Hello Endrika D. Marselino! At my project, I cant see variables in Programming mode. Have not IO Mapping category, as at your examle. How i can add Variable folder(with local or field variables)?
@@ArvindKumar-pi3rs you must have a backup data. If you don’t have, i think you must make a new program. You can download only paramater from plc using machine expert hvac installer
Range scalling of AI and AO is 0-1000. if you want to change AI range, you can change in Bios parameters. If you want to change AO range you can add basic add library
Why scaled values from AI adjusted as 4-20 mA showing at display of M172 as “divided on 10”? For example real temperature is 17.3 C degrees on display is 1.7 …
Teriakasih pembelajarannya
Bagaimana cara upload program untuk HVAC M172 ?
Mohon infonya
@@suganda2775 M172 tidak bisa upload program
Mantap 👍
M172 rada jarang disini, baru dapet satu buat ujicoba saya
Masih baru 2 tahun masuk indonesia
@@endrikamarsel Ada guide untuk baca analog ga ya? ini mau baca pressure transducer pusing saya 😅
aplikasinya beda sama M221, lebih repot
@@scroogemcduckenjoyer pressurenya pakai 4-20 atau 0-10?
how to get license for machinne expert hvac v1.4
Machine expert hvac is free software, you can regist on schneider web and login to machine expert hvac
Hello Endrika D. Marselino! At my project, I cant see variables in Programming mode. Have not IO Mapping category, as at your examle. How i can add Variable folder(with local or field variables)?
try to save project after you'r create variable
@@endrikamarsel Thank you, Endrika! All is working good!
mas ada kontak yg bisa sya hubungi
Di deskripsi
PLESE SUGGEST ME HOW TO UPLOAD FROM PLC
M172 not support to upload program from plc
@@endrikamarsel sir then how we can trouble shoot without backup.
@@ArvindKumar-pi3rs you must have a backup data. If you don’t have, i think you must make a new program. You can download only paramater from plc using machine expert hvac installer
How to Scaling Analog Input and Analog Output? Help me, please. Thank you!
Range scalling of AI and AO is 0-1000. if you want to change AI range, you can change in Bios parameters. If you want to change AO range you can add basic add library
Why scaled values from AI adjusted as 4-20 mA showing at display of M172 as “divided on 10”? For example real temperature is 17.3 C degrees on display is 1.7 …
@@r_iam what the display?
@@endrikamarsel Onboard display of M172. I move scaled variables to status variables, that am created for indicate on plc display
@@r_iam what value and range for your AI?