Why we use Resistors at the end of line on alarm security panels

แชร์
ฝัง
  • เผยแพร่เมื่อ 1 ก.พ. 2013
  • In this video , we talk about using resistors in securrity alarm panels. Why it is important to place them at the EOL or End of line. We also look at alarm basic circuits.
    The EOL allows the control panel to supervise the field wiring for open or short circuit .
  • แนวปฏิบัติและการใช้ชีวิต

ความคิดเห็น • 193

  • @dean7690able
    @dean7690able 4 ปีที่แล้ว +3

    Man this video is golden for me. Apprentice fire alarm tech in commercial. And this just made things real clear for me. Thanks a lot

  • @stormin2217
    @stormin2217 11 ปีที่แล้ว

    thank you for taking the time to show us ,,I will say thanks for all the thousands that watch your vids.

  • @paulburger2866
    @paulburger2866 8 ปีที่แล้ว +2

    Thanks for showing why this is better. Now it will be easier to remember whenever I'm in doubt again.

  • @stevenweii
    @stevenweii 8 ปีที่แล้ว +4

    this is a very useful video, i was trained before and knew the why EOL resistor is a must, but just in theory, you experiment and explain more details and prove what i was trained and told is pretty right..

  • @solitudeesttriste5396
    @solitudeesttriste5396 8 ปีที่แล้ว +21

    still there are a wonderful peoples in this world.thanks man for your help.

    • @Krakology
      @Krakology  8 ปีที่แล้ว +3

      +solitude esttriste NP thanks for watching

    • @rehanzahid9600
      @rehanzahid9600 4 ปีที่แล้ว

      @@Krakology can you explain about how conventional sounder activated in addressable fire system how sounder get signal from panel through smoke detector please explain or send some link for this

  • @SpewNation
    @SpewNation 7 ปีที่แล้ว

    I have two words for you.... Great video! the best explanation ive ever seen. Good job

  • @dannyf4995
    @dannyf4995 9 ปีที่แล้ว

    I'm installing a new Alarm system in my house (Pima - Hunter PRO), and couldn't understand their explanation about the ELO resistor, till now :-).
    Thank you so much for helping me understand this issue.

  • @snowcatxx87
    @snowcatxx87 7 ปีที่แล้ว +7

    Great video, explained it quickly and efficiently.

  • @MrDumonic
    @MrDumonic ปีที่แล้ว +1

    Love the explanation. I just use n/c loops. Especially now with wireless. If a wire is shorting out and I can’t use a different pair, sorry time to go wireless. Resistors are mostly used for supervision in commercial circuits where someone may try and tamper with wiring. But that’s more on the really big commercial side. Residential and small commercial we don’t use EOL. I hate EOL’s cause I find it harder to troubleshoot why a zone keeps false’ing. I work better with uninterrupted circuits. I totally understand why you would do this, but it just complicates things. Dealing with resistors at the panel is much more convenient.

  • @jamesrago2135
    @jamesrago2135 6 ปีที่แล้ว

    Thanks so much for taking the time to make this video. Very helpful and informative.

  • @TheRealAfroRick
    @TheRealAfroRick 11 ปีที่แล้ว

    This was excellent. I'm putting the in now to upgrade my home wiring setup. Will ensure no issues.

  • @jacksondeans8121
    @jacksondeans8121 ปีที่แล้ว

    thank you, explained it so much better than my textbook

  • @inspiredinvesting
    @inspiredinvesting 6 ปีที่แล้ว

    Really helpful, easy to understand. Thanks for taking the time

  • @francoisashton7156
    @francoisashton7156 4 ปีที่แล้ว

    Thanks, such a simple concept, but very effective. Well explained.

  • @Brandon-qr8zz
    @Brandon-qr8zz 6 ปีที่แล้ว +1

    Very helpful and easy to understand. Thank you!

  • @DiyintheGhetto
    @DiyintheGhetto 4 ปีที่แล้ว +1

    Hello Thank you for the video i know it's a older one but it helped me a lot. I never know what the resistors are for. But i saw a lot of other videos of people adding resistors but never say what they are for. So again thank you.

