Heat Pump 12 Hight Pressure trips only in Heating

แชร์
ฝัง
  • เผยแพร่เมื่อ 16 ม.ค. 2025

ความคิดเห็น • 73

  • @robertcounts5300
    @robertcounts5300 ปีที่แล้ว +8

    I have been a HVAC service tech for over 30 years, I worked on every thing from 500 ton chillers to 9,000 btu ptec units and this guy knows his stuff! A welcomed sight. Thank you sir! Merry Christmas Ty.

    • @love2hvac
      @love2hvac  ปีที่แล้ว

      Thank you and Merry Christmas Robert!

    • @mikepan3189
      @mikepan3189 14 วันที่ผ่านมา

      Question: I have a 10 tonn2 stage water source heat pump, runs good at cooling mode! However, having head head pressure problem during heating mode!! Evaporator coil is clean, filter is clean, free return! Water temp during winter is around 90 degree supply! Only one txv! True suction pressure is at 120 psi during heating, and head pressure is at 580 psi and up, then trip the hps! Any thoughts will help! Much appreciated!

    • @robertcounts5300
      @robertcounts5300 10 วันที่ผ่านมา

      @@mikepan3189 is it a 2 stage compressor or 2 5 ton compressors?

    • @mikepan3189
      @mikepan3189 10 วันที่ผ่านมา

      @@robertcounts53002 5 ton compressor! Even with only one compressor running, it will still runs at above 500 psi of head pressure, 410a ! And it will trip at 550 psi!

  • @charlieromeo7663
    @charlieromeo7663 ปีที่แล้ว +2

    Great lesson,Ty. Thank you for yet another year of fantastic and educational videos. You sir “moved the needle” in HVAC education.

    • @love2hvac
      @love2hvac  ปีที่แล้ว

      Thanks Charlie!

  • @ulairecantea9231
    @ulairecantea9231 ปีที่แล้ว +5

    It's not just that you are a great teacher. You have such great energy with a big smile that is enjoyable to see. Thank you.

    • @love2hvac
      @love2hvac  ปีที่แล้ว

      I do love this stuff. So many things I had to learn the hard way over the years. Thanks for the compliment!

    • @bigxbudxbudda
      @bigxbudxbudda 8 หลายเดือนก่อน

      Nah this dude is so toxic is unbelievable. He literally spends his time on Facebook groups responding to every single post like the troll he is. We just kicked this twat from our group for attacking several business owners

  • @Powerstroke57
    @Powerstroke57 ปีที่แล้ว +2

    You are awesome! I wish I had someone like you to coach me when I was learning back in early 2000!

  • @1971omi
    @1971omi ปีที่แล้ว +2

    Thank you for your time and tips. I was at this call just last month 38 years old GE heat pump, maintenance tech in summer from other companies overcharged the system which was not even necessary because it was basement his suction was low apparently added a charge, therefore in heat mode they started having issues, again 2 companies went out there couldn't figure it out guess too intimidating bunch of old Relays, wanted to sell new system, I went out there figured it out overcharged, pulled some out, no issues since then.
    Integrity is gone

    • @love2hvac
      @love2hvac  ปีที่แล้ว +2

      Thank you for doing right by the customer!
      Unfortunately many of these companies want us to be salesmen instead of tradesmen.
      They will hold weekly sales training up rarely technical training.

  • @HfJax
    @HfJax หลายเดือนก่อน +1

    I learned tons of stuff on your channel thank you so much for making this videos, so glad I came across your channel pls keep making this videos and pass your knowledge

  • @chesstime356
    @chesstime356 ปีที่แล้ว +1

    TY your one of the best technician and teacher I do like your videos nice videos

  • @TomLawson05
    @TomLawson05 ปีที่แล้ว +2

    Great job Ty your a good teacher always like and learn from your videos have a merry Christmas and a blessed new year

    • @love2hvac
      @love2hvac  ปีที่แล้ว

      Thanks Tim! You have a Merry Christmas and Happy new year as well!

  • @mohamedtroufy6410
    @mohamedtroufy6410 ปีที่แล้ว +1

    Great informations. Learned many things from this channel. Thank you Ty.

    • @love2hvac
      @love2hvac  ปีที่แล้ว

      Glad to hear it!

  • @deanmartin1966
    @deanmartin1966 ปีที่แล้ว +2

    Good video Ty. Thanks for sharing.

