Jaise hi gas compressor se nikal ke condenser me in hota hai us condition ke beech ke temp. Ko ham discharge temp. Kahte hai ... Condenser me jaise hi gas jayegi to uska temp. Down hone legega । Air ya water ke through
agar aap HVAC engineer honge to apko .. HVAC se related saare equipment dekhne honge like this 👉chiller .ahu .fcu .fahu. pahu. cooling tower. air cooled chiller water cooled chiller package unit .... aor electrical ka acha knowledge hona chaiyye iske sath sath apko har report banani rahegi . related to your field ... baki thoda bahoot plumbing ka knowledge...
Right hai .. but 0.5 digri celcius tab aa sakta hai jab chiller new ho aor water parameters under coc ho aor chiller low load pe running kar raha ho ... Isliye ham isko 1.5 to 4.0 digri celcius tak rakhte hai condenser approch ko ... 👉 Evaporater ka 0.5 to 1.5 digri celcius tak hona chiye
@@c4chiller9984 alag alag nhi bhai mene overall bataya h Condensor ka pata h 1.5 se 4 Nd Evaporator 0.5 se 1.5 Overall approach agr koi puch le toh 0.5 se 4*c bol sakte hena
You are great sir ❤❤ good video
Very useful vedio👌👍
thank you 👍
Sir ji AAP vrv system per video bnaye
How to shut down new type of chiller.. please make a vedio on it if possible. I was asked a question in an interview...
Recharge temp condenser temp ko hi bolte hai kya sir ji
Thanks
Sir ye sab option jo chiller ke display par dikha Raha ahi ye sab reading wala logbook me option available rahta hai ki nahi. Please tell me
Thank you sir
Bahut badhia
good job bro
Thanx
Sir ji Running Chiller ka reading dalo n load pe
Ok ....jii
What should be condenser and evaporator approach????
For chiller efficiency
M asking about its general values in normal operating condition ..of condenser and evaporator approach?????
Depend ur chiller efficiency or ton
Decharge temp ko hi condenser temp bolte hai kya sir
Jaise hi gas compressor se nikal ke condenser me in hota hai us condition ke beech ke temp. Ko ham discharge temp. Kahte hai ... Condenser me jaise hi gas jayegi to uska temp. Down hone legega । Air ya water ke through
Aur kitna hota hai decharge temp sir
Knowledgeable.........
thank you ...
Screw compressor me Konsa oil dalta hai sir ji
gas agar ...r134a hai usme to ... polyester oil use hoga
@@c4chiller9984 thanks sir ji
Thank you
Thanks sir
sukriya apka 🙏
Eva.and condensar saturation kitna hota h r134a
Eva 7 to 10 digri celcius
Condenser 35 to 40 digri celcius
Load pe kam ya jyada hota rahta hai sukriy
HVAC service engineer pr vedio banavo
service engineer me kya janna hai apko ??
@@c4chiller9984 service engineer ka kam kya hota... Kaisa routine hota hai...
agar aap HVAC engineer honge to apko .. HVAC se related saare equipment dekhne honge like this 👉chiller .ahu .fcu .fahu. pahu. cooling tower. air cooled chiller water cooled chiller package unit ....
aor electrical ka acha knowledge hona chaiyye iske sath sath apko har report banani rahegi . related to your field ... baki thoda bahoot plumbing ka knowledge...
apke neeche kitne bande HVAC technician hai ya jo bhi hai unko bhi apko hi Handel karna rahta hai ... with good combination 👍
@@c4chiller9984 thank u sir ji
Hii sir how r u
Im good ... Aap kaise hai ?
Sir aap ne course kiya h kya?
These parameters maintained daily?
Yes
Yes offcourse
Sir ap kam kaha sikhe the plz boliye
0.5 se 4 *c hona cahiye
Right yah wrong???
Ye approach temp. ???
@@c4chiller9984 yes approach h
Right hai .. but 0.5 digri celcius tab aa sakta hai jab chiller new ho aor water parameters under coc ho aor chiller low load pe running kar raha ho ... Isliye ham isko 1.5 to 4.0 digri celcius tak rakhte hai condenser approch ko ...
👉 Evaporater ka 0.5 to 1.5 digri celcius tak hona chiye
@@c4chiller9984 alag alag nhi bhai mene overall bataya h
Condensor ka pata h 1.5 se 4
Nd Evaporator 0.5 se 1.5
Overall approach agr koi puch le toh 0.5 se 4*c bol sakte hena
Yes .. overall aap bol sakte hai
Sir Chiller ka model number keya hai
York company
YKG5EXP95EP
Display password kitna sir
9675 for York chiller
What should be Evaporator and condenser pressure?????
If approch and pressure will increase
So chiller efficiency low .. chiller will not proper work
@@c4chiller9984sir i m asking about evp. And condenser pressure values in normal operating conditions??
@@thakursachin1547 depends how many loads ur chiller like 4 Ahus or fcus