  • @akiladilusha
    @akiladilusha 5 ปีที่แล้ว +1

    This is very helpful. thank you!

  • @buzzyng
    @buzzyng 10 ปีที่แล้ว

    really appreciate the explanation. Very thorough and the demo helped solidify. thanks

  • @MarkCarline
    @MarkCarline 5 ปีที่แล้ว

    Very useful! Thanks for this!!

  • @MrAnhNo
    @MrAnhNo 9 ปีที่แล้ว +2

    Thanks for taking your time doing this video. This is my issue and I have no one to explain!! Thanks again

    • @TrongNguyen1994
      @TrongNguyen1994 6 ปีที่แล้ว

      Troy T Dinh hey bro. Can u explain this by vietnamese

  • @jdigi78
    @jdigi78 5 ปีที่แล้ว

    thanks for the video, was very confused why there were a bunch of resistors at the control panel. Turns out whoever did the install years and years ago never watched this video!

  • @tequilatyrant3992
    @tequilatyrant3992 2 ปีที่แล้ว

    This video is GREAT, thank you so much

  • @joshclarke7279
    @joshclarke7279 8 ปีที่แล้ว

    Great clip. Thanks mate.

  • @youzulf
    @youzulf 3 ปีที่แล้ว

    I understood that perfectly. Thank you.

  • @JohnDoe-ch5pf
    @JohnDoe-ch5pf 9 ปีที่แล้ว +5

    thank you for this explanation!! i have asked why to most of the people i have worked with but no one ever could tell me why.

    • @MrAnhNo
      @MrAnhNo 9 ปีที่แล้ว +2

      John Doe Because they don't know either or they just don't want you to know . Sad but truth :-(

    • @donlackie911
      @donlackie911 4 ปีที่แล้ว

      If you are in the industry and haven't figured this our on your own, you shouldn't be in the industry. It's not rocket science. The purpose of the EOL is the one of the basics.

  • @bignedu4871
    @bignedu4871 4 ปีที่แล้ว

    Thank you very much for this video.

  • @mariusbronikovskis8151
    @mariusbronikovskis8151 10 ปีที่แล้ว +1

    Thanks, this was really useful!

  • @NathanDelCamp
    @NathanDelCamp 2 ปีที่แล้ว

    Thanks for the explanation. Great work brother.

  • @craigleppan7164
    @craigleppan7164 2 ปีที่แล้ว

    Awesome man. Thanks. Nice and clear

  • @kenmorton2571
    @kenmorton2571 11 หลายเดือนก่อน

    Thanks for a great video,

  • @rudisammel8049
    @rudisammel8049 8 ปีที่แล้ว

    Very good information.
    Thank you for sharing

  • @alitajvidi5610
    @alitajvidi5610 8 ปีที่แล้ว

    You are an excellent teacher...

  • @apeyson1
    @apeyson1 2 ปีที่แล้ว

    Very helpful, thanks.

  • @shaunchetty4223
    @shaunchetty4223 3 ปีที่แล้ว +1

    Great explanation...thank you very much

  • @bkoz319
    @bkoz319 2 ปีที่แล้ว

    clear and concise, thank you

  • @chadrowland5234
    @chadrowland5234 ปีที่แล้ว

    If it were me, I would have the panel programmed for EOL resistor operation. The resistor offers the best of both worlds. Open and closed circuit operation. And, if you are an alarm hobbyist, the resistor is a must. You can tie resistors in series and do some cool stuff. The resistor is fun to play with in alarm systems. And, especially with fire zones...the trouble condition can be demonstrated to friends and stuff about what a trouble condition would look like on an alarm system. And, you can't do that without a resistor. And, especially if you have smoke detectors in your system, the trouble condition can be used as a reminder to put the smoke detector back. Especially me...everyone has done this, you've done this, I've done this. In fact, every time I do work in my house, I stand on a step ladder or a piano stool and twist off the smoke detector and drop it in a desk drawer and then put it right back when finished. Well, if you don't have the resistor, the trouble condition won't work and then, you could easily forget to put the smoke detector back. I would highly recommend keeping the resistor.

