo lng.... gobless po sir at ingat lagi

  • @thereisalwaysaway6152
    @thereisalwaysaway6152 2 ปีที่แล้ว

    Imformative ... Ty sir

  • @acdcdiycircuits7069
    @acdcdiycircuits7069 2 ปีที่แล้ว +3

    in 4:39 mark of the video, that's what you called SELECTIVE SIGNALING. This applicable especially for high rise building where the rule fire above and below of the floor notification appliances will only be activated. This to avoid stampede during evacuation. If not for this rule, in case of fire the whole building fire alarm bell and horn strobe activated simultaenously, then tenants of the building will evacuate at once which eventually caused stampede.

  • @jubelnuestro6667
    @jubelnuestro6667 3 ปีที่แล้ว

    Salmat kabayn

  • @rolandovelasco-by6im
    @rolandovelasco-by6im 8 หลายเดือนก่อน

    Sir kaya po ako ako nagtanong dahil mag take po ako ng NCII ,Sana maipaliwanag po ninyo sa susunod ninyong blog.salamat po.

  • @jenwellnieves2274
    @jenwellnieves2274 ปีที่แล้ว +1

    Sir wala po kayong panel configuration 😊😊😊😊

  • @apolinarioremescal3762
    @apolinarioremescal3762 3 ปีที่แล้ว +2

    Sir gud pm po sa adresable po may nabangit nyo po na may balik sa positive sa huling smoke detector..saan po ba nakalagay sa panel ung balik na suply..

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว +1

      Don din sa terminal kong san nagmula ang wiring mo simula umpisa ang return ng wiring mo don din babalik yon..sir magkapit lang sir pisitive at negative lang din yan kasi may polarity

    • @apolinarioremescal3762
      @apolinarioremescal3762 3 ปีที่แล้ว

      A ok po kala ko sa batery...salamat po sir...

  • @emmanuellimjoco4709
    @emmanuellimjoco4709 3 ปีที่แล้ว +3

    Malinaw ang paliwanag mo Sir, the best ka talaga.

  • @arielescamillas7180
    @arielescamillas7180 3 ปีที่แล้ว +2

    To add more info's sir, some other addressable brand like ZETA its loop wiring to all devices should be in reverse polarity, example in the base of detector L1 and L2 is negative and the common is positive.

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว +2

      Magaling kapa sir...salamat sa info mo...

  • @MarkJerollBarrameda
    @MarkJerollBarrameda 7 วันที่ผ่านมา

    Addressable po Tanung Ku LNG po sir ok LNG po ba na naka bypass / jumper po ba ang loop in at tska loop out?

  • @edwinicogo5022
    @edwinicogo5022 ปีที่แล้ว

    Sir ano ang mga factors para piliin mo ang one over the other? Thanks

  • @arielescamillas7180
    @arielescamillas7180 3 ปีที่แล้ว

    Ang addressable system ang pinaka madaling imaintenance, alam mo agad saan ang problema di gaya ng conventional maraming gala at tingala ang gagawin mo para makita saan problema.

  • @jaykicks23
    @jaykicks23 2 ปีที่แล้ว

    Sir Pg ngpalit ng smoke detector kailagan pa ng programming ng new detector?

  • @hoowardluckidara3826
    @hoowardluckidara3826 3 ปีที่แล้ว

    Boss tanong kolang po,,ano po yung close and open system.sa smoke detector,,diagram,salamat po?,,

  • @liezlianetabag3558
    @liezlianetabag3558 ปีที่แล้ว

    Sa coventional sir sa issng zone. Pwed ba na mglagay ng tatlo hanggang apat na strove pero nka pararel lng

  • @arifgani5326
    @arifgani5326 3 ปีที่แล้ว +1

    What you speak is beyond of my mind please speak in English thanks Pare

  • @rickycustodio9752
    @rickycustodio9752 2 ปีที่แล้ว +1

    Master,, may tanung po ako
    patingin po ako ng connection ng (addressable)sa loob po ng panel!
    Kung paano mo po na connect
    Sa mga temenal

    • @jub.tv123
      @jub.tv123  2 ปีที่แล้ว

      Pasensya na sir wala na ako ngayon sa fire alarm sa construction na ngayon ang work ko..

