These are the proper setups to do the debugging GREE GMV VRF system 1, db 01 A0 - System is in non - commissioning status 2, db 01 CC - the system does not set master unit, master unit need to set by dip switch setting ( off the main power supply before do the dip settings) 3, db 01 OC - the system successfully set a master unit and ready for commissioning 4, db 02 Ad - Assigning the address to all indoor units 5, db 03 01-04 ( outdoor units 1 to 4 nos) and this display will blinking- you have to manually press and confirm the modules or it will automatically calculate and move to next step, it means 01 master +1 slave or +2 slave or + 3 slave 6, db 04 1-80 ( indoor units 1 to 80 nos) display will blinking and if you dont conform by manually it will automatically calculate the indoor units qty and move to next step 7, db 05 OC - internal communication checking 8, db 06 OC - internal component check outdoors 9, db 07 OC - internal component check indoor units 10, db 08 OC - compressor preheating ( must power on the system for 12 hours before do the commissioning otherwise system not allow to move to next step ) 11, db 09 OC - Refrigerant check in the system 12, db 10 OC - outdoor unit valves status checking 13, db 11 - manually calculated refrigerant perfusion status 14, db 12 - unit commissioning startup 15, db 15 AC - system is in cooling decommissioning operation System will run approx 40 minutes and will come to below display status for normal opertion if there is no error codes when test run 01 AC OF - this display says system is ok and can switch by remote controller One you switch on following display will show for normal performance 01 AC ON
Thank you.Tawath vrv / vrf gana video danna
Kollo AC video kranna thawa vrv vrf... Godak wadagat
ඔයාගේ වීඩියෝ එක වටිනවා පුලුවන්නන් පිටින් දීලා තියන මියුසික් එක නැතිඋනානන් ගොඩාක් වටිනවා ඔයා කියන දෙවල් සමහරක් තැන් ඇහෙනවා මදි
How did change the mode lock from outdoor or by the remote
Ela machan ♥️
Make the music louder we still here the man a little
Sir I am facing some trouble gmv 5 remote showing fap
What this error mean
Ela
Thanks
Oyala kiyala dunna vidihatama kara thanx aiye danuqath kalata
Sahenna igena gaththa aiye
Mantaapppp
what cause gmv5 db 02 L7
Bro apitath support ekK thala yanna, math dunna ekak oyata
Tawa mewage vrf gana video danna
First of all before debugging must on the power for 12 hours to heat up the compressor oil, specially GREE not allowing to do the debugging
year
Aiya puluwan nm LG malti v vi oya program ekam karal pananko
LG malti V iv
DB 3 02 means not meaning of maximum 03 units only can be connect, this series maximum 04 units can be connect
i want contact to you
These are the proper setups to do the debugging GREE GMV VRF system
1, db 01 A0 - System is in non - commissioning status
2, db 01 CC - the system does not set master unit, master unit need to set by dip switch setting ( off the main power supply before do the dip settings)
3, db 01 OC - the system successfully set a master unit and ready for commissioning
4, db 02 Ad - Assigning the address to all indoor units
5, db 03 01-04 ( outdoor units 1 to 4 nos) and this display will blinking- you have to manually press and confirm the modules or it will automatically calculate and move to next step, it means 01 master +1 slave or +2 slave or + 3 slave
6, db 04 1-80 ( indoor units 1 to 80 nos) display will blinking and if you dont conform by manually it will automatically calculate the indoor units qty and move to next step
7, db 05 OC - internal communication checking
8, db 06 OC - internal component check outdoors
9, db 07 OC - internal component check indoor units
10, db 08 OC - compressor preheating ( must power on the system for 12 hours before do the commissioning otherwise system not allow to move to next step )
11, db 09 OC - Refrigerant check in the system
12, db 10 OC - outdoor unit valves status checking
13, db 11 - manually calculated refrigerant perfusion status
14, db 12 - unit commissioning startup
15, db 15 AC - system is in cooling decommissioning operation
System will run approx 40 minutes and will come to below display status for normal opertion if there is no error codes when test run
01 AC OF - this display says system is ok and can switch by remote controller
One you switch on following display will show for normal performance
01 AC ON
good it is debugging step
@@MrGruu-oz3pw I need Some help bro because I have 1 Gree VRFMV5 Unit but I don't no How I Can Commissioning this Unit
good
First of all if you are changing the dip switch settings, must switch off the power supply before changing any dip switch setting
GMV-335WM/H-X --- error HL?
@@thiensuutv1286 check compressor bord
@@thiensuutv1286 th-cam.com/video/j0gpqepKxiU/w-d-xo.htmlsi=Kd3EIT7HyMiP-EN1
I will send ful repair video
Creat video in english or hindi yaar
🤲🤲🤲
Po vrf3 AC model po error plese help
Speak engoish bro
Thank you.Tawath vrv / vrf gana video danna
Ela machan😍