  • @MiddleBencher1989
    @MiddleBencher1989 3 ปีที่แล้ว

    Thank you for sharing valuable information 💖

  • @babumon8677
    @babumon8677 7 ปีที่แล้ว

    thank you very much man..You are an excellent teacher... Salute..

  • @janr.9035
    @janr.9035 7 ปีที่แล้ว +1

    thanks for your effort sir. u such a nice guy!

  • @rayanjan4666
    @rayanjan4666 3 ปีที่แล้ว

    Brilliant explanation 👍

  • @yousufsahib6690
    @yousufsahib6690 ปีที่แล้ว

    Simple and perfect explanation

  • @darynweir97
    @darynweir97 2 ปีที่แล้ว

    Great video helped me so much!

  • @crystalblueocean
    @crystalblueocean ปีที่แล้ว

    Thanks for the explanation

  • @TCJC1213
    @TCJC1213 7 ปีที่แล้ว +2

    very nice video now I can let my tech know why this is importent

  • @MrJasonrajesh
    @MrJasonrajesh 10 ปีที่แล้ว

    thanks, it's very helpful...

  • @jamesmeader2261
    @jamesmeader2261 7 หลายเดือนก่อน

    Great video 👍

  • @AliG.G
    @AliG.G 4 ปีที่แล้ว

    brilliant very useful thank you

  • @arbit3r
    @arbit3r 11 ปีที่แล้ว

    Excellent explanation.

  • @laneburgess1643
    @laneburgess1643 3 ปีที่แล้ว

    Great video.

  • @faiznordin7339
    @faiznordin7339 7 ปีที่แล้ว

    thnks for the lesson bro 👍😁

  • @jerrykr01
    @jerrykr01 11 ปีที่แล้ว

    Thank you for spending the time to make this. Clarified things for me alot.

  • @cheekymonkey2400
    @cheekymonkey2400 7 ปีที่แล้ว +3

    awesome video. I'm an apprentice. you explain it so well and make it so easy. I really don't the theory work but after watching this the theory of it is not so daunting.
    thanks for your video

    • @Krakology
      @Krakology  7 ปีที่แล้ว

      your welcome

    • @NinoNiemanThe1st
      @NinoNiemanThe1st 6 ปีที่แล้ว

      If you're going to do this professionally, it's a good idea to learn some (very) basic electronics. Makes understanding things like the purpose of EOL resistors really simple to understand (and things like this video would take 1 minute instead of 8). Without basic electronics, you'll be rote memorizing stuff, and will then get things wrong when you forget that stuff. Basic electronics is not too difficult - just think of water instead of electricity and each component will become clear. For example, a lot of people find voltage calculations with resistors in parallel difficult to grasp. How can putting 2 resistors allow MORE current to flow, and not less. If you think 'water', it all just makes sense - even capacitors and transistors!

  • @danieldsch
    @danieldsch 10 ปีที่แล้ว

    Thank you, your explanations are very clear and usefull for me, I have one question the movement detectors are wired like the smoke detector. (it has an open description). Thank you in advance.

  • @kunalnbhoyroo7994
    @kunalnbhoyroo7994 5 ปีที่แล้ว

    Thanks for explanation

  • @lazbl1979
    @lazbl1979 3 ปีที่แล้ว

    Awesome video

  • @Weaselspleen75
    @Weaselspleen75 8 ปีที่แล้ว

    This helped me thanks

  • @MrDumonic
    @MrDumonic ปีที่แล้ว

    Same thing with commercial cameras now a days. I’ll run the wire, install the cameras and do all the connections. But don’t ask me to get it online. Cameras are usually all plug in play. But when they want to secure it all and get it working over a local and external network, that’s up to the IT guys.

  • @anwarktm1
    @anwarktm1 8 ปีที่แล้ว

    thank you very much man.. Salute..

    • @Krakology
      @Krakology  8 ปีที่แล้ว

      your welcome

  • @GelebFlamebringer
    @GelebFlamebringer 9 ปีที่แล้ว

    Nice video thanks

  • @aksinghheikham4096
    @aksinghheikham4096 3 ปีที่แล้ว

    nice explanation

  • @danieldsch
    @danieldsch 10 ปีที่แล้ว

    Ok, I will wire it in series and see what happen. Thank you.