  • @scoobtoober2975
    @scoobtoober2975 6 หลายเดือนก่อน +1

    ACIQ inverter heat pump. says during heating mode, initial turn on ever. re-torque the flares while hot. Interesting for sure. Thanks for the tips over the year.

    • @love2hvac
      @love2hvac  6 หลายเดือนก่อน

      Thank you for the heads up! I looked through a few ACIQ instaltion PDF's and I cand find that. Which model is it that shows that?

    • @scoobtoober2975
      @scoobtoober2975 6 หลายเดือนก่อน

      @@love2hvacquick start guide 2023 V1.0 on hvac direct site. For aciq-24-hpb. "To ensure no leaks are present startup the unit in heating mode. While the unit is operating retorque the flare
      adaptors (while unit is HOT). It is recommended to use a digital torque wrench."
      Also note the dip switch settings in this quick start are not correct. Read what's on the unit itself. I confirmed this with hvac direct. Side not too, the indoor coil ACiQ-24-ACL vapor side is 3/4 like the HPB manual calls for. Very nice unit, super quiet.

  • @jpenn727
    @jpenn727 ปีที่แล้ว +1

    Another great video. Thank you!!

  • @RobertLemons-z8g
    @RobertLemons-z8g 10 หลายเดือนก่อน +1

    Unit was overcharged, thanks again!

  • @bangtwister
    @bangtwister ปีที่แล้ว +1

    Thanks and Merry Christmas

    • @love2hvac
      @love2hvac  ปีที่แล้ว

      MERRY Christmas!

  • @MarcusHamilton-vk1tt
    @MarcusHamilton-vk1tt 5 หลายเดือนก่อน

    Such a blessing

  • @DaríoMartínez-w6w
    @DaríoMartínez-w6w ปีที่แล้ว +1

    I have also seen that somebody uses a copper pipe that is too small for the liquid line and acts as a big restriction.
    Other thing I have seen is that tam7 air handlers have something called enhanced mode which basically what it does is to run 50% airflow for the first minute or so to allow for the coil to warm up and it ends up going out on high limit for the first minutes until the blower is running at 100% airflow. What I do in those rare cases is to remove the blower delay.
    Merry Christmas Ty.

    • @love2hvac
      @love2hvac  ปีที่แล้ว

      This is true, there is a commercial building I consulted for that ran 3/8 to the wall then 1/4 most of them way and again 3/8 before the air handler. some over 100. It was a mess they hose to reduce the charge and deal with performance loss rather than change all the liquidines.
      I did not know you could turn the delay off on the Tam7. Thanks, will check it out.
      You have a Merry Christmas

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC ปีที่แล้ว +1

    Great video Ty. Thanks for sharing with us

    • @love2hvac
      @love2hvac  ปีที่แล้ว

      Thanks Jason! I have to get over there so we can hang out sometime.

    • @jasonjohnsonHVAC
      @jasonjohnsonHVAC ปีที่แล้ว +1

      @@love2hvac i would very much enjoy that

  • @tonycisneros296
    @tonycisneros296 3 หลายเดือนก่อน

    Great teaching!

  • @brianmcdermott2430
    @brianmcdermott2430 11 หลายเดือนก่อน +1

    Great tips, Ty. Thank you.

  • @rudyhildenbrand7842
    @rudyhildenbrand7842 ปีที่แล้ว +2

    Always enjoy your video’s. Always use to say when on doubt weigh it out!!

  • @CapsCup2012
    @CapsCup2012 ปีที่แล้ว +1

    Great video

  • @Hvacr123
    @Hvacr123 ปีที่แล้ว +1

    Mr.Ty Branaman The Mr.Beast of Hvac .
    Will you planing marking these great videos about walking cooler and walking freezer.
    I have been learning from a lot and apply on job make money for my family.
    I am gratefully appreciate your teaching!

    • @love2hvac
      @love2hvac  ปีที่แล้ว

      Yes I will be doing some cooler videos. I'm trying to get some old panels and parts to make a demonstration

    • @Hvacr123
      @Hvacr123 ปีที่แล้ว +1

      @@love2hvac Can’t wait.
      And thank you so much again Mr.Beast of Hvac/R

  • @edgar20109
    @edgar20109 4 หลายเดือนก่อน

    Thank you for sharing

  • @samersarah957
    @samersarah957 ปีที่แล้ว +1

    Hi Ty!
    In walk in cooler or freezer in wintertime should use weight method in charge or checking refrigerant?
    Thank you and have a bright future.🌹

    • @love2hvac
      @love2hvac  ปีที่แล้ว

      If it has a head master it will affect how it's charged in low ambient.
      With the variety of condensor evaporator matchups and accessories, it's difficult to get manufacture numbers on weighing in.
      In any case when it's pumped down, the receiver should never be more than 80% full.

