How to read data from encoder by using PLC S7-300 FM350-1 high speed counter module part1

แชร์
ฝัง
  • เผยแพร่เมื่อ 29 ส.ค. 2024
  • Hello TH-camrs and Programmers,
    Today I have one video for show and share about how to read data from encoder by using PLC S7-300 FM350-1 high speed counter module.
    In this video everyone will understand about the basic create function and block for read data from incremental encoder by using PLC S7-300 FM350-1 high speed counter module part1 and also know clearly about how to wiring cable from encoder to PLC module.
    If everyone have any questions please kindly drop comment under my videos or contact me by:
    / plc.scada.7564
    Link below is related to PLC programming:
    Download software library for FM350x module
    drive.google.c...
    Sample project file
    drive.google.c...
    Download example project of Scaling AI, AO and PID control here:
    drive.google.c...
    TIA Portal V16 Scaling ANALOG OUTPUT and test with real PLC S7-300
    • TIA Portal V16 Scaling...
    TIA Portal V16 Scaling Analog INPUT and test with real PLC S7-300
    • TIA Portal V16 Scaling...
    TIA Portal V16 read data from encoder using PLC S7-300
    • TIA Portal V16 read da...
    Mix PLC Tutorial in 6 hours Simulation and Testing with real PLC & HMI
    • Mix PLC Tutorial in 6 ...
    SLC500 SEQUENCE Output explanations and test with real PLC
    • SLC500 SEQUENCE Output...
    Download project file
    drive.google.c...
    Allen Bradley SLC 500 Scaling Analog Input and Analog Output
    • Allen Bradley SLC 500 ...
    Link data between PLC S7-300 with S7-200 SMART and S7-200 via PROFIBUS-DP communication
    • Link data between PLC ...
    Download sample project file for example
    drive.google.c...
    Download GSD file S7-200 and 300 and S7-200 smart
    drive.google.c...
    drive.google.c...
    drive.google.c...
    drive.google.c...
    Link data between PLC S7-300 with S7-200 via PROFIBUS-DP communication
    • Link data between PLC ...
    Mix PLCs tutorial GE, S7-300, S7-200 in 11 hours
    • Mix PLCs tutorial GE, ...
    How to wiring 2 WIRE & 4 WIRE of temperature transmitter to PLC S7-300 Analog module 331-7KF02-0AB0
    • How to wiring 2 WIRE &...
    Proficy Machine Edition & Proficy HMI Workbench to create the program for start/stop motors sequence
    • Proficy Machine Editio...
    PLC GE tutorial how to add 2 VerSaMax remote I/O and testing
    • PLC GE tutorial how to...
    How to backup and restore project of SIMATIC HMI MP277 10" Touch by using USB flash
    • How to backup and rest...
    How to backup and restore project of HMI MP277 10" touch using LAN cable
    • How to backup and rest...
    Download software SIMATIC ProSave V15
    drive.google.c...
    Download software SIMATIC ProSave V16
    drive.google.c...
    TIA Portal tutorial with PLC SIEMENS start from beginner in 3hours
    • TIA Portal tutorial wi...
    How to connect and configuration hardware & software PLC S7-300 analog input with PT-100 and TC EP2
    • How to connect and con...
    How to connect and configuration hardware & software PLC S7-300 analog input with PT-100 and TC EP1
    • How to connect and con...
    GE PLC analog output module IC200ALG331 configuration and scaling by using Proficy Machine Edition
    • GE PLC analog output m...
    How to back up PLC LS model XBC-DR64H by using RS232C cable
    • How to back up PLC LS ...
    PLC S7-300 connect with HMI touch screen for control the motors step by step using timer
    • PLC S7-300 connect wit...
    PLC S7-300 connect with touch screen how to set and show timer on HMI
    • PLC S7-300 connect wit...
    GE PLC analog output module IC200ALG331 configuration and testing by using Proficy Machine Edition
    • GE PLC analog output m...
    GE PLC analog input module IC200ALG264 15Bit 15channel configuration and testing with current loop
    • GE PLC analog input mo...
    PLC XBC-DR64H how to upload program from PLC by using USB cable
    • PLC XBC-DR64H how to u...
    Read data from Encoder from PLC S7-300 and connect with HMI LS model XP-30
    • Read data from Encoder...
    LS HMI XP-30 connect with PLC S7-300 CPU 314C-2PN/DP
    • LS HMI XP-30 connect w...
    XG5000 SOFTWARE CONNECT WITH PLC LS XBC CREATE NEW PROJECT AND TESTING WITH REAL PLC
    • XG5000 SOFTWARE CONNEC...
    Thanks you so much for watching my video.
    I'm also sorry if I have mistake in this video.
    Please like share and subscribe my video also to get new notification and new videos.
    Good luck for everyone!
    See you next videos.
    Thanks!

ความคิดเห็น • 39

  • @tauqiranwar5699
    @tauqiranwar5699 3 ปีที่แล้ว +1

    Thanks for video, Excellent. Make video to read Speed through FM module

  • @motormadman
    @motormadman ปีที่แล้ว +1

    At about 31:00. Load 16 to DB1.DBD 12 will interfere with DB1.DBD14. Making it hard to reset value since DB1.DBD14 is for reseting. Write to DB1.DBB12 instead!