  • @ivorubenis3247
    @ivorubenis3247 6 ปีที่แล้ว

    thanks it was good to know

  • @dstankovic973
    @dstankovic973 10 ปีที่แล้ว

    nice explanation tnx

  • @TomVereecke
    @TomVereecke 7 ปีที่แล้ว +3

    You can also use normal closed contacts and use 1 resistor in series with the contact and one parralel to the contact. For example if you use 3K3 resistors, in a normal non alarm state it will read 3K3, in alarm state it will read 6K6, when the conductor is cut it will read out off limit, and when it's shorted it's about 0 ohms. It's the standard way of working here. For fire detectors which are normally open we use the same method as you do.

  • @ajitmacwan4974
    @ajitmacwan4974 5 ปีที่แล้ว

    Very nice video

  • @ochungochieng8863
    @ochungochieng8863 2 ปีที่แล้ว

    Good evening. Can you incorporate a maglock into the alarm panel so that we have an intruder detection as well as an access control working togethee

  • @Krakology
    @Krakology  11 ปีที่แล้ว

    Glad it helped

  • @rahulmali1978
    @rahulmali1978 11 ปีที่แล้ว

    Thank you sir.

  • @jamie1400
    @jamie1400 4 ปีที่แล้ว

    Hi, can you confirm on a smoke detector that the resistor goes across the positive and negative terminals. If so can I use the spare negative and positive terminals on the device itself?

  • @mr702s
    @mr702s 4 ปีที่แล้ว

    Thank you

  • @brendanchase9068
    @brendanchase9068 3 ปีที่แล้ว

    Thanks!

  • @MichaelRadie
    @MichaelRadie 9 ปีที่แล้ว

    thanks explains alot.

  • @MrLibbyloulou
    @MrLibbyloulou 2 ปีที่แล้ว

    O.k.....i have just bought a jet ski, i need to run a wire from my house alarm panel, about 10ft long to the jet ski, am going to loop a wire too and from the ski, i suppose i would (using two wires) run say my blue out to the ski, with my red, (the wires i use) and could just wire either end to a resistor to do the same job.....? it's only like running them to a magnet.....?.....yes...? and if that would be fine, what resitor would you recommend......thank you for your help.......

  • @phuochau88
    @phuochau88 10 ปีที่แล้ว

    thanks much!!!

  • @jwj2xx4
    @jwj2xx4 10 ปีที่แล้ว

    Usually with just one resistor at the last sensor in the loop/furthest from the panel, but some systems (like the Vista series) allow for using double loops with two resistors on a single zone.

  • @rahulmali1978
    @rahulmali1978 11 ปีที่แล้ว

    Please load more videos related to F & G system wiring.

  • @phillipjessop2902
    @phillipjessop2902 3 ปีที่แล้ว +1

    Thanks. Been looking for an answer for the need for a resistor. My door contacts also have a resistor between terminals? Don't know why. Also, are resistors directional? Regards Phillip

    • @Krakology
      @Krakology  3 ปีที่แล้ว

      resistors are not directional. Diodes are. For the reason for your contact to have the resistor across both terminals.. Well had to say without more info.. My first 2 thoughts.. A, maybe normally open contact, b, they are trying to correct the resistance with a seprate resistor.

  • @marko7843
    @marko7843 8 ปีที่แล้ว

    That's a great demo! My only question is why they bothered to put the "eol" resistors in my control panel, where there's no difference between a closed switch and a short... Just a necessary current limiter?

    • @Krakology
      @Krakology  8 ปีที่แล้ว +1

      +Mark O some panels cant be programmed to not look for the resistor.. it needs to see that load.. so people cheat and put at panel.

  • @seanbrooks5012
    @seanbrooks5012 9 ปีที่แล้ว

    Kraka, How many of these sets do you think i would need to run an RV refrig, say a 31" lcd, a small water pump and maybe a radio with some surround speakers?

