Make sure drv is set 1. You can directly loop cm,p1 and p5, one of the option i have done there. The do your speed settings at F20,which is a jog,if at all you are running on constant speed. Incase you are running from outside reference 0-10v dc,just loop cm and p1 only.
Nice help video thanks
❤thank you sir
Thanks
Thank you sir
You are welcome
Hi sir I’m rana from Bangladesh.i living dubai. Control panel technician.
Get in touch with me through, johnmunam@gmail.com
Bagaimans bila muncul OCT,solusinya🙏
OCT is over Current.
You can check your motor.
Check the output cables whether there is a short.
@@John-qr4kf saya sudah mencoba melepas kabel ,tanpa motor. Inverter tetap masih kode OCT
@@ozilh2826Incase you have disconnected both the motor and the cable and still the OCT indication is there,then the IGBT (SCR/Thyristor) are faulty.
Dear sir' once switched on vfd its showed 0.00 only how to set the frequency
Make sure drv is set 1.
You can directly loop cm,p1 and p5, one of the option i have done there.
The do your speed settings at F20,which is a jog,if at all you are running on constant speed.
Incase you are running from outside reference 0-10v dc,just loop cm and p1 only.
You can as well watch another video of mine.