  • @mikev.1034
    @mikev.1034 ปีที่แล้ว +1

    👍👍

  • @manschool4992
    @manschool4992 ปีที่แล้ว +1

    So if we have a pressure drop across the TXV we have a restriction. And since the relationship between pressure and temperature is there, we'll also have a temperature drop. Can we use clamp probes across our TXV to see restrictions like a liquid line filter drier? I just encountered this issue on a new install (I'm a warranty tech) and I opened up the TXV to get flow and it worked. But what's going to happen when we go back into cooling season, I'm sure I'll have low superheat and have to adjust it again. It seems like most of our problems are installation induced.

    • @love2hvac
      @love2hvac  ปีที่แล้ว +1

      A TXV is suppose to have a pressure drop across it when it's metering.
      When it's in bypass either an internal or external check valve should open bypassing the TXV so there is no pressure or temperature difference in that mode.
      In cooling mode the outdoor metering device is bypassed and the indoor will have a pressure and temperature drop.
      In heating mode the inside metering device should be bypassed and the outdoor metering device used.
      If you are saying you have a TXV indoor, and you had to open it all the way up to work in heating mode, then there is a problem. Either the check valve inside is stuck closed, an external check valve is stuck closed, or it is the wrong TXV for the application that does not have an internal check valve.
      #1 look to see. If it has an external check valve inside. If it does it may be stuck closed. If the external is stuck closed replace it and go to #4 If it does not have an external check valve...
      #2 check the TXV model number with the manufacturer. If it does not have an external or internal check valve for bypass, replace it with one that does.
      #3 if it does have an internal check valve and it's causing a restriction in heating mode, replace it as the internal check valve is likely stuck.
      #4 there is a reason it stuck so a system clean will need to be performed. Flush with nitrogen, check and clean the strainers of the indoor and outdoor metering devices, flow nitrogen while brazing, replace the biflow liquid line filter drier, pull a very deep vacuum and recharge.

    • @manschool4992
      @manschool4992 ปีที่แล้ว +1

      Wow! Thank you for such a detailed response. You're one of the few that actually responds and I learn so much when you do. HVAC is truly one of the most difficult trades out there. It's non stop.@@love2hvac

  • @spartan6005
    @spartan6005 หลายเดือนก่อน +1

    Mine seems to trip when the aux comes on only why drives the high pressure no air flow restriction could it be the RV ?

    • @makswell6993
      @makswell6993 หลายเดือนก่อน

      Does the fault code say high pressure lockout?

  • @Jose-o2x8t
    @Jose-o2x8t 10 หลายเดือนก่อน +1

    So what if liquid line pressure is slightly high in cooling but still cools and in heat runs for 5 min if that and trips and resets itself

  • @scoobtoober2975
    @scoobtoober2975 6 หลายเดือนก่อน

    Airflow cfm might be ok but if it can't get the room air and it's leaky before and after the unit, pressure can stay high.

  • @carltonthomas4819
    @carltonthomas4819 7 หลายเดือนก่อน

    Can you please do a video on heat pump going out on high pressure in cooling but work in heating

  • @kevintran5234
    @kevintran5234 23 วันที่ผ่านมา

    man i love to have this guy as my teacher, crystal clear.
    why is the heat pump running ac mode?

  • @cool_rick618
    @cool_rick618 2 หลายเดือนก่อน +1

    Just had a new indoor unit installed (carrier infinity 4t) mated up to a lennox xp21 4t hp and is having exactly this condition. Installer after checking pressures (good suction, high output) claims the only route forward is to take refrigerant out in the fall and add back in the spring or use gas-only. Any reason why or why not they couldn't install a charge compensator?

    • @love2hvac
      @love2hvac  2 หลายเดือนก่อน +1

      Mismatching basic systems like 10-14 seer would operate but it was never good and never meet the effecent.
      Mismatched high efficiency equipment is going to be an ongoing problem. Neither was designed to operate with the other.
      Should have never been offered as an option. Everything done next will be bandages and guesswork trying to solve engineering problems for 2 pieces that were never designed to work together.
      You likely have airflow issues but that's just a start. I would not touch that system as a tech unless you wanted it replaced and installed correctly .