    • @ESkateLP
      @ESkateLP 8 ปีที่แล้ว

      +Sean Brooks you need 42

  • @michaelstolman536
    @michaelstolman536 2 ปีที่แล้ว

    Great explanation as to why the resistor should be at the end of the line but it is a pity that magnet manufacturers make allowance for these in the magnet switch.

  • @ruiftavares
    @ruiftavares 3 ปีที่แล้ว

    Good afternoon, can I please ask for your help? I have a Ademco Microtech Galaxy 8 C055 alarm, and want to attach a GSM communicator to it. It can work with either NO or NC outputs. I just dont kmow in wich terminals I have to connect the communicator to the alarm, and can´t find any schematics online. Can you help me? Thanks in advance.

  • @calebphipps164
    @calebphipps164 5 ปีที่แล้ว

    nice!

  • @marcisaacs9407
    @marcisaacs9407 ปีที่แล้ว

    Great

  • @drumrboynoid
    @drumrboynoid 6 ปีที่แล้ว

    Thanks for the video. I'm installing my own alarm system at my house. I'm all caught up in the thing about how people can fool the magnet switches, like the ones in your video. Can you recommend a good magnet switch for me? Much appreciated.

    • @philharrison8857
      @philharrison8857 5 ปีที่แล้ว

      There are lots of comments about magnetic switches and how to fool them, or quality. Can I just say, you should only use them as a means of being able to be sure a door is closed when the alarm sets, and to be able to initiate a countdown entry timer from the final exit door. Very rarely these days to people break doors down when breaking in, far easier, and in most cases quieter, to push a panel out of a door, or go through a window in which case the contact isn't broken and the alarm is not triggered. Motion detection is really what is required, of good quality of course.

    • @globalmagicnation8464
      @globalmagicnation8464 3 ปีที่แล้ว

      @@philharrison8857 Actually most break ins are people kicking in back doors. Hardly hear about window break ins. I get my info from jobs I do for the people who have gotten broken into.”

  • @RainierWestVideos
    @RainierWestVideos 10 ปีที่แล้ว

    I have a nice little supervised (1.8 KOhm) four zone panel built in to a programmable keypad. I ran all my wiring to a closet behind the keypad and thru-walled the keypad feeds to my closet backbox. This mini-panel also has two supervised open inputs (emerg/fire) and a fixed/momentary contact output for aux out.
    I have two doors that must be individually zoned, that's zone one and two. I have eight windows, four on zone three and four on zone four. Each run was a homer AND each contact was supervised at the contact (1.8 KOhm resistor). Now, I've discovered a problem, as you can imagine. The panel wants to see 1.8K, the series-ed windows on each zone offer 7.2K of resistance which looks like a short to the panel.
    Do I have to remove three of the resistors on the window contacts so that the panel only sees one resistor? Or maybe, I should have divided by four and put .45KOhm resistors on each window, the combined offering 1.8K at the panel. As long as the zone threshold sees an open (drop of .45KOhm), this should work. Putting the windows in series (at the back box) won't work - do the math.
    Didn't USP have built-in resistored contacts at one time?

    • @Krakology
      @Krakology  10 ปีที่แล้ว

      Most people only use one resistor . The rest leave off.

    • @RainierWestVideos
      @RainierWestVideos 10 ปีที่แล้ว

      Kraka069
      That was just a fun question. I worked in the security alarm industry for 30 years. The panel I was referring to was a modified MOOSE keypad system. Great little panel. They had some issues with sub-standard power supplies back in the '80's, fixed that and became a pretty good choice for the low end market. I preferred NAPCO (they still around?). Solid performance, many featured and properly priced. They weren't RADIONICS but I preferred their dealer network over RADIONICS.

    • @Krakology
      @Krakology  10 ปีที่แล้ว +1

      napco sux. GE or ademco gets my vote

    • @RainierWestVideos
      @RainierWestVideos 10 ปีที่แล้ว

      Kraka069
      well, i don't have any idea what panels are good or bad anymore, but we always referred to the junior installers and do it your selfers to ademco. real pro's used napco, radionics, dsl, dsr and accutech before your time. nowadays ademco might be the best, but it was the stepping stone alarm panel of its day.