  • @JonahDeJesus
    @JonahDeJesus 7 หลายเดือนก่อน

    Hello po tanong ko lang po kapag addressable wala po sya end of line na may resistor ?

    • @jub.tv123
      @jub.tv123  7 หลายเดือนก่อน

      Pwdeng wala na kong walablng error sa FACP

  • @fireprotectionguy7943
    @fireprotectionguy7943 ปีที่แล้ว

    Nice. Saan ang lugar mo. Why not mag-set up ka ng a day and I will lecture sa Pinas. Visiting Lecturer. You can invite all electrician and FDAS people. My other channel "Ako Sa Sydney"

    • @jub.tv123
      @jub.tv123  ปีที่แล้ว +1

      Dito po ako sa ibang bansa sir...sa HUNGARY

    • @fireprotectionguy7943
      @fireprotectionguy7943 ปีที่แล้ว

      @@jub.tv123 hahahaha...akala ko sa Pinas. Ingat Lagi.

  • @juliushobbies8858
    @juliushobbies8858 4 หลายเดือนก่อน

    Sir ok lng po ba kahit d magkaka sunod sunod yong numbering ng mga devices??

    • @jub.tv123
      @jub.tv123  4 หลายเดือนก่อน

      Dapat sir magkasunod sunod para mabilis hanapin pag mag trouble shoot,

  • @jub.tv123
    @jub.tv123  3 ปีที่แล้ว

    Sa mga gostong pong humingi kong pano mag address ng fire alarm DEVICE na may depth switch paki lagay na lang po ng gmail acount sa may comment section at bibigyan ko.

    • @normandavid3398
      @normandavid3398 3 ปีที่แล้ว

      normandavid294@gmail.com

    • @rambncle8850
      @rambncle8850 3 ปีที่แล้ว

      Hello sir, paki suyo nalang po. "bhomar.bancale@gmail.com" . Thank you

    • @marlonsaraza2335
      @marlonsaraza2335 3 ปีที่แล้ว

      New subscriber po pa hingi rin po ako idoll.. slamat po sa video tutorial nyo po..
      marlonsarazabinuya@gmail.com

    • @accetv.amv.anime.animation
      @accetv.amv.anime.animation 3 ปีที่แล้ว

      asiadonhadz@gmail.com . Thanks lodi .

  • @carlkennethflores3697
    @carlkennethflores3697 ปีที่แล้ว

    Good pm po sir Jub, pede po bang ipagsama sa iisang loop ang Manual Pull Station, Alarm with Strobe Lights, Bell at Smoke Detector? Salamat po sa magiging kasagutan niyo po.

    • @carlkennethflores3697
      @carlkennethflores3697 ปีที่แล้ว

      Pahabol po pala. Yung mga components po ba para sa addressable ay hindi pede gamitin sa conventional FACP? Or Vice versa po. Salamat po ulit.

  • @robertbasijan8991
    @robertbasijan8991 2 ปีที่แล้ว

    Good pm, sir pag wireless po ang gagamitin need parin poba ng program ng panel para sa smoke? Salamat sir god bless

  • @diannecoderesninja5535
    @diannecoderesninja5535 3 ปีที่แล้ว

    Hi po sir tanong ko lang po may polarity po ba yung fire alarm at bell?

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว

      mayron po sir kasi DC po yan ang red po ay + or positive ang - po ay negative...

  • @JhemzVtv83
    @JhemzVtv83 3 ปีที่แล้ว +1

    Nice one Master.. May natutunan na naman po ako... Ask lng Master pag addressable ba di na need nang EOLR....

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว +1

      Hindi na sir

    • @JhemzVtv83
      @JhemzVtv83 3 ปีที่แล้ว

      Nice Master
      Sana yung actual naman na pag terminate nang addressable fdas....

  • @bloodymary6704
    @bloodymary6704 3 ปีที่แล้ว

    In addressable Fire Alarm system, what is the purpose of isolator base?

  • @reycortez4738
    @reycortez4738 3 ปีที่แล้ว

    Sir ilang oras magagamit ang back up battery if may power supply shutdown?
    Required din ba connect sa UPS ang FACP power supply?

