680.26 Equipotential Bonding (swimming pools and similar)

แชร์
ฝัง
  • เผยแพร่เมื่อ 28 ก.ย. 2024
  • The rules for bonding the deck around a pool were clarified, then made (perhaps) less clear by a Tentative Interim Amendment (TIA)

ความคิดเห็น • 33

  • @jasondavies4073
    @jasondavies4073 7 หลายเดือนก่อน +3

    Great video. I have shared this with numerous local inspectors.

  • @Katiebelly123
    @Katiebelly123 8 หลายเดือนก่อน

    Very informative, and very clear. Seriously excellent presentation.

  • @julianfolk
    @julianfolk ปีที่แล้ว +3

    Thank you for the informative videos!

    • @MrMaxyield
      @MrMaxyield ปีที่แล้ว +1

      Ryan's the 🐐

  • @iaov
    @iaov ปีที่แล้ว +4

    Single #8 copper wire does not sound like a good idea. Most electricians won’t settle for “good enough “, we want things to be safe and bulletproof. Excellent video once again. Thanks

    • @vlad1889
      @vlad1889 ปีที่แล้ว +3

      Yea, I agree. There's nothing like running the minimum just to realize you have to tare everything up to do it again 😅

  • @4gizzle85
    @4gizzle85 2 หลายเดือนก่อน

    This is for conductive pools only and the single conductor method still seems to be accepted for nonconductive pools in the TIA correct?

  • @261Pro
    @261Pro 11 หลายเดือนก่อน

    Thank you Ryan 😊 great video..

  • @tymccart164
    @tymccart164 ปีที่แล้ว

    Hello Ryan,
    Concerning packaged hot tubs being exempt from an equipotential grid on the perimeter surface, what is the justification of the stipulation of the “top rim at least 28 inches above perimeter surface”? Is it assuming that a person could get out of the hot tub without using the typical non-conductive steps if this distance was

  • @josemancia3689
    @josemancia3689 ปีที่แล้ว

    I am confuse ..I have an exterior Panel for the pump , water heat sistem , lights etc ,the sub panel it’s feed with 4 wires gauge # 10… of course neutral separate with the ground … do I need to complete the bounding around the pool , conect all the metal bare , ladder , lights , Water heat , sum pump , etc and then conect to the sub panel ground together? ? Also I installed 2 rod for ground , but the NEC say is no necessary to a add the bounding to any panel ??

    • @josemancia3689
      @josemancia3689 ปีที่แล้ว +1

      😂😂 wow he gave me the answer on the video !!! Amazing help , pictures all the details Thank mr you are a master

  • @mikaelfehlberg6854
    @mikaelfehlberg6854 ปีที่แล้ว

    Thanks Ryan!

  • @chrisf3875
    @chrisf3875 ปีที่แล้ว

    Question for the inspectors, with input from all whoever installed swimming pool equipment particularly outside where you would have a combination panel/controller for all the associated pool equipment. I think i might have dropped the ball over the years, regarding article 250.32 structure supplied by feeders. once we install 2 posts in the ground and mount our pool equipment to it( now is this not a structure?), then pull our feeders. I do believe we're obligated to install a grounding electrode system as well. Never have done this or been called out by an inspector over this.
    Thoughts?

    • @MrSamsamsammy
      @MrSamsamsammy ปีที่แล้ว

      I’ve never had anyone require a ground rod for that. Just bond it to the panel feeding the pool panel. If it’s on the back of a detached garage or something, the garage feed would require a ground rod to be driven but I don’t think a couple of posts in the ground classifies as a “separate structure”

    • @chrisf3875
      @chrisf3875 ปีที่แล้ว

      I would agree with you that if you put it on the exterior of a garage,then the feeder originated from the panel from the garage that you wouldn't need one, other than the freestanding garage would need one. The example I'm trying to use is if you had to build something to mount your panel to, other than an existing structure.

    • @chrisf3875
      @chrisf3875 ปีที่แล้ว

      Also just add... Done many pools where the pool equipment is exterior Island(All out in the open) situation 30 to 50 ft away from the house.

    • @liferelation
      @liferelation ปีที่แล้ว

      If it stands alone separated from a garage or house it’s a separate structure that has been built. It Will require a grounding electrode system.

    • @chrisf3875
      @chrisf3875 ปีที่แล้ว

      I do tend to agree

  • @Electric_Sherlock
    @Electric_Sherlock ปีที่แล้ว

    Wait. There was testing, which yielded factual results, that further evidenced a single conductor was not good enough in which people were getting shocked and not able to use their pool and you and other “panelists” voted No?!?! …the purpose of the code is THE SAFE GUARDING OF PEOPLE & PROPERTY. If that’s not a direct example then idk what is. I’m glad the others got it right!!

    • @RyanJacksonElectrical
      @RyanJacksonElectrical  ปีที่แล้ว +2

      There was a lot more to it than that.

    • @timrobinson4330
      @timrobinson4330 8 หลายเดือนก่อน +1

      Dude what?! Please explain in further detail. Comments like this must be backed with something other than a Karen response. Ryan does a great job bruh

    • @shonashook2497
      @shonashook2497 2 หลายเดือนก่อน

      ​@timrobinson4330 Karen forgot there's a thing called HUMAN ERROR!😂 And whatever the process entails to be on this panel tells me you probably have an engineering degree, or an extended amount of electrical knowledge...so I'm sure there was a very good reason Ryan voted it down!

  • @tomp9447
    @tomp9447 ปีที่แล้ว +2

    Holly crap, the fact that 500k volts could be traveling through a pool is scary. Every one with a pool needs to watch this.

  • @nhicks8028
    @nhicks8028 11 หลายเดือนก่อน +1

    This is the best explanation of , why we need to bond pools correctly, I have seen on TH-cam.

  • @MrMaxyield
    @MrMaxyield ปีที่แล้ว +2

    Great work Ryan! It's always a pleasure learning from you, thanks!

  • @brianwinn-fd7ww
    @brianwinn-fd7ww ปีที่แล้ว +1

    Great information, Ryan. Thanks as always.

  • @KJSKKNP
    @KJSKKNP ปีที่แล้ว +1

    Thanks!

  • @tymccart164
    @tymccart164 ปีที่แล้ว

    @tymccart164
    2 minutes ago
    Hello Ryan,
    Concerning packaged hot tubs being exempt from an equipotential grid on the perimeter surface, what is the justification of the stipulation of the “top rim at least 28 inches above perimeter surface”? Is it assuming that a person could get out of the hot tub without using the typical non-conductive steps if this distance was

  • @eriknovak5452
    @eriknovak5452 ปีที่แล้ว

    Some areas around me above ground pools are popular and installed by the lowest bidder (often the pool salesmen never explain how much electrical work is required). Most of these installations are just on the unpaved grass, and therefore we will bury the #8 conductor 5" under the surface.
    How would this work with the copper grid? Im not arguing that it creates a better equipotential area, but would it be required to dig up a three foot path around the pool?

  • @liferelation
    @liferelation ปีที่แล้ว

    Thanks again Ryan, would like to know about the substantiation and corroboration for the pool shocks caused by the single conductor method. Could be just bad install. Loose joints, water not bonded etc.
    I would have fell on the minority side of this TIA also without corroborating evidence

  • @H750S
    @H750S ปีที่แล้ว

    About the 12:00 min mark. With the fence being that far away wouldn’t it be more of a danger to have it bonded so it could potentially have voltage on it? Seems more likely to have someone staring on the dirt outside it and touching it that someone in the water.

  • @seasonaldepression840
    @seasonaldepression840 2 หลายเดือนก่อน

    Nice video