  • @ubluis
    @ubluis 4 ปีที่แล้ว

    First time i see it can cut or open a line just only pressing the cable with a plier....can you explain that? greets

  • @ChristopherJones242
    @ChristopherJones242 10 ปีที่แล้ว +2

    This isn't only about preventing wiring trouble. If I was a burglar, hell bent on getting access to a building to steal something, I could theoretically get past the alarm if I really wanted to. Perhaps the building is open during the day, I could go inside and short out some window sensors. Or at night, cut or break the glass out of a window, reach through, and short the sensor. Then, you can open the window without setting off the alarm. With the end of line resistor, if somebody were to do this, as soon as you short the wire, the alarm would go off.

    • @NinoNiemanThe1st
      @NinoNiemanThe1st 6 ปีที่แล้ว

      @Christopher Jones: I think that's what they are for in most cases, but that wasn't mentioned in the video. In fact I'm not sure the video really summarised why EOL resistors exist at all, more just a non-electronics discussion of what happens when you put EOL resistors into a circuit.

    • @MrLibbyloulou
      @MrLibbyloulou 5 ปีที่แล้ว

      You can't cover the RIGHT sensors like you used to...they go into tamper even with the alarm unset...

    • @philharrison8857
      @philharrison8857 5 ปีที่แล้ว

      @@MrLibbyloulou what you mention here is anti masking, these are sensors of a high quality and grade which have this feature and are wired in line with EOL resistor wiring, an extension of it if you like.

  • @Krakology
    @Krakology  11 ปีที่แล้ว +1

    Glad i could help

  • @MattZiggy
    @MattZiggy 6 ปีที่แล้ว +1

    Basically what he's saying is by using a resistor at EOL you are supervising the entire wire and device which is the correct way of wiring a security device.

    • @MattZiggy
      @MattZiggy 3 ปีที่แล้ว

      @D Smith Which is the wrong way to supervise a circuit. It's the lazy way. No disrespect, but at that point, there's no reason to have a resistor at all. You're not truly supervising anything. Resistor at EOL is actually supervising the entire zone. Resistor at the panel is not supervising to EOL device. In commercial you should not being sv at panel. Reisi I don't even think SV is necessary but to each their own.

  • @coloradowilderness3139
    @coloradowilderness3139 5 ปีที่แล้ว

    Very nice explanation. Excuse me , What is written on Your Left Hand ?

    • @Krakology
      @Krakology  5 ปีที่แล้ว

      that says jacob in Japanese . other arm says chase, My boys.
      i now also have aurebesh that says my daughters name as well

  • @graphguy
    @graphguy 11 ปีที่แล้ว

    Many sensors are wired in series on one zone, not sure how a control panel would need to be or could be programmed and wired to do resistors at each sensor for an in series closed circuit zone.

  • @MrLibbyloulou
    @MrLibbyloulou 5 ปีที่แล้ว +7

    Brilliantly explained...you may of saved someone going to prison {:-) haha

  • @rythem17
    @rythem17 10 ปีที่แล้ว

    commercial we always use at device also unless doing some-kinda special bypass switch or something

  • @RadioReprised
    @RadioReprised 7 ปีที่แล้ว +2

    Am I the last guy left who still services Morse MDC-16's!.....one of the best systems ever. And then there's the Optex-Morse Genysis POS!

    • @Krakology
      @Krakology  7 ปีที่แล้ว

      RadioReprised yup

    • @RadioReprised
      @RadioReprised 7 ปีที่แล้ว

      LOL!...I have about 300 of them monitored and like a Radionics 41 or 61..........they just won't DIE!

  • @starlite528
    @starlite528 4 ปีที่แล้ว

    The best reason for putting the resistor at the device is to monitor the wire for tampering while the alarm system is armed.

  • @pointyduck6422
    @pointyduck6422 7 ปีที่แล้ว

    So do you have a video how to wire eolr on fire strobe

    • @chrisledbetter3762
      @chrisledbetter3762 7 ปีที่แล้ว

      I don't think a burglar alarm system requires bell circuit supervision......... fire alarms it just jumps across your data circuit at the end of line.........for a class B circuit.............. but fire alarms you can have class A circuits and class B circuits.................... class A circuits you loop the circuit back to the panel and monitor the circuit from the panel and put your resister in the panel.... you also have to program the fire system to which type you use

  • @thepumpkingking8339
    @thepumpkingking8339 9 ปีที่แล้ว

    It's all in the name..