  • @bachelorkitchentamil4330
    @bachelorkitchentamil4330 3 ปีที่แล้ว

    Super very useful amazing video thanks bro

  • @Salirbeber1
    @Salirbeber1 ปีที่แล้ว

    Excelent video!! Thank you so much

  • @user-ov1qg3mp7c
    @user-ov1qg3mp7c 3 ปีที่แล้ว

    Thanks for the Video. It is very helpfull

  • @ebrahimmohammadpour4384
    @ebrahimmohammadpour4384 7 หลายเดือนก่อน

    Many thanks for the video ❤

  • @jasonjesmislang8929
    @jasonjesmislang8929 2 ปีที่แล้ว +2

    Hi thanks for the video.
    Can you make video for encoder positioning. How to interface the on and off degree.

  • @janetawuah2535
    @janetawuah2535 2 ปีที่แล้ว

    Thanks for this video...but please, where do you connect the power supply to the PLC and where do you connect your laptop to the PLC....
    What are the use of the PN port and DP ports

  • @saragabtni3744
    @saragabtni3744 ปีที่แล้ว +1

    merci pour le video mr , mais j'ai un Question s'il vous plait, est ce que on peut utilise the high speed avec plc 315 2pn/dp?

  • @pradeepmourya9362
    @pradeepmourya9362 3 ปีที่แล้ว

    Nice video
    Can u please make video of FM 352 for absolute encoder

  • @ebrahimmohammadpour4384
    @ebrahimmohammadpour4384 7 หลายเดือนก่อน

    I have already used fc2 in my project, can I change the name for the new encoder ?

  • @tauqiranwar5699
    @tauqiranwar5699 2 ปีที่แล้ว +1

    If you choose 5V incremental, it gives different options than selecting 24V incremental encoder

    • @generaltechnologyknowledge5165
      @generaltechnologyknowledge5165  2 ปีที่แล้ว

      Yes it should be different

    • @tauqiranwar5699
      @tauqiranwar5699 2 ปีที่แล้ว +1

      @@generaltechnologyknowledge5165 brother, I have to count 5V single pulse...Can I use "A" only in monitoring or is it possible?

    • @generaltechnologyknowledge5165
      @generaltechnologyknowledge5165  2 ปีที่แล้ว

      @@tauqiranwar5699 Yes that correct,
      Please select to A possition

    • @tauqiranwar5699
      @tauqiranwar5699 2 ปีที่แล้ว

      @@generaltechnologyknowledge5165 thanks, when I select Operating mode @ continuous counting it gives SF, but when I use single counting it gets OK..

  • @achrafaqdim9002
    @achrafaqdim9002 2 ปีที่แล้ว

    hi I have an application using an incremental encoder to measure a length and make the cut to the specific length. i use this module but i have probleme with sumulation can you help me please ?

  • @keysansa
    @keysansa 2 ปีที่แล้ว +1

    The module worked with the old project.
    When loading a new one (the hardware has changed), the module gives an error "module without parameters".
    I did everything as in the video.
    Still the same error.

    • @generaltechnologyknowledge5165
      @generaltechnologyknowledge5165  2 ปีที่แล้ว

      Dear sir,
      Please check power supply 24VDC supply to module connect correctly or not?

    • @keysansa
      @keysansa 2 ปีที่แล้ว

      @@generaltechnologyknowledge5165 auxilary supply ok. If i disconnect, module says : "no supply"

    • @thomasb4422
      @thomasb4422 2 ปีที่แล้ว

      @Key Sansa were you able to fix your problem? I have the same problem

    • @keysansa
      @keysansa 2 ปีที่แล้ว +1

      @@thomasb4422 Yes. Disconnect the encoder and configure the module without it. After that, connect the encoder.

    • @keysansa
      @keysansa 2 ปีที่แล้ว

      @@thomasb4422 All connections with power off procedure

  • @vorapobautomation9760
    @vorapobautomation9760 3 ปีที่แล้ว +1

    ใน TIA ทำยังไงครับ S7-1500

  • @shahaalom6891
    @shahaalom6891 3 ปีที่แล้ว +2

    How to use FM350 - 1 in TIA

  • @vorapobautomation9760
    @vorapobautomation9760 3 ปีที่แล้ว

    How to do with S7-1500 ?

  • @tauqiranwar5699
    @tauqiranwar5699 3 ปีที่แล้ว +1

    Please let me know how to read speed through FM 350-1

    • @generaltechnologyknowledge5165
      @generaltechnologyknowledge5165  3 ปีที่แล้ว

      Dear sir,
      We can use the formula to calculate speed by using encoder.

    • @tauqiranwar5699
      @tauqiranwar5699 3 ปีที่แล้ว +2

      @@generaltechnologyknowledge5165 any clue about formula?

    • @generaltechnologyknowledge5165
      @generaltechnologyknowledge5165  3 ปีที่แล้ว

      @@tauqiranwar5699
      Please test with this
      Electrical speed=[[(Max Frequency response(kHz)*1000(Cycles/minutes)]/PPR]*60(Sec/minutes)
      Example: Max Frequency response=120kHz, PPR=25mm/0.01mm=2500PPR(if the required linear resolution is 10 microns (0.01 mm), and a screw with a 25 mm lead is used) then
      Electrical speed=[(120*1000)/2500]*60=48*60=2880rpm
      I hope it work.
      Thanks

    • @tauqiranwar5699
      @tauqiranwar5699 3 ปีที่แล้ว +1

      @@generaltechnologyknowledge5165 Thanks a lot...
      In FM350-1 (6ES7350-1AH03....the operating mode RPM measurement is available....is it also need for this latest FM 350-1..

    • @generaltechnologyknowledge5165
      @generaltechnologyknowledge5165  3 ปีที่แล้ว

      @@tauqiranwar5699 Yes sir