HOW TO CLEAR THE TROUBLE SHOWING MEMORY CORRUPT AT CARD 14 |JHAN2X TV VLOG#96

แชร์
ฝัง
  • เผยแพร่เมื่อ 16 ม.ค. 2025

ความคิดเห็น • 34

  • @عليعوض-ع3د
    @عليعوض-ع3د 2 ปีที่แล้ว

    Thanks brother I'm Make like the video and cleard the card 14 and no fault in the panel

  • @muhammaddanish3305
    @muhammaddanish3305 2 ปีที่แล้ว +1

    Hy , brother how many card in gent vigilon panel?

    • @JHAN2XTV
      @JHAN2XTV  2 ปีที่แล้ว +1

      Brother check my other vedio about gent panel.

  • @AhsanAbbas-c5x
    @AhsanAbbas-c5x 2 หลายเดือนก่อน

    Thanks brother its really worked

  • @عليعوض-ع3د
    @عليعوض-ع3د 2 ปีที่แล้ว +1

    Please how can solve this problem

  • @عليعوض-ع3د
    @عليعوض-ع3د 2 ปีที่แล้ว

    But when trying test for the fire Pressure the Call point fire not work and find this message ( Zone Disabled & loop stopped at card 4) and panel make allocated

    • @JHAN2XTV
      @JHAN2XTV  2 ปีที่แล้ว +1

      Yes that why the mcp not trigger because the loop4 or card 4 is off condition showing stopped..need to allocate the loop 4 to make normalize of all device in card 4 mains loop 4 need power up you should be allocated....ok

    • @عليعوض-ع3د
      @عليعوض-ع3د 2 ปีที่แล้ว

      We make allocated and backup for the loop and make test fire not wark and massage ( zone disabled (

    • @JHAN2XTV
      @JHAN2XTV  2 ปีที่แล้ว +1

      En able the zone 1-128 loop 4 or loop 1-6 all loop

    • @عليعوض-ع3د
      @عليعوض-ع3د 2 ปีที่แล้ว +1

      Thanks. Brother .how make enable?

    • @JHAN2XTV
      @JHAN2XTV  2 ปีที่แล้ว +1

      Go menu=/control/-en able-/zone=/1-128/loop 4 that is card or you make all loop 1=6 just follow that brother

  • @jkabayan105
    @jkabayan105 ปีที่แล้ว +1

    boss battery discharge trouble kahit ok naman yung reading ng dalawang battery ano kaya posibleng problema salamat boss

    • @JHAN2XTV
      @JHAN2XTV  ปีที่แล้ว

      reading ok pero yung amper rating wala na. try mo spark yung battery gamit kanang wire e short mo kung walang spark o mahina na wala ng amper rating yan. faulty nayan kailangan palitan kaya battery discharge.

    • @jkabayan105
      @jkabayan105 ปีที่แล้ว

      @@JHAN2XTV boss paano ma recover yung labeling ng device kasi recovery fail sya tapos patingin namin sa labeling niya not setup na xa

    • @JHAN2XTV
      @JHAN2XTV  ปีที่แล้ว

      nay video ako nyan how to recover label kailangan completo yung device para ma recover walang kulang sa loop..at check morin kung may back up naba yang loop na e recover mo check mo status card 0 makikita mo dyan kung naka back up, may roon din akung vedio nyan panoorin mo....pag mag type ka sa search sa youtube( how to back up) (How to recover ) Basta pag type HOW TO lalabas yung mga vedio ko.

    • @jkabayan105
      @jkabayan105 ปีที่แล้ว

      cge boss salamat

    • @jkabayan105
      @jkabayan105 ปีที่แล้ว

      boss paano alisin yung sector disable 1-32 kusa nalang cyang lumabas pag katapos ng allocation salamat

  • @hanysallam4690
    @hanysallam4690 ปีที่แล้ว +1

    Hi brother
    I have this faults
    1-Memory corrupt number 35 on loop 2
    2- Memory corrupt number 29 on loop 2
    3- Memory corrupt number 39 on loop 2
    How I can solve this?

    • @JHAN2XTV
      @JHAN2XTV  ปีที่แล้ว

      that device's brother is already faulty you need to replace it because the software of that devices is already corrupted..

    • @hanysallam4690
      @hanysallam4690 ปีที่แล้ว +1

      @@JHAN2XTV thanks brother
      I will replace it and update you

  • @jkabayan105
    @jkabayan105 ปีที่แล้ว

    boss anong dahilan bakit walang 24V power supply yung loop card kahit nakakabit siya salamat

    • @JHAN2XTV
      @JHAN2XTV  ปีที่แล้ว

      check mo lahat ng fuse sa board na kung saan nag bigay supply sa loop