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว

      Depende sa MAH. ng battery mo sir meang MILLIAMPS PER HOUR

    • @reycortez4738
      @reycortez4738 3 ปีที่แล้ว

      Thank u sir for your very informative presentation.

  • @bonilyn21
    @bonilyn21 11 หลายเดือนก่อน

    Ok lng Po ba kahit Anong brand Ng smoke detector, heat detector,manual push button sa addresssable salamat sa sagot

    • @jub.tv123
      @jub.tv123  11 หลายเดือนก่อน

      Recommended ko lang po sir yong mganda na brand ( seimens or simplex) ang brand subok napo namin yan...

  • @jaysontalan2932
    @jaysontalan2932 ปีที่แล้ว

    Sir halimbawa po sa isang unit po meron na po sya naka abang na isang smoke detector tapos po dadagdagan po sya ng smoke detector, pano po gagawin sir sa panel, addressable po sya sir

    • @jub.tv123
      @jub.tv123  ปีที่แล้ว

      Sir nasagot kona po ang tanong mo sa fb. Page ko..

  • @decalibrejunior1353
    @decalibrejunior1353 2 หลายเดือนก่อน

    Dami ko natutunan salamat idol

  • @junelofficialvlog.6762
    @junelofficialvlog.6762 2 ปีที่แล้ว

    Ang sa convensional class b wiring

  • @arielescamillas7180
    @arielescamillas7180 ปีที่แล้ว

    General alarm sir Ang protocol sa lahat Ng fire alarm system Lalo nat iisang building..kung magkakahiwalay Ang building pero monitored by one panel pede rin izoning Ang alarm sounder especially sa mga hospital

  • @jumelnonod6849
    @jumelnonod6849 3 ปีที่แล้ว

    mkhang 24V yan sir.dalawa e😁

  • @raineriorentor6110
    @raineriorentor6110 3 ปีที่แล้ว

    Master, kada floor ba katumbas non 1 loop? Para kada floor ay halimbawa 2 bell lang gagana

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว

      Pwde sir kong maliit lsng ang are mo,

    • @raineriorentor6110
      @raineriorentor6110 3 ปีที่แล้ว

      @@jub.tv123 pero sa 1 loop po ba kung 3 bell sounder sa 1 loop, lahat Ung 3 sabay2 na gagana kc Sakop siya ng 1 loop?

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว

      Depende sa panel at sa pag program sir at kong anong brand ng FACP. MO

    • @raineriorentor6110
      @raineriorentor6110 3 ปีที่แล้ว

      @@jub.tv123 ah ok po, Salamat sa reply master

  • @anniedacles433
    @anniedacles433 2 ปีที่แล้ว

    Boss poidi makangi ng klarong daigram ng addessables fire alarm? Ty and god bless

    • @jub.tv123
      @jub.tv123  2 ปีที่แล้ว

      Message mko sa fb. Page sir JUB.TV don ko e send sayo

  • @dx-hd2th
    @dx-hd2th 3 ปีที่แล้ว

    Sir , paano po malalaman sa plano Kung ,Ang fda's ay conventional o addressable?

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว +1

      Malalaman po yan sir sa wiring ...pag naka ring ckt. Meaning addressable yan..tapos kong hindi naka ring ckt. Meaniing conventioanal yan.

    • @aldrinymana9147
      @aldrinymana9147 3 ปีที่แล้ว +2

      Ang addressable may supply at return. ang conventional may endline with resistor

    • @jaimeignacio1240
      @jaimeignacio1240 3 ปีที่แล้ว +1

      brod nakapagkabit kana ba ng ganyan..kac dtu ginagamitan ko ng CC1 yung sau wala aku nakikitang CC1..kac parang kulang..sorry brod nagtatanung lang..kapag addressable kac my CC1 dahil pinoprogram lahat na device sa FAP..

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว

      Sa skimatic wiring diagram sir malalaman mo kong conventional or adressable

  • @CarlitoJrBayon
    @CarlitoJrBayon 2 ปีที่แล้ว

    JUB. TV , sir meron kabang FB? meron sana akung tanung sir salamat

    • @jub.tv123
      @jub.tv123  2 ปีที่แล้ว

      Mayron sir send mo email mo don ko ibigay sayo..

  • @jonathantalirongan3830
    @jonathantalirongan3830 3 ปีที่แล้ว

    Anong device ang e install sir para mag function ang splinkler ng tubig?

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว +1

      flow switch.. po sir mayron. po . sa springler yan na thermal operating element. normally fusible links or glass bulbs.. na kong sakaling may sunog maabot nya ang temperature yan ay mababasag ... at mag spray Ng tubig ang springker mo or foam....

    • @jonathantalirongan3830
      @jonathantalirongan3830 3 ปีที่แล้ว

      Ahh ok boss...salamat

    • @jonathantalirongan3830
      @jonathantalirongan3830 3 ปีที่แล้ว

      May video ka nyan boss?

    • @aldrinymana9147
      @aldrinymana9147 3 ปีที่แล้ว

      Gamit nmin module sa supervisory ay DCM4 o duel Contact pra flow switch at tamper switch

  • @junelofficialvlog.6762
    @junelofficialvlog.6762 2 ปีที่แล้ว

    Yan ang class A wiring

  • @decalibrejunior1353
    @decalibrejunior1353 2 หลายเดือนก่อน

    Salamat idol

  • @hoowardluckidara3826
    @hoowardluckidara3826 3 ปีที่แล้ว

    Sir yung addressional yun ba yung close system diagram,salamat po,,

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว

      Ang addressable fire alarm system sir aay ang mga devices nya ay nakaprogram sya or naka address at naka ring ckt. Connection sya..ang ring ckt connection ay pag out nya ang last wiring wiring device ay babalik yan sa FACP. may return cya ..
      ang conventional namn sir aY d naka address. Ang deviceS at d naka ring ckt. Pero ang last na wiring mo ay may END OF LINE RESISTOR SIR ..

    • @hoowardluckidara3826
      @hoowardluckidara3826 3 ปีที่แล้ว

      San po sir sa kanila ang close system diagram sir?

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว +1

      Ang addressable sir

    • @hoowardluckidara3826
      @hoowardluckidara3826 3 ปีที่แล้ว

      @@jub.tv123 thank you sir,,gud blz you sir,,

  • @reccakarl
    @reccakarl ปีที่แล้ว

    sa addressable fire alarm system po ba yun Bell at strobe light kailangan bang meron sariling power supply para gumana?

  • @retselzaracla5052
    @retselzaracla5052 2 ปีที่แล้ว

    Sir ask ko din po kung pwedi ndi kana mag return, smoke detector to panel board at sa strobe light/alarm? salamat sir..

  • @retselzaracla5052
    @retselzaracla5052 2 ปีที่แล้ว

    Sir, Ilang minimum ng Smoke detector ang pwedi sa isang MCP?

  • @huanfriend8857
    @huanfriend8857 3 ปีที่แล้ว +1

    Very good tutorial💖 watching iloilo tech

    • @glomanpanaligan5694
      @glomanpanaligan5694 8 หลายเดือนก่อน

      Sir ga kabit kamo automatic alarm,location mo

  • @paanovlog3296
    @paanovlog3296 ปีที่แล้ว

    Ang addresable sir is loop wire ang nilalagay at sa conventional ang end nya ay EOL resistor tama po ba?

  • @rolandovelasco-by6im
    @rolandovelasco-by6im 8 หลายเดือนก่อน

    Pwede bang i splice yong wiring ng addressesable

    • @jub.tv123
      @jub.tv123  8 หลายเดือนก่อน

      Pwde po

  • @rowelljamesmartin7942
    @rowelljamesmartin7942 2 ปีที่แล้ว

    SIR PWEDE BANG ABOUT CONTROL AND MONITOR MODULE NAMAN ANG TOPIC.SALAMAT

  • @molobologuys6112
    @molobologuys6112 3 ปีที่แล้ว

    Boss bakit yong call point tenest ko nag fault sa panel pero hindi nag ring ang bell,tapos tenest ko ang smoke detector na kasama nya sa circuit nag eergized naman Bell ano ang problema doon boss.salamat sa sagot

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว

      Sir anong ba ang system ng fire alarm nio?..at ang tenest moba na mCP. isa lng sila ng loop ng Smoke detector na tenest nong nag activate ang bell mo?..

  • @johnartalferez3888
    @johnartalferez3888 2 ปีที่แล้ว

    mga bos paano sa zone -1 tatlong kwarto tigdalawa ang smoke detictor ilan po ba ang push botton?

  • @nitzmendoza3675
    @nitzmendoza3675 3 ปีที่แล้ว

    sir doon po sa loob ng facp,khit saan po b...pde ilagay ung sd,s,mc...o my nkagay po sa loob ng facp kung saan lng pde ilagay...ty po

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว

      sir may ibang module ang sd.. sa id. net card pobyan naka connect and SD.

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว

      ang BELL namn or strobe light ay sa MODULE ng NAC. notification appliance circuit..

  • @aranilosiningan4290
    @aranilosiningan4290 ปีที่แล้ว

    good evening ser,,,Ang addressable alarm bell niya kailangan May return talaga ser,, salamat po..

    • @jub.tv123
      @jub.tv123  ปีที่แล้ว

      Opo sir kasi kong sakali maputol sir sa gitna at kong sang parte man may signal parin po.....at supply parin boo parin

    • @aranilosiningan4290
      @aranilosiningan4290 ปีที่แล้ว

      @@jub.tv123 salamat Po ser,,bagohan lang po...palagi akong nag sobaybay sa mga video mo

    • @aranilosiningan4290
      @aranilosiningan4290 ปีที่แล้ว

      @@jub.tv123 good evening ser...may video kaba sa fire alarm intercom Kong paano mag wireng niyan,,,hintay Po ako sa sagot ser.. salAmat po..

  • @manuelmendez5148
    @manuelmendez5148 2 ปีที่แล้ว

    sir bakit po nag biblink ang indicator Ng zone 3

    • @jub.tv123
      @jub.tv123  2 ปีที่แล้ว +1

      San po nag bliblink..sa facp ba sa monitor? Ano ba ang conventiional ba or addressable?..

    • @manuelmendez5148
      @manuelmendez5148 2 ปีที่แล้ว

      Sa monitor po.addressable po

  • @Rizwanahmad-cv4zl
    @Rizwanahmad-cv4zl 2 ปีที่แล้ว

    Bhai aap Language translate kre Hindi ya English me ,ok plz

  • @joy-qo9rv
    @joy-qo9rv 2 ปีที่แล้ว

    Sir ano po ginagamit n sensor sa kitchen?

    • @jub.tv123
      @jub.tv123  2 ปีที่แล้ว

      Heat detector sir pag sa kitchen hindi pwde ang smoke kasi mausok po ang kitchen..

  • @raymondcatamora5282
    @raymondcatamora5282 3 ปีที่แล้ว

    Nakaprogram din ba ang convincional

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว

      Alin ang tinatanong mo sir ang naka program ang conventional ang device ba? Kong ang device hindi... ang naka program lang kong device ay addressable na device.. lang....

  • @mennenbarredo5276
    @mennenbarredo5276 8 หลายเดือนก่อน

    Mahusay klaro ang pag babahagi ng kaalaman, salamat madaming salamat

  • @glomanpanaligan5694
    @glomanpanaligan5694 8 หลายเดือนก่อน

    Sir location mo

    • @jub.tv123
      @jub.tv123  8 หลายเดือนก่อน

      Nasa HUNGARY po ako sir sa ibang bansa,❤️❤️

  • @emmanuellimjoco4709
    @emmanuellimjoco4709 3 ปีที่แล้ว

    Boss, halimbawa po ihiwalay ko na sa circuit ng mga smoke detector yung manual call point. Pagsasamahin ko nalang sila puro manual call points halimbawa sa zone4, then separate circuit puro smoke detectors sa zone 1 at zone 2, kitchen area heat detectors sa zone 3. Pwede po ba iyon. Yung wala sila manual call point smoke at heat detector circuit

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว +1

      Wag mo pa hiwalayin sir isama mo parin ang smoke detector mo at sa manual call point mo at heat detector mo kasi baka wala kna mailagay sa terminal mo pag may another zone ka na idadagdag....

  • @reccakarl
    @reccakarl ปีที่แล้ว

    anong klaseng wire size po ba ang pwede gamitin sa Addressable Fire alarm? Pwede ba gamitin sa lahat ng detector at bell at facp iisang wire size?

    • @jub.tv123
      @jub.tv123  ปีที่แล้ว

      Hindi po sa mcp at SD 16 AWG. belden ang brand at sa BELL AT STROBE LIGHT 14 awg.

    • @reccakarl
      @reccakarl ปีที่แล้ว

      @@jub.tv123 yung bell po ba kailangan pa ng sariling power supply kahit nasa loop na?

    • @jub.tv123
      @jub.tv123  ปีที่แล้ว +1

      Deritso napo sa FACP panel kong malayo na pero kong malayo kailangan nio ng transponder..

    • @reccakarl
      @reccakarl ปีที่แล้ว

      @@jub.tv123 anong aparato po sa fire alarm loop yung kailangan pa ng sariling power supply? sounder po ba?

  • @lhanlhanantonio2462
    @lhanlhanantonio2462 ปีที่แล้ว

    Idol ano po trabho nyo bakit pati electrical hawak mo

    • @jub.tv123
      @jub.tv123  ปีที่แล้ว +1

      E & P ako sir electrical at instrument po sir...

    • @lhanlhanantonio2462
      @lhanlhanantonio2462 ปีที่แล้ว

      Ok sir salamat andito ka ba ngayon sa saudi gusto ko Sana lumipat sa electrical nasa piping kase ako ngayon gusto maka pag experience ng instrument Sana graduate po ako ng electrical technology

  • @ronnelcastro5031
    @ronnelcastro5031 ปีที่แล้ว

    nice po master napakalinaw nio magpaliwanag..newbie sa fdas and new subscriber nio po..Master tanong lang po.
    1.Sa addressable loop po tawag?sa conventional naman po is Zone?
    2.Sa addressable po master no need na po ng resistor no?thank u po master sana masagot newbie lng po sa fdas

    • @jub.tv123
      @jub.tv123  ปีที่แล้ว

      Depende po kong nag kaka error pwde din po lagyan ng resistor kahit addressable...sya...pero sa conventional mostly may resistor po...

  • @RRNARCISO-u4w
    @RRNARCISO-u4w 11 หลายเดือนก่อน

    Sir pag may module po saan po lalagay yung module?

    • @jub.tv123
      @jub.tv123  11 หลายเดือนก่อน

      Sa loob po ng FACP PANEL sir..

    • @RRNARCISO-u4w
      @RRNARCISO-u4w 11 หลายเดือนก่อน

      @@jub.tv123 sir pwde ba yun addressable yung mga module tas yung mga sd conventional?

  • @diannecoderesninja5535
    @diannecoderesninja5535 3 ปีที่แล้ว

    Sir nka seres ho ba yung line1 at line 2 ng zone 1 papunta zone 2. At ilang devices ang maximum sa zone 1

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว

      hindi sir individual dapat ang wiring...every zone.. sa device dapat 20 device lang every zone... para dka mahirap kag locate pag may trouble ang device mo

  • @arielmarapao1570
    @arielmarapao1570 3 หลายเดือนก่อน

    Thank you sir SA pag turo

  • @sirdenstv9747
    @sirdenstv9747 2 ปีที่แล้ว

    sir meron kami main panel sa guard house tas mag iindicate dun kung anong planta ang may alarm ..yung isang planta d nag iindicate ng alarm .. ano po possible problem at pano wiring papunta sa panel sa guard house.. san po yun nakacconnect sa panel na nasa planta kung san may alarm . aning terminal ang nagbabato ng signal sa main guard house?? salamat po

    • @jub.tv123
      @jub.tv123  2 ปีที่แล้ว

      Sir tanong ko muna ang device nio po ba na na d nag alarm may power po ba?at anong system po ng fire alarm nio?..

    • @sirdenstv9747
      @sirdenstv9747 2 ปีที่แล้ว

      @@jub.tv123 meron naman po sir may naginspection po kase pero d ko nakita actual sabi nya d daw po nagbabato ng signal dun sa panel na nasa guard house may possible daw po may putol na wire papunta sa guard house ..san po kaya nanakonnect yung wire nung sinasabi nya ? or aling connection terminals yung irerewire ko?

    • @jub.tv123
      @jub.tv123  2 ปีที่แล้ว

      Bakit walA po bang tagging?..

  • @apollofranza4410
    @apollofranza4410 2 ปีที่แล้ว

    Sir, halimbawa magdagdag ako ng detector sa bandang gitna ng system?? mababaho ba lahat ng configuration sa mga susunod na detector??

    • @jub.tv123
      @jub.tv123  2 ปีที่แล้ว

      Hindi namn mag babago yan sir pero e address mo sya... halimbawa last device mo ay 100 ang idagdag mo na address ay 101 102 103

  • @brothamacky2281
    @brothamacky2281 2 ปีที่แล้ว

    Salamat kuya sa iyong mga turo bagong kaalaman sakin to

  • @markangeloremot4392
    @markangeloremot4392 3 ปีที่แล้ว

    ano boss meaning ng mcp? hehehe thanks boss

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว

      Manual Call point po..ang mcp...pag sa ilaw sya ang switch mo

  • @weljosem9889
    @weljosem9889 2 ปีที่แล้ว

    Paano ba boss mag configure sa address f ever magpalit ka ng new smoke detector sa addressable type na fire alarm?

    • @jub.tv123
      @jub.tv123  2 ปีที่แล้ว

      Kailangan sir may pang program ka sa devices mo kong may depth swicth e setting mo lang syankong anong device no. Nya

  • @buildlastvlog6426
    @buildlastvlog6426 3 ปีที่แล้ว

    Sir kung tama po ako sa idea ko pwede ko pong i-convert ang wiring ng addressable sa conventional need ko lng lagyan ng Resistor dun sa dulo na bumalik sa panel salamat po sa pagsagot, 2nd question ko po sir pwd ba na hindi ko na palitan yung mga smoke na ginamit sa addressable kung i-convert sa conventional nlng salamat po

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว

      Nagka ka error din sir sa panel pag e convert mo ang addressable wiring sa conventional sir dapT pag addressable ay naka ring circuit sya

  • @jezzjimez9472
    @jezzjimez9472 3 ปีที่แล้ว

    Tadtad sa ads.. sobra namn ung ads..

  • @markguibo3611
    @markguibo3611 3 ปีที่แล้ว

    Sir sa addressable fire alarm system lahat na ba ng smoke detector.. Bell. Horn with strobe light.. Naka parallel lahat NG wiring connection??

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว

      Yes sir naka parallet at naka ring Ckt.

    • @markguibo3611
      @markguibo3611 3 ปีที่แล้ว

      @@jub.tv123 pero sa loop 1 smoke detector lang lahat at sa loop 2 serin with strobe light lahat. At sa loop 3 heat detector at manual call point tama ba sir?

  • @lueescobia4601
    @lueescobia4601 3 ปีที่แล้ว

    Sir pg sa conventional pg ng alarm si smoke detector mg alarm dn si bell, strobe??

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว +2

      Sir ang smoke d nag alarm yan..ang trabaho ng smoke ay to detect lang konh may usok...para maibato nya sa FACP. tapos tataas ang current saka mag alarm si bell at strobe
      ..

  • @marcianojrlofranco6234
    @marcianojrlofranco6234 3 ปีที่แล้ว

    Sa conventional at addressable sir may resistor ba ung mga sd Nila sa dulo.

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว +1

      Mosrly ginagamitan ng resistor sir ang Conventioanal fire alarm system lang kasi hindi naka ring ckt. Ang wiring nya, kaya may EOLR

  • @danieltayag9862
    @danieltayag9862 6 หลายเดือนก่อน

    Ang galing

  • @gerundionangel7293
    @gerundionangel7293 2 ปีที่แล้ว

    Salamat sir sa pagtutoro

  • @joselitopilien2073
    @joselitopilien2073 2 ปีที่แล้ว

    Sir Jub ask ko lang, pwede ba sa isang loop magkakasama ang smoke det.,heat det, mcp at strobe/bell?

  • @john23miranda
    @john23miranda 3 ปีที่แล้ว

    Ayos boss

  • @sarmientopepe6154
    @sarmientopepe6154 3 ปีที่แล้ว

    Salamat

  • @jhonerequejo374
    @jhonerequejo374 3 ปีที่แล้ว

    Idol request nman pano mag disable ng detector?

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว +1

      Pag gosto mo e disable sir. Ang detector tanggalin mo sa sa termination at e connect mo ulit ang cable na tinanggal mo sa device para tuloy ang flow ng current tapos e delete mo sya sa panel para walang truoble na nakalagay don...

  • @norway5306
    @norway5306 3 ปีที่แล้ว

    Sir ask ko lang kung pwede s una ilagy ang mcp kasunod nya yung smoke

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว +1

      wala ang problema sir kong San sa kanila ang mauna

  • @lawrencepaquinol1775
    @lawrencepaquinol1775 3 ปีที่แล้ว

    salamat po sir sa tutorial nyu.

  • @aldrinymana9147
    @aldrinymana9147 3 ปีที่แล้ว

    Kabayan pag convetional dba dpat may resistor sa end line ?

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว

      korek po

    • @aldrinymana9147
      @aldrinymana9147 3 ปีที่แล้ว

      Sir ..anung module gamit nyo sa supervisory ?

  • @bobbylubos3089
    @bobbylubos3089 3 ปีที่แล้ว

    Sir ask ko langpo kung naka experience na po kayo ng unprogrammed device data lumalabas sa HMI. Ano po kaya problema pagganito?

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว

      anong klase ba ang fire alarm system nio sir at anong brand Ng device nio?

    • @bobbylubos3089
      @bobbylubos3089 3 ปีที่แล้ว

      @@jub.tv123 sir EST3 na brand po addressable nmn po

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว

      sir try mo tanggalin at e re program mo ang device kong ganun parin try mo palitan and device...

    • @bobbylubos3089
      @bobbylubos3089 3 ปีที่แล้ว

      @@jub.tv123 noted po. Reprogram meaning ulitin ko po magassign ngmga address?

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว

      korek po sir baka defective na po ang device at d nya nabasa pag program.. try mo palitan ... marami po ba ang device nio na ganyan... at baka ang panel mo at device mo ay mag kaiba Ng brand...

  • @renatopat-ongay1831
    @renatopat-ongay1831 3 ปีที่แล้ว

    Pwde po bang mas malinaw tong diagram pls...

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว

      drop po kau ng gmail...para mabigyan kita ng malinaw na diagram..

    • @renatopat-ongay1831
      @renatopat-ongay1831 3 ปีที่แล้ว

      K sge po... At saka may tutorial video ba ng actual nito?

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว

      gagawa palang po sir....

    • @renatopat-ongay1831
      @renatopat-ongay1831 3 ปีที่แล้ว

      Ko po abangan ko po sir...

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว

      cge po

  • @charliekurtantiquera476
    @charliekurtantiquera476 3 ปีที่แล้ว

    Sir, paano po mag Program? Tnx

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว +1

      ano e program mo sir device Ng fire alarm or ang fire alarm panel

    • @charliekurtantiquera476
      @charliekurtantiquera476 3 ปีที่แล้ว

      Yung FACP po sana sir. Hehe

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว +1

      kailangan Ng laptop yon sir... e connect mo sa FACP... saka mo e program... ang no. Ng devices mo at location nya at aNg looping Ng alarm... kailangan tama ang pag program Ng device mo halimba notification... kgaya Ng detector device smoke or mcp. tapos yon alarm. BELL or strobe light..

    • @charliekurtantiquera476
      @charliekurtantiquera476 3 ปีที่แล้ว

      May ma rerefer kabang manual sir or Tutorial din po?

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว

      pag nag program na kmi sir... sa ngayon wala kami gawa sa fire alarm ang pag address lng Ng may depth switch ang mayron ako.....

  • @kawtskagid1198
    @kawtskagid1198 3 ปีที่แล้ว

    Sir,ano po dahilan,palaging umiilaw Ang Fire Alarm Ng isang zone Ng panel, palaging mg ring Ang bell pag e switch on ko

    • @jub.tv123
      @jub.tv123  3 ปีที่แล้ว

      Sir try mo palitan yan defective na yan sir ang device mo...

    • @kawtskagid1198
      @kawtskagid1198 3 ปีที่แล้ว

      @@jub.tv123 Ang sign na fire alarm sa FACP Ang umiilaw,Di Ang device..pinalitan ko na Ang mga devices sa zone na Yun,nilinis kopa baka may alikabok,,mgtrigger talaga sa panel