    Input Isolation Transformer
    Lead Acid sealed maintenance free Batteries
    Inverter unit
    Servo-controlled Voltage Regulator in the Bypass line
    Automatic switching (Static Switch)
    Maintenance bypass switch
    Protective devices and other accessories
    Control and Display Unit for monitoring of parameters and control of UPS
    The solid-state rectifier/charger shall convert incoming AC power to DC power. The rectifier/charger output shall be fed to a solid-state inverter.
    The inverter shall convert the DC power into AC power which shall supply to the load. Upon failure of AC power or in case voltage drops below the operating range of battery charger, input power for inverter shall automatically be supplied from the battery with no interruption/disturbance in inverter output in excess of limits specified in this specification. At the same time, UPS shall energize an alarm circuit.
    UPS shall have a storage battery with 30 min + 30 min (for double battery bank) minimum backup capacity to meet the power requirements in the event of failure of the main supply. Battery Bank shall consist of 12 Volt battery blocks.
    Ezoic
    When A/C power is restored, the input power for the inverter and for recharging the battery shall automatically be supplied from rectifier/charger output without interruption/ disturbance in inverter output in excess of the limits specified herein (in these specifications).
    If the battery is exhausted before AC power is restored, the UPS shall shut down automatically.
    System Configuration
    A parallel Redundant UPS system shall comprise two sets of UPS streams each of a designed kVA rating and a common Bypass with servo controlled Voltage Stabilizer (SCVS).
    Each UPS shall be supplied with Battery banks of a size suitable for UPS rating. Both the UPS shall run in parallel and share the connected load.
    Ezoic
    The switchover from UPS to standby and vice versa shall be without any interruption. Bypass with SCVS shall come in line only when both the UPS are out of order and not in working condition.
    Rectifier / Charger Unit
    An input AC filter shall be incorporated into the rectifier or charger unit. The filter is not to be an add-on in front of the rectifier or charger.
    This filter’s purpose is to reduce the current harmonics feedback into the input AC line to not more than 5%. The filter is needed also to improve the input power factor so that it is 0.8 lag or better.
    The rectifier/charger unit shall be provided with the feature which does not allow input power required to go beyond 20% of the rated load upon resumption of AC power after operation of UPS on batteries.
    Ezoic
    Power semiconductors in the rectifier/charger shall be used with fast-acting fuses so that the loss of any one power semiconductor will not cause cascading failures.
    All fuses shall be provided with a blown fuse indicator with an alarm indicator on the control panel. The filter shall be adequate to ensure that the DC output of the rectifier/ charger will meet the input requirements of the inverter.
    Inverter Unit
    The inverter unit shall be an IGBT based capable of accepting the output of the rectifier and charger or the unregulated voltage of the battery and provide regulated rated AC output within specified limits. Means shall be provided to hold the inverter output frequency to +0.1% for both steady state and transient conditions.
    Total frequency deviation, including short time fluctuations and drift, shall not exceed +0.1% from the rated frequency. The inverter output shall stay synchronized with the static bypass line provided the static bypass line remains within +3 Hz of the nominal frequency.
    Ezoic
    If the line frequency goes outside these limits, the inverter is to break synchronization with the line and run on its internal frequency. When the line frequency returns, within limits, the inverter output is to automatically re-synchronize with the line.
    The rate of change of frequency is not to exceed 0.1 Hz per second. The unit shall be provided with an internal switch so that the synchronizing frequency range can be changed from +3 Hz to +1 Hz or to +0.5 Hz.
    Static Transfer Switch
    The Static Transfer Switch, using solid state devices, shall be provided to transfer the load between the UPS module and the static bypass line uninterrupted.
    Automatic static load transfers shall be initiated when a system overload is greater than specified here, a branch load circuit faults, or a fault within the UPS module occurs.
    If the static transfer was caused by an overload or branch fault and this condition was rectified, then the static transfer switch is to automatically re-transfer the load to the UPS module.
    The static transfer switch shall be sized to provide 125% rated load continuously. The switch shall also have an overload rating of 2000 % rated load for two cycles.