    • @cool_rick618
      @cool_rick618 2 หลายเดือนก่อน

      @@love2hvac thanks for the advice!!

  • @kg7735
    @kg7735 ปีที่แล้ว +1

    He's looking at the wrong meter device!!! Ty should be looking at the meter device at the outdoor condenser. Remember Ty said everything works "great in cool mode" but in heat mode the system turns off due to high pressure. That would be the metering devise at the outdoor condenser. Merry Christmas all.

    • @love2hvac
      @love2hvac  ปีที่แล้ว +2

      You might want to rewatch the video and take some notes.
      Merry Christmas

    • @DJV94022
      @DJV94022 หลายเดือนก่อน

      On lennox the drier is inside the condenser unit (behind the liquid port) and right before it is the drier ..i found a bad drier the other day customers first time going into heat mode after their cooling summer

  • @philiph1234
    @philiph1234 ปีที่แล้ว +1

    Ty, what’s your feeling about looking for a restriction using temperature probes before and after any suspected part? ( drier, txv in bypass, etc)

    • @love2hvac
      @love2hvac  ปีที่แล้ว +2

      Temperature is a great way to find a restriction. Pressure is the best way but we don't usually have the luxury of a pressure port before and after. It is possible to have a restriction without a temperature drop as Bryan Orr found out in a lab test.

  • @user-nb5pw6nu4l
    @user-nb5pw6nu4l ปีที่แล้ว

    Hi Mr ty
    Is it possible to explain about the heat pump system with good pressure and the suction line is hot above 150 degrees but supply air temperature is not going to be above 80 degree

  • @tphvac87
    @tphvac87 3 หลายเดือนก่อน

    I have a question! Today I had a heat pump working okay in cooling mode but in heat mode the head pressure went past 600 psi, airflow is good coils and filters are clean…I was thinking the outdoor txv? Any thoughts? It’s a little 2 ton residential split system. According to your video I have a bad indoor txv? Please help! System definitely not overcharged was 60 degrees out today and my standing pressure was 61 degrees saturated. Residential Trane unit from 2016. Also had a 2-3 degree temp drop across my filter dryer, is that too much?

  • @eretza666
    @eretza666 ปีที่แล้ว

    can reversing get stuck and send high pressure on both lines(high and low ) on heating mode? both pressures rise equally on my gauge on heating mode, but on cooling mode works just fine

    • @love2hvac
      @love2hvac  ปีที่แล้ว +1

      Both lines will be high pressure in heating mode. You will have to use the true suction port for your suction pressure. I have a video on that in this same playlist.

    • @eretza666
      @eretza666 ปีที่แล้ว

      @@love2hvac yes, but pressures should be equal and rise the same, to the point to stop the compressor?

    • @love2hvac
      @love2hvac  ปีที่แล้ว +1

      @@eretza666 not all units have a high pressure switch.
      Reversing valves rarely fail but are often blamed. They are misdiagnosed way to much. I have been to 100's of calls where company A said it was a bad reversing valve and I find something completely different. In all the years I have had to change 6 3 of those where overheated when someone tried to change them, 2 from debrise and 1 that was leaking refrigerant to the atmosphere.
      A failed reversing valve cannot send high pressure to the suction and discharge at the same time.

    • @eretza666
      @eretza666 ปีที่แล้ว +1

      @love2hvac thanks , that's what I needed to know .Rules out reversing valve, now if the txv is not by passing, that should be the cause for pressure to rise if air flow is fine and everything else is clean (coil.filter)
      Done you think? Thank you for replying

  • @kevinpearce3281
    @kevinpearce3281 17 วันที่ผ่านมา

    English please?!?

  • @usahoangsatruongsa
    @usahoangsatruongsa 7 หลายเดือนก่อน

    All information presented good BUT BUT speak slowly PLEASE ! I had to pause the video all the times ! You're explaining complex technical issues so please give time for people green techs one as well as seasoned techs time to digest the info you're trying to convey Many many thanks.

  • @heatingairservices8708
    @heatingairservices8708 11 หลายเดือนก่อน

    what genius created micro channels save a buck or 2 on power bill ? less Refer needed to transfer heat ....I don't know & yes Carrier cheaped out putting piston In LL service Port directly connected & not @ distributor another Genus move -Harpy HVAC_KIng