  • @NinoNiemanThe1st
    @NinoNiemanThe1st 6 ปีที่แล้ว +1

    Good demo with the multimeter, but the explanation was kind of all over the place with the major point not made clearly. If you understand high school physics, easiest way to thing about EOL resistors is: they allow an alarm system to detect THREE states via a voltage read instead of two. The states are: 1) Open circuit - no current/voltage, 2) Normal close, with a reduced voltage due to the resistor and 3) Abnormal close, ie. a full short without the resistor being in-line. Of course, your alarm system needs to be able to measure these 3 states, but almost all have EOL resistor detection to do so.

  • @ghisayawan
    @ghisayawan 7 ปีที่แล้ว

    Hello I have a DSC 1832 alarm system. I have a motion sensor that keeps tripping the alarm off at times. I replaced the sensor and still the alarm is being set off. Can you please help?

    • @Krakology
      @Krakology  7 ปีที่แล้ว

      Darin Ghisayawan whats in the room? Animals? Balloons or anything that moves? A/c vents? Whats the environment like?

    • @ghisayawan
      @ghisayawan 7 ปีที่แล้ว

      Kraka069 it's in my attic, so there's not much there. No animals, people or anything. The system will arm Ok and then sometime after the alarm will sound, very annoying when it goes off at 3am. Sometimes the zone will be open and it has to be bypassed to arm the system.

    • @Krakology
      @Krakology  7 ปีที่แล้ว

      Attic is not the place for a motion detector. If you're worried about someone breaking in through the attic to contact switch on your attic hatch

    • @chrisledbetter3762
      @chrisledbetter3762 7 ปีที่แล้ว

      unless it is a microwave motion detector it shouldn't be in an attic, and if it is microwave, it can go through walls like sheetrock.. and is not normal to use in a residential site....... more than likely it isn't a motion detector in your attic, if it is anything, it is a heat detector, if it is on the alarm, but the fact you can arm it, .... if it is a heat detector, it would be a fixed temperature heat detector and would only be able to go into alarm once, and you wouldn't be able to get it out of alarm to arm it again until it was replaced.............its probably not that...... but you said you replaced the sensor, so I'm guessing you know for sure it is a motion in the attic?.................there are a few different types of motion detectors... Infrared and microwave are the two most common....... no one would put infrared detectors in an attic, it gets hot and stays hot, all the motion would see is red all the time and not pick up body heat.....microwave is usually for commercial jobs, where the motion has to see through boxes and around corners and gets stopped by concrete walls..... people put them in houses sometimes, but not often., ... you said it is going off at night when you sleep and if it is a motion and was programmed as a motion in the panel, it would get bypassed when you arm the system in stay mode to sleep, so a motion anywhere wouldn't set it off at 3 am, if the system was armed and you were sleeping............................. I think what your looking at in the attic isn't connected to the alarm system, its not common to put motions in attics, and an 1832 is a normal residential panel.............. ive seen a lot of homeowners think their AC powered smoke detectors are hooked to the system, or think some other device is part of the alarm, when it isn't...... the only thing I don't understand is what you replaced........... if it turns out to be a microwave detector somehow... they don't just go off with animals or people, they will bounce microwaves off anything that moves, so the slightest breeze could move insulation and make it go off...... the infrared one would have to see body heat move................. ive heard people say balloons but I don't see how, its helium, its not hot, unless it moves in front of a 60W light and distorts the heat signature............ an AC vent or sun on a window would do it... not likely at 3am in an attic........................ if it really turns out to be a motion detector in your attic, and it for sure is the zone tripping, you might have squirrels in your attic, they get in there a lot....................... did you have the alarm company install the motion in your attic or was it there when you moved in....... you would of had to specifically request a motion in the attic..... so if you did, why?

  • @stevegonzales4411
    @stevegonzales4411 8 ปีที่แล้ว

    Great video. Now I know that my installer totally screwed up my entire system!!