Hi Jose, You will need to confirm you are using a mA generating device. Some PIRECL units are for the Det-Tronics EQP and will not generate a mA signal. Once you confirm it’s a mA device, you will have to ensure you have a jumper in at terminals 5 and 6 with the signal wire on 7. Power is important as well. Terminal 2 is +24 and terminal 1 is the negative. If you are doing a 4 wire configuration, then the mA loop will need to be powered. Terminals 6 and 7 are the mA loop. The wiring diagrams can be found on page 10 of the manual. If you like, I can email this to you (lets connect via info@spartancontrols.com). - Leon Jackson, Field Service Specialist
I find this material very helpful.. think you guys.. personally I can tell Dettronics are the best detection device I ever see thinks again. Greetings from Algeria 🇩🇿
This video is very useful as we are doing f&g system commissioning
New subscriber watching here Al Khafji Saudi Arabia. Thank for sharing this video it's very helpful...
Thanks for subbing!
Hi Leon, congratulations! very good!
Thank you mr. Leon... For information...
Great short video to the point. You’re awesome. I’ve been trying to understand these at my work for years. This video made it all come together. Thank You 👍
Glad it was helpful!
Indeed this is a very great explanation ,I am doing a procedure and I will follow it ,thanks a lot quiet nice .
Txs very much
I need help!!! I'm currently working in one of them but its not giving nothing on my 4-20mA signal.
Hi Jose,
You will need to confirm you are using a mA generating device. Some PIRECL units are for the Det-Tronics EQP and will not generate a mA signal. Once you confirm it’s a mA device, you will have to ensure you have a jumper in at terminals 5 and 6 with the signal wire on 7. Power is important as well. Terminal 2 is +24 and terminal 1 is the negative.
If you are doing a 4 wire configuration, then the mA loop will need to be powered. Terminals 6 and 7 are the mA loop.
The wiring diagrams can be found on page 10 of the manual. If you like, I can email this to you (lets connect via info@spartancontrols.com).
- Leon Jackson, Field Service Specialist