  • @raceestep6498
    @raceestep6498 ปีที่แล้ว +1

    Thanks for this, new to a seismic area and when they told me to go and install seismic bracing, I had no idea how they went about it.

    • @SprinklerFitting
      @SprinklerFitting  ปีที่แล้ว +1

      If you have any questions let me know .

    • @SprinklerFitting
      @SprinklerFitting  ปีที่แล้ว +1

      The video is showing how to attach to steel beams .
      If attaching to concrete then use 1/2 inch concrete wedge anchors .

    • @SprinklerFitting
      @SprinklerFitting  ปีที่แล้ว +3

      The sprinkler drawing should indicate where the bracing is needed .
      Generally every change of direction is a 4 way brace , then 40 ft is a 2 way ,then 4 way at 80 ft . Longitudinal and lateral .
      1 inch pipe is used for bracing under 7 ft , over 7 feet then use 1.25